Kidde Smoke Alarm 0916 User Manual

For models: 0916, 440375  
Smoke and Fire Alarm  
User’s Guide  
9 Volt Battery Operated Smoke Alarm with “HUSH” Control to  
temporarily silence nuisance alarms.  
Thank you for purchasing this smoke and fire alarm. It is an  
important part of your familys home safety plan. You can trust  
this product to provide the highest quality safety protection. We  
know you expect nothing less when the lives of your family are  
at stake.  
For your convenience, write down the following information.  
If you call our Consumer Hotline, these are the first questions  
you will be asked.  
Smoke Alarm Model Number (located on back of alarm):  
Date Code (located on back of alarm). National Fire Protection Association  
(NFPA) and the manufacturer recommends replacing this alarm ten years  
from the date code:  
Date of Purchase:  
Where Purchased:  
LISTED  
Download from Www.Somanuals.com. All Manuals Search And Download  
This product is designed to detect products of combustion using the ionization tech-  
nique. It contains 0.9 microcurie of Americium 241, a radioactive material. Distributed  
under U.S. NRC License No. 32-23858-01E. Manufactured in compliance with U.S.  
NRC safety criteria in 10 CFR 32.27. The purchaser is exempt from any regulatory  
requirements.  
For mobile home installation, select locations carefully to avoid thermal barriers that  
may form at the ceiling. For more details, see MOBILE HOME INSTALLATION  
below.  
When mounting a alarm on the ceiling, locate it at a minimum of 4” (10 cm) from  
the side wall. (see Diagram A).  
WARNING! BATTERY DOOR WILL NOT CLOSE UNLESS BATTERY IS  
PRESENT. REMOVAL OF BATTERY WILL RENDER THE SMOKE ALARM  
INOPERATIVE.  
When mounting the alarm on the wall, use an inside wall with the top edge of the  
alarm at a minimum of 4” (10 cm) and a maximum of 12” (30.5 cm) below the  
ceiling. (see Diagram A).  
IMPORTANT! READ ALL INSTRUCTIONS BEFORE INSTALLATION AND KEEP  
THIS MANUAL NEAR THE ALARM FOR FUTURE REFERENCE.  
Put smoke alarms at both ends of a bedroom hallway or large room if the hallway  
or room is more than 30 feet (9.1 m) long.  
CONTENTS OF THIS MANUAL  
Install Smoke Alarms on sloped, peaked or cathedral ceilings at or within 3ft  
(0.9m)of the highest point (measured horizontally). NFPA 72 2-5.11 states: “Smoke  
alarms in rooms with ceiling slopes greater than 1 foot in 8 feet (.3m in 2.4m) hori-  
zontally shall be located on the high side of the room.” NFPA 72 5-2.4.4.1 states:  
“A row of alarms shall be spaced and located within 3 ft (0.9m) of the peak of the  
ceiling measured horizontally” (see diagram ”C”).  
1 -- RECOMMENDED LOCATIONS FOR SMOKE ALARMS  
2 -- LOCATIONS TO AVOID  
3 -- INSTALLATION INSTRUCTIONS  
4 -- OPERATION AND TESTING  
5 -- NUISANCE ALARMS  
6 -- MAINTENANCE  
7 -- LIMITATIONS OF SMOKE ALARMS  
8 -- GOOD SAFETY HABITS  
9 -- NRC INFORMATION  
Smoke Alarms for Minimum Protection  
Smoke Alarms for Additional Protection  
Ionization Type Smoke Alarms with  
“Hush” Control or Photoelectric Type  
10 -- NFPA PROTECTION STANDARD 72  
11 -- CALIFORNIA STATE FIRE MARSHALL REQUIRED INFORMATION  
12 -- SERVICE AND WARRANTY  
DIAGRAM “B”  
ANYWHERE  
IN THIS AREA  
This smoke alarm uses an extremely small amount of radioactive element in the  
ionization chamber (see Section 9). Do not try to repair the smoke alarm yourself.  
Refer to the instructions in Section 12 for service.  
DIAGRAM “A”  
3 ft  
3 ft  
(0.9m)  
(0.9m)  
1. RECOMMENDED LOCATIONS FOR ALARMS  
Locate the first alarm in the immediate area of the bedrooms. Try to protect the  
exit path as the bedrooms are usually farthest from the exit. If more than one  
sleeping area exists, locate additional alarms in each sleeping area.  
HORIZONTAL DISTANCE  
FROM PEAK  
DIAGRAM “C”  
MOBILE HOME INSTALLATION  
Locate additional alarms to protect any stairway as stairways act like chimneys for  
smoke and heat.  
Mobile homes built in the past five to seven years have been designed to be energy  
efficient. Install smoke alarms as recommended above (refer to RECOMMENDED  
LOCATIONS and Diagram A).  
Locate at least one alarm on every floor level.  
Locate an alarm in every bedroom.  
In mobile homes that are not well insulated compared to present standards, extreme  
heat or cold can be transferred from the outside to the inside through poorly insulated  
walls and roof. This may create a thermal barrier which can prevent the smoke from  
reaching an alarm mounted on the ceiling. In such units, install the smoke alarm on  
an inside wall with the top edge of the alarm at a minimum of 4” (10 cm) and a maxi-  
mum of 12” (30.5 cm) below the ceiling (see Diagram A).  
Locate an alarm in every room where electrical appliances are operated (i.e.  
portable heaters or humidifiers).  
Locate an alarm in every room where someone sleeps with the door closed. The  
closed door may prevent the alarm from waking the sleeper.  
Smoke, heat, and combustion products rise to the ceiling and spread horizontally.  
Mounting the smoke alarm on the ceiling in the center of the room places it closest  
to all points in the room. Ceiling mounting is preferred in ordinary residential con-  
struction.  
If you are not sure about the insulation in your mobile home, or if you notice that the  
outer walls and ceiling are either hot or cold, install the alarm on an inside wall. For  
minimum protection, install at least one alarm close to the bedrooms. For additional  
protection, see SINGLE FLOOR PLAN in Diagram B.  
 
WARNING: TEST YOUR SMOKE ALARM OPERATION AFTER R.V. OR MOBILE  
HOME VEHICLE HAS BEEN IN STORAGE, BEFORE EACH TRIP AND AT LEAST  
ONCE A WEEK DURING USE.  
2. To insure aesthetic alignment of the alarm with the hallway or wall, the “A” line on  
the mounting plate must be parallel with the hallway when ceiling mounting or hori-  
zontal when wall mounting.  
3. After selecting the proper smoke alarm location as described in Section 1, attach  
the mounting plate to the ceiling as shown in Figure 1. For wall mounting see  
Figure 2. Place mounting plate on the wall. Be sure the “UP FOR WALL MOUNT-  
ING “ text and arrow are facing up. Use the screws and anchors provided to  
secure the mounting plate (use 3/16” drill bit for anchors).  
2. LOCATIONS TO AVOID  
In the garage. Products of combustion are present when you start your automobile.  
Less than 4” (10cm) from the peak of an “A” frame type ceiling.  
In an area where the temperature may fall below 40ºF or rise above 100ºF.  
In dusty areas. Dust particles may cause nuisance alarm or failure to alarm.  
In very humid areas. Moisture or steam can cause nuisance alarms.  
In insect-infested areas.  
4. Battery installation instructions are provided on the inside of the battery door. To  
ensure proper installation of the smoke alarm battery, follow the instructions.  
5. When installing the battery, press the battery reminder finger down into the battery  
compartment and install the battery (see Figure 3).  
CAUTION! IF THE BATTERY REMINDER FINGER IS NOT HELD DOWN IN THE  
BATTERY COMPARTMENT BY THE BATTERY, THE BATTERY DOOR WILL  
NOT CLOSE AND THE UNIT WILL NOT ATTACH TO TO THE MOUNTING  
BRACKET.  
Smoke alarms should not be installed within 3 ft (.9m) of the following: the door to  
a kitchen, the door to a bathroom containing a tub or shower, forced air ducts used  
for heating or cooling, ceiling or whole house ventilating fans, or other high air flow  
areas.  
6. Alignment marks are provided on the edge of the trim plate and the alarm. After  
installing the mounting plate, place the alarm  
on the mounting plate with the alignment  
Kitchens. Normal cooking may cause nuisance alarms. If a kitchen alarm is desired,  
it should have an alarm silence feature or be a photoelectric type.  
Near fluorescent lights. Electronic “noise” may cause nuisance alarms.  
marks lined up. Twist the alarm in the direc-  
tion indicated by the “ON” arrow on the alarm  
cover (see Figure 4) until it locks in place.  
3. INSTALLATION INSTRUCTIONS  
7. USING TAMPER RESIST LOCKING PIN: To  
make your smoke alarm somewhat tamper  
resistant, a locking pin has been provided in  
the bag with the screws and anchors. Using  
this pin will deter children and others from removing the alarm from the mounting  
plate. To use the pin, insert it into the hole in the side of the alarm after the alarm  
has been installed on the mounting plate (see Figure 5).  
CAUTION: THIS UNIT IS SEALED. THE COVER IS NOT REMOVABLE!  
FIGURE 5 Tamper Resist  
When wall mounting,  
the “A” line should  
be horizontal and  
the “UP FOR WALL  
MOUNTING” arrow  
must be pointing up.  
Locking Pin  
When mounting  
in a hallway, the  
“A” line should  
be parallel with  
the hallway.  
NOTE: THE TAMPER RESIST PIN WILL HAVE TO BE REMOVED IN ORDER TO  
CHANGE THE BATTERY. USE A LONG NOSE PLIERS TO PULL THE PIN OUT  
OF THE HOLE. IT IS NOW POSSIBLE TO REMOVE THE ALARM FROM THE  
MOUNTING PLATE.  
FIGURE 2  
FIGURE 1  
8. After installation, test your alarm by depressing and holding down the test button  
for several seconds. This should sound the alarm.  
Alignment Marks  
4. OPERATION AND TESTING  
OPERATION: The smoke alarm is operating once a fresh battery is installed and test-  
ing is complete. When products of combustion are sensed, the unit sounds a loud  
85db pulsating alarm until the air is cleared.  
HUSH CONTROL: The “HUSH” feature has the capability of temporarily desensitizing  
the alarm circuit for approximately 7 minutes. This feature is to be used only when a  
known alarm condition, such as smoke from cooking, activates the alarm. The  
smoke alarm is desensitized by pushing the “HUSH” button on the smoke alarm  
cover. If the smoke is not too dense, the alarm will silence immediately and “chirp”  
every 30 -40 seconds for approximately 7 minutes. This indicates that the alarm is in  
a temporarily desensitized condition. The smoke alarm will automatically reset after  
approximately 7 minutes and sound the alarm if particles of combustion are still pres-  
Install  
Remove  
FIGURE 3  
FIGURE 4  
1. Remove the mounting plate from the back of the alarm by holding the mounting plate  
and twisting the alarm in the direction indicated by the “OFF” arrow on the alarm  
cover.  
 
ent. The “HUSH” feature can be used repeatedly until the air has been cleared of the  
condition causing the alarm. Pushing the test/reset button on the alarm will end the  
hush period.  
USE ONLY THE FOLLOWING 9 VOLT BATTERIES FOR SMOKE ALARM  
REPLACEMENT.  
Carbon Zinc Type:  
Alkaline Type:  
EVEREADY 216 OR 1222;  
GOLD PEAK 1604P OR 1604S  
NOTE: DENSE SMOKE WILL OVERRIDE THE HUSH CONTROL FEATURE AND  
SOUND A CONTINUOUS ALARM.  
EVEREADY 522; DURACELL MN1604, MX1604  
GOLD PEAK 1604A  
CAUTION: BEFORE USING THE ALARM HUSH FEATURE, IDENTIFY THE  
SOURCE OF THE SMOKE AND BE CERTAIN A SAFE CONDITION EXISTS.  
Lithium Type:  
ULTRALIFE U9VL  
FLASHING LED LIGHT: This smoke alarm is equipped with a flashing red indicator  
light. The light is located under the test button and will flash every 30 - 40 seconds  
to indicate that the smoke alarm is receiving power.  
NOTE: REGULAR TESTING IS RECOMMENDED.  
WARNING!! USE ONLY THE BATTERIES SPECIFIED. USE OF DIFFERENT  
BATTERIES MAY HAVE A DETRIMENTAL EFFECT ON THE SMOKE ALARM.  
TESTING: Test by pushing the test button on the cover and holding it down for a min-  
imum of 2 seconds. This will sound the alarm if the electronic circuitry, horn, and bat-  
tery are working. If no alarm sounds, the unit has defective batteries or other failure.  
DO NOT use an open flame to test your alarm , you could damage the alarm or ignite  
combustible materials and start a structure fire.  
NOTE: IF AFTER BATTERY REPLACEMENT THE UNIT CONTINUES TO CHIRP,  
WAIT FOR APPROXIMATELY 7 MINUTES. THE “HUSH” FEATURE MAY HAVE  
BEEN ACTIVATED ACCIDENTALLY WHILE CHANGING THE BATTERIES AND  
PUSHING THE TEST BUTTON WILL END THE HUSH CYCLE.  
TEST THE ALARM WEEKLY TO ENSURE PROPER OPERATION. Erratic or low  
sound coming from your alarm may indicate a defective alarm, and it should be  
returned for service (see Section 12).  
CLEANING YOUR ALARM  
YOUR ALARM SHOULD BE CLEANED AT LEAST ONCE A YEAR  
To clean your alarm, remove it from the mounting bracket as outlined in the beginning  
of this section. You can clean the interior of your alarm (sensing chamber) by using  
compressed air or a vacuum cleaner hose and blowing or vacuuming through the  
openings around the perimeter of the alarm. The outside of the alarm can be wiped  
with a damp cloth.  
5. NUISANCE ALARMS  
Smoke alarms are designed to minimize nuisance alarms. Cigarette smoke will not  
normally set off the alarm, unless the smoke is blown directly into the alarm.  
Combustion particles from cooking may set off the alarm if the alarm is located close  
to the cooking area. Large quantities of combustible particles are generated from  
spills or when broiling. Using the fan on a range hood which vents to the outside  
(non-recirculating type) will also help remove these combustible products from the  
kitchen.  
After cleaning, reinstall your alarm and test your alarm by using the test button. If  
cleaning does not restore the alarm to normal operation the alarm should be  
replaced.  
Model 0916 has a “HUSH” control that is extremely useful in a kitchen area or other  
areas prone to nuisance alarms. For more information refer to Section 4, OPERATION  
AND TESTING.  
7. LIMITATIONS OF SMOKE ALARMS  
WARNING: PLEASE READ CAREFULLY AND THOROUGHLY  
If the alarm does sound, check for fires first. If a fire is discovered, get out and call  
the fire department. If no fire is present, check to see if one of the reasons listed in  
Section 2 may have caused the alarm.  
NFPA 72 states: Life safety from fire in residential occupancies is based primarily  
on early notification to occupants of the need to escape, followed by the appropri-  
ate egress actions by those occupants. Fire warning systems for dwelling units are  
capable of protecting about half of the occupants in potentially fatal fires. Victims  
are often intimate with the fire, too old or young, or physically or mentally impaired  
such that they cannot escape even when warned early enough that escape should  
be possible. For these people, other strategies such as protection-in-place or  
assisted escape or rescue are necessary.  
6. MAINTENANCE  
BATTERY REPLACEMENT  
If tamper resist pin has been used, refer to TAMPER RESIST LOCKING PIN in Section  
3 for removal instructions.  
Smoke alarms are devices that can provide early warning of possible fires at a rea-  
sonable cost; however, alarms have sensing limitations. Ionization type alarms  
offer a broad range of fire sensing capabilities but are better at detecting fast flam-  
ing fires than slow smoldering fires. Photoelectric alarms sense smoldering fires  
better than flaming fires. Home fires develop in different ways and are often unpre-  
dictable. Neither type of alarm (photoelectric or ionization) is always best,  
and a given alarm may not always provide warning of a fire.  
To replace the battery, remove the alarm from the mounting plate by rotating the  
alarm in the direction of the “OFF” arrow on the cover (see Section 3, Figure 1).  
The Model 0916 Smoke Alarm is powered by a 9V carbon zinc battery (alkaline and  
lithium batteries may also be used). A fresh battery should last for one year under  
normal operating conditions. This alarm has a low battery monitor circuit which will  
cause the alarm to “chirp” approximately every 30 - 40 seconds for a minimum of  
seven (7) days when the battery gets low. Replace the battery when this condition  
occurs.  
A battery powered alarm must have a battery of the specified type, in good condi-  
tion and installed properly.  
 
A.C. powered alarms will not operate if the A.C. power has been cut off, such as  
by an electrical fire or an open fuse.  
There are situations where a smoke alarm may not be effective to protect against fire  
as stated in the NFPA Standard 72. For instance:  
Smoke alarms must be tested regularly to make sure the batteries and the alarm  
circuits are in good operating condition.  
a) smoking in bed  
b) leaving children home alone  
c) cleaning with flammable liquids, such as gasoline  
Smoke alarms cannot provide an alarm if smoke does not reach the alarm.  
Therefore, smoke alarms may not sense fires starting in chimneys, walls, on roofs,  
on the other side of a closed door or on a different floor.  
Further information on fire safety can be obtained in a pamphlet titled “IN A  
FIRE SECONDS COUNT” published by the NFPA, Batterymarch Park, Quincy,  
MA 02269  
If the alarm is located outside the bedroom or on a different floor, it may not wake  
up a sound sleeper.  
The use of alcohol or drugs may also impair ones ability to hear the smoke alarm.  
For maximum protection, a smoke alarm should be installed in each sleeping area  
on every level of a home.  
9. NRC INFORMATION  
Ionization type smoke alarms use a very small amount of a radioactive element in the  
sensing chamber to enable detection of visible and invisible combustion products.  
The radioactive element is safely contained in the chamber and requires no adjust-  
ments or maintenance. This smoke alarm meets or exceeds all government stan-  
dards. It is manufactured and distributed under license from the U.S. Nuclear  
Regulatory Commission.  
Although smoke alarms can help save lives by providing an early warning of a fire,  
they are not a substitute for an insurance policy. Home owners and renters should  
have adequate insurance to protect their lives and property.  
Install and maintain fire extinguishers on every level of the home and in the kitchen,  
basement and garage. Know how to use a fire extinguisher prior to an emergency.  
10. NFPA REQUIRED PROTECTION  
The National Fire Protection Associations Standard 72 provides the following  
information:  
8. GOOD SAFETY HABITS  
DEVELOP AND PRACTICE A PLAN OF ESCAPE  
Smoke alarms shall be installed outside each separate sleeping area in the immediate  
vicinity of the bedrooms and on each additional story of the family living unit, including  
basements and excluding crawl spaces and unfinished attics. In new construction, a  
smoke alarm also shall be installed in each sleeping room.  
Make a floor plan indicating all doors and windows and at least two (2) escape  
routes from each room. Second story windows may need a rope or chain ladder.  
Have a family meeting and discuss your escape plan, showing everyone what to  
do in case of fire.  
Smoke Detection - Are More Smoke Alarms Desirable? The required number of  
smoke alarms might not provide reliable early warning protection for those areas sep-  
arated by a door from the areas protected by the required smoke alarms. For this  
reason, it is recommended that the householder consider the use of additional smoke  
alarms for those areas for increased protection. The additional areas include the  
basement, bedrooms, dining room, furnace room, utility room, and hallways not pro-  
tected by the required smoke alarms. The installation of the smoke alarms in the  
kitchen, attic (finished or unfinished), or garage is normally not recommended, as  
these locations occasionally experience conditions that can result in improper opera-  
tion.  
Determine a place outside your home where you all can meet if a fire occurs.  
Familiarize everyone with the sound of the smoke alarm and train them to leave  
your home when they hear it.  
Practice a fire drill at least every six months. Practice allows you to test your plan  
before an emergency. You may not be able to reach your children. It is important  
they know what to do.  
WHAT TO DO WHEN THE ALARM SOUNDS  
This equipment should be installed in accordance with the National Fire Protection  
Associations Standard 72 (NFPA, Batterymarch Park, Quincy, MA 02269).  
Leave immediately by your escape plan. Every second counts, so don’t waste  
time getting dressed or picking up valuables.  
NOTIFY YOUR LOCAL FIRE DEPARTMENT AND INSURANCE COMPANY OF YOUR  
SMOKE ALARM INSTALLATION.  
In leaving, don’t open any inside door without first feeling its surface. If hot, or if  
you see smoke seeping through cracks, don’t open that door! Instead, use your  
alternate exit. If the inside of the door is cool, place your shoulder against it, open  
it slightly and be ready to slam it shut if heat and smoke rush in.  
11. CAUTION (AS REQUIRED BY THE CALIFORNIA  
STATE FIRE MARSHAL)  
“Early warning fire detection is best achieved by the installation of fire detection  
equipment in all rooms and areas of the household as follows. A smoke alarm  
installed in each separate sleeping area (in the vicinity of, but outside of the bed-  
rooms), and heat or smoke alarms in the living rooms, dining rooms, bedrooms,  
kitchens, hallways, attics, furnace rooms, closets, utility and storage rooms, base-  
ments and attached garages.”  
Stay close to the floor if the air is smoky. Breathe shallowly through a cloth, wet if  
possible.  
Once outside, go to your selected meeting place and make sure everyone is there.  
Call the fire department from your neighbors home - not from yours!  
Don’t return to your home until the fire officials say that it is all right to do so.  
 

Insignia Cell Phone X7510 User Manual
Intel Webcam SE7501CW2 User Manual
JVC Blu ray Player LVT2007 003C User Manual
Kenmore Freezer 23501 User Manual
Kenmore Trash Compactor 6651363 User Manual
Kenwood Stereo System HM 582MD User Manual
King Canada Dust Collector KC 3105C User Manual
KitchenAid Cooktop KHIF 9010 User Manual
KitchenAid Dishwasher W10216167A User Manual
Kodak Digital Camera M575 User Manual