• Addressable conventional technology
• Maximum temperature 58°C
• Addressing by means of address
module or detector parameterisation
• Remote readout of detector condition
• Function testable with Remote Test
Unit ECO1000RTU
Description
The Thermal ROR Detector 5351E reacts to tempera-
ture changes within defined periods of time, up to a
maximum temperature of 58°C. The intelligent evalua-
tion of these data allows the early detection of sprea-
ding fires. The detector complies with Class A1R and
can be used up to a room height of 7.5m.
by means of the Remote Programming and Test Unit,
is displayed on the Zonal Display Unit S300ZDU.
A test activation of the detector can be carried out
using the Remote Test Unit ECO1000RTU. In addition
to the test activation of the detector, the Remote Pro-
gramming and Test Unit S300RPTU can also be used
to set and display the following detector parameters:
• the detector address, and
Addressable conventional technology is used for alarm
transmission to the fire detection control panel. The
detector addressing can be achieved in 2 ways:
• A detector with an Address Module NG58-1 can be
individually identified by the suitable control panel.
• An address, which has been stored in the detector
• the date of the previous maintenance.
The detector can be attached to various detector ba-
ses and it can be protected against theft.
Specifications
Operating voltage
Current consumption
Alarm temperature
Operating temperature
Ambient temperature
Relative humidity
Dimensions ø × H
Colour
Supply through the detector line voltage
typ. 80µA (quiescent)
58°C (maximum-heat component)
max. +45°C
-30°C to +70°C
5 – 95% (no condensation)
102 × 43 (mm)
cream
Weight
75g
Approval
VdS G202014
Order number
Order name
242040
Thermal ROR Detector/Conv./300/SS 5351E
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
5351E_DBL_LST_EN_0804.PDF • PAGE 1
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
|