Safety Barrier
• Allows to create intrinsically safe
circuits
• Galvanic isolation of the detector line
voltage
• Connection of intrinsically safe
detectors
• Industrial plastic surface-mount case
• ATEX certified
Description
The Safety Barrier ES58-2 for the galvanic isolation of
the detectors in the hazardous area serves for the de-
sign of an intrinsically safe electric circuit. The plastic
surface-mount housing allows to mount the safety bar-
rier near the hazardous area.
number of detectors depends on the country-specific
regulations and can be found in the Connection of De-
tectors.
Due to the galvanic isolation, the earth leakage moni-
toring can remain activated in the fire detection control
panel. Thus, the installation can also be monitored in
the hazardous area.
The built-in zener barrier limits the current and the vol-
tage of the detector line, as well as the electric energy
stored in the intrinsically safe circuit. The maximum
Specifications
Ignition protection
Ex classification
Operating voltage
Quiescent current
Ambient temperature
Dimensions W × H × D
Colour
intrinsically safe
EEx ia llC
Supply through the detector line voltage
approx. 5mA
-20°C to +60°C
120 × 160 × 90 (mm)
light grey, similar to RAL 7035
650g
Weight
Approval
BASEEFA98ATEX7343
228003
Order number
Order name
Safety Barrier/Conv. ES58-2
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
ES58-2_DBL_LST_EN_0805.PDF • PAGE 1
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
|