PVI Industries Water Heater 1000 P 225A TPL User Manual

LOW NOx TURBOPOWER® • PACKAGED WATER HEATER  
POLYSHIELD® POLYMER-LINED STORAGE TANK  
TANK SERIES 225 GALLONS VERTICAL  
Min. Inlet  
Flow Gas  
Pressure  
" W.C. d  
Dimensions  
(inches)  
Blower  
Motor  
Shipping  
Weight  
#
Recovery gph c  
MODEL  
NUMBER  
INPUT  
Btu/h  
SCAQMD Energy  
Model No.  
40° - 120°F 40° - 140°F  
A
B
C
HP  
Amps  
1000 P 225A-TPL  
1000  
800  
800,000  
4.5  
8TPL  
800 MBtu/h  
44  
8
1
1/2  
7
1540  
c Recoveries based on 83% thermal efficiency. ASHRAE 90.1 compliant for efficiency and standby loss.  
d With standard gas train  
* The information presented is for natural gas 0.6 S.G.  
Dimensions are in inches unless otherwise specified.  
For standard and optional equipment, see form #PV 6453.  
STANDARD GAS PRESSURE REQUIREMENTS:  
SEE TABLE FOR MINIMUM PRESSURE BY MODEL.  
MAXIMUM STATIC INLET GAS PRESSURE IS 10.5" W.C.  
STANDARD ELECTRICAL REQUIREMENTS:  
VOLTAGE: 120V, 1Ø, 60 HZ., 20 AMPS.  
OTHER VOLTAGES REQUIRE AN EXTERNAL  
STEPDOWN TRANSFORMER.  
FOR GAS PRESSURES OUTSIDE OF THIS RANGE,  
CONTACT YOUR PVI REPRESENTATIVE.  
PVI RESERVES THE RIGHT TO CHANGE THE DESIGN AND  
SPECIFICATION WITHOUT NOTICE.  
VENTING REQUIREMENTS:  
-.02" TO -.06" W.C. (NEGATIVE PRESSURE).  
TYPE B VENTING.  
ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED UPON  
THE VENT CONNECTION DIAMETER EXCLUSIVELY. CHECK  
NATIONAL FUEL GAS CODE UNDER "FAN ASSISTED."  
Product is patented in the U.S., Canada, and Mexico.  
PVI INDUSTRIES, LLC  
FORT WORTH, TEXAS 76111  
PV 6513 02/25/04  
(800) 784-8326 www.pvi.com  
 

Peavey Music Mixer 1606M User Manual
Philips Biscuit Joiner MCD515 User Manual
Philips Cell Phone CT7668 User Manual
Philips Computer Drive PCA103CD User Manual
Philips Indoor Furnishings P 5973 User Manual
Philips TV Antenna 37PF5321 User Manual
Philips TV VCR Combo CCZ092AT User Manual
Philips Universal Remote pmdvd6 User Manual
Pride Mobility Wheelchair INFMANU1206 User Manual
ProForm Treadmill 831246240 User Manual