Thank you for purchasing a MINUTEMAN power protection product. It has been  
designed and manufactured to provide many years of trouble free service.  
IMPORTANT SAFETY INSTRUCTIONS  
SAVE THESE INSTRUCTIONS !  
Please read this manual before installing your PRO-E Series UPS, models  
PRO500E, PRO700E, PRO1100E, PRO1500E, PRO500iE, PRO700iE,  
PRO1100iE, PRO1500iE, as it provides important information that should be  
followed during installation and maintenance of the UPS and batteries allowing  
you to correctly set up your system for the maximum safety and performance.  
Included is information on customer support and factory service if it is required.  
If you experience a problem with the UPS please refer to the Troubleshooting  
guide in this manual to correct the problem or collect enough information so  
that the MINUTEMAN Technical Support Department can rapidly assist you.  
This symbol indicates "ATTENTION"  
This symbol indicates "Risk of Electrical Shock"  
This symbol indicates "Alternating Current Supply Phase"  
This symbol indicates "Alternating Current Supply"  
This symbol indicates "Direct Current Supply"  
This symbol indicates "Equipment Grounding Conductor"  
CAUTION! To reduce the risk of electrical shock with the installa-  
tion of this UPS equipment and the connected equipment, the user  
must ensure that the combined sum of the AC leakage current does  
not exceed 3.5mA.  
2
 
CAUTION! Connect the UPS to a two pole, three wire grounding  
AC wall outlet. The receptacle must be connected to the appropriate  
branch protection (circuit breaker or fuse). Connection to any other  
type of receptacle may result in a shock hazard and violate local elec-  
trical codes.  
CAUTION! To reduce the risk of electrical shock in conditions where  
the load equipment grounding cannot be verified, disconnect the UPS  
from the AC wall outlet before installing a computer interface cable.  
Reconnect the power cord only after all signaling connections are made.  
WARNING: Risk of Electrical Shock. Hazardous live parts inside  
these power supplies are energized from the battery even when the  
AC input is disconnected.  
To de-energize the outputs of the UPS:  
1. If the UPS is on press and release the On/Off/Test button.  
2. Disconnect the UPS from the AC wall outlet.  
3. To de-energize the UPS completely, disconnect the battery.  
This Uninterruptible Power Supply (UPS) contains potentially hazardous volt-  
ages. DO NOT attempt to disassemble the UPS. This UPS contains no user  
serviceable parts. Repairs and battery replacement must be performed by  
AUTHORIZED SERVICE PERSONNEL ONLY.  
NOTICE: This equipment has been tested and found to comply with  
the limits for a Class B computing device in accordance with the speci-  
fications in Subpart J of Part 15 of FCC Rules and the Class B limits for  
radio noise emissions from digital apparatus set out in the Radio Interference of  
the Canadian Department of Communications. These limits are designed to  
provide reasonable protection against such interference in a residential installa-  
tion. This equipment generates and uses radio frequency and if not installed  
and used properly, that is, in strict accordance with the manufacturer's instruc-  
tions, this equipment may cause interference to radio and television reception.  
If this equipment does cause interference to radio or television reception, which  
can be determined by turning the equipment off and on, the user is encouraged  
to try to correct the interference by one or more of the following measures:  
!
!
!
!
Re-orient the receiving antenna.  
Relocate the computer with respect to the receiver.  
Move the computer away from the receiver.  
Plug the computer into a different outlet so that the computer and receiver  
are on different branch circuits.  
!
Shielded communications interface cables must be used with this product.  
WARNING: Changes or modifications to this unit not expressly ap-  
proved by the party responsible for compliance could void the user's  
authority to operate the equipment.  
3
 
Receiving Inspection  
After removing your MINUTEMAN UPS from its carton, it should be inspected  
for damage that may have occurred in shipping. Immediately notify the carrier  
and place of purchase if any damage is found. Warranty claims for damage  
caused by the carrier will not be honored. The packing materials that your UPS  
was shipped in are carefully designed to minimize any shipping damage. In the  
unlikely case that the UPS needs to be returned to MINUTEMAN, please use  
the original packing material. Since MINUTEMAN is not responsible for ship-  
ping damage incurred when the system is returned, the original packing mate-  
rial is inexpensive insurance. PLEASE SAVE THE PACKING MATERIALS!  
Para Systems Life Support Policy  
As a general policy, Para Systems Inc. (Para Systems) does not recommend  
the use of any of its products in life support applications where failure or mal-  
function of the Para Systems product can be reasonably expected to cause  
failure of the life support device or to significantly affect its safety or effective-  
ness. Para Systems does not recommend the use of any of its products in  
direct patient care. Para Systems will not knowingly sell its products for use in  
such applications unless it receives in writing assurances satisfactory to Para  
Systems that (a) the risks of injury or damage have been minimized, (b) the  
customer assumes all such risks, and (c) the liability of Para Systems Inc. is  
adequately protected under the circumstances.  
Examples of devices considered to be life support devices are neonatal oxygen  
analyzers, nerve stimulators (whether used for anesthesia, pain relief, or other  
purposes), auto transfusion devices, blood pumps, defibrillators, arrhythmia  
detectors and alarms, pacemakers, hemodialysis systems, peritoneal dialysis  
systems, neonatal ventilator incubators, ventilators for both adults and infants,  
anesthesia ventilators, and infusion pumps as well as any other devices desig-  
nated as “critical” by the United States FDA.  
Hospital grade wiring devices and leakage current may be ordered as options  
on many PARA SYSTEMS UPS systems. PARA SYSTEMS does not claim  
that units with this modification are certified or listed as Hospital Grade by  
PARA SYSTEMS or any other organization. Therefore, these units do not  
meet the requirements for use in direct patient care.  
4
 
On-Line/On-Battery/Boost/Buck LED  
Fault LED  
Overload LED  
Weak/Bad Battery LED  
On/Off/Test Button  
Press and release the ON/OFF/Test Button after 1 beep to turn the  
UPS ON or OFF (see section 4).  
On-Line  
On-Battery  
Buck  
Boost  
The On-Line/On-Battery/Boost and Buck (green) LED illuminates in a steady  
state when the UPS is on and supplying AC power to the load. The LED blinks  
and the audible alarm sounds, when supplying battery power to the load. The  
LED blinks and no audible alarm when the UPS is in either the boost or the  
buck mode.  
The Fault (red) LED illuminates when the UPS has detected an inter-  
nal fault. (see section 5)  
The Overload (yellow) LED illuminates when the loads connected to  
the UPS exceeds the UPS power rating. (see section 5)  
The Weak/Bad Battery (red) LED illuminates when the UPS has  
detected that the batteries are Weak/Bad. Battery replacement might  
be required. (see section 5)  
5
 
REAR PANEL  
1
10  
2
120V Models  
3
9
4
5
8
6
7
1. The Information/Rating Label.  
2. The Battery Backup and Surge output power receptacles are NEMA 5-15R  
type (IEC 320 C13 sockets for 230V models).  
3. The USB Communications Interface Port is for UPS monitoring and control.  
4. The RS232 Communications Interface Port is for UPS monitoring and  
control.  
5. The Dipswitches are for setting the Inverter output voltage.  
6. The input power cord has a NEMA 5-15P Plug (IEC 320 C14 socket for 230V  
models).  
7. The input circuit breaker will trip in the event the load exceeds the UPS’s  
power rating.  
8. The RJ11/RJ45 modular connectors are used for 10 Base-T Network/Fax/  
Modem protection.  
WARNING: The 230V models are NETWORK PROTECTION ONLY.  
9. The Surge ONLY output power receptacles are NEMA 5-15R type (IEC 320  
C13 sockets for 230V models).  
NOTE: The Surge ONLY output power receptacles are only on the following  
models: PRO500E, PRO700E, PRO500iE, PRO700iE.  
10. The Site Wiring Fault (SWF) LED illuminates when the UPS detects an  
improperly wired AC wall outlet (120V models only).  
1
2
230V Models  
3
9
4
8
5
6
7
6
 
INSTALLATION PLACEMENT  
The PRO-E series is intended to be install in a temperature controlled environ-  
ment that is free of conductive contaminants. Select a location which will pro-  
vide good air circulation for the UPS at all times. Avoid locations near heating  
devices, water or excessive humidity, or where the UPS is exposed to direct  
sunlight. Route power cords so they cannot be walked on or damaged.  
Operating Temperature (Maximum): 0 to 40 degrees C (+32 to 104 degrees F)  
Operating Elevation: 0 to 3,000m (0 to 10,000 ft)  
Operating and Storage Relative Humidity: 95%, non-condensing  
Storage Temperature: -15 to +45 degrees C (+5 to +113 degrees F)  
Storage Elevation: 0 to 15,000m (0 to +50,000 ft)  
INSTALLATION  
Be sure to read the installation placement and all the cautions before installing  
the UPS. Place the UPS in the final desired location and complete the rest of  
the installation procedure. USE CAUTION: The UPS is heavy. Use the  
appropriate number of personnel when installing the UPS.  
CONNECTING YOUR EQUIPMENT  
Plug the equipment into the output receptacles on the rear panel of the UPS.  
Do not use extension cords, adapter plugs, power strips or surge strips on the  
output of the UPS. Ensure that you do not exceed the maximum output rating  
of the UPS (refer to the UPS's back panel or the Electrical Specifications in this  
manual).  
DO NOT connect a laser printer to the output receptacles on the  
CAUTION!  
UPS, unless the UPS is rated 2000VA or greater. A laser printer  
draws significantly more power when printing than at idle and  
may overload the UPS.  
7
 
DO NOT plug Power Strips or Surge Protection Devices into  
the ”Battery Backup” Receptacles on the UPS. Plugging Power  
Strips or Surge Protection Devices into the “Battery Backup”  
Receptacles may cause internal damage to the UPS, the Power  
Strip, or the Surge Protection Device.  
WARNING!  
CONNECTING THE UPS TO AN AC SOURCE  
Plug the UPS into a two pole, three wire, grounded receptacle only. Do not use  
extension cords, adapter plugs, power strips or surge strips.  
CHECKING THE SITE WIRING FAULT  
After plugging in the UPS, check the Site Wiring Fault (SWF) LED on the rear  
panel of the UPS. If the SWF LED is illuminated, the UPS is plugged into an  
improperly wired AC outlet.  
If the UPS indicates a Site Wiring Fault (SWF), have a  
Qualified Electrician correct the problem.  
CAUTION!  
CHARGING THE BATTERY  
The PRO-E Series UPS will charge the internal batteries whenever the UPS is  
connected to an AC source. It is recommended that the UPS's batteries be  
charged for a minimum of 4 hours before use. The UPS may be used  
immediately, however, the “ON Battery” runtime may be less than normally  
expected.  
NOTE: If the UPS is going to be out of service or stored for a prolonged period  
of time, the batteries must be recharged for at least twenty-four hours  
every ninety days.  
COMMUNICATIONS PORT CONNECTION (OPTIONAL)  
MINUTEMAN Power Monitoring Software and interface cables kits can be used  
with the PRO-E Series UPS. Use only MINUTEMAN or MINUTEMAN approved  
interface cables with these UPSs. Connect the interface cable (Serial or USB)  
to the appropriate communications port on the rear panel of the UPS. Connect  
the other end of the cable to the device that will be monitoring/controlling the  
UPS.  
NOTE:  
Connecting to the Communications Port is optional. The UPS works  
properly without a connection.  
NETWORK/FAX/MODEM PROTECTION CONNECTION (OPTIONAL)  
Connect a 10 Base-T network, Fax or Modem line to the RJ11/45 protection  
sockets on the rear panel of the UPS. This connection will require another  
length of telephone or network cable. The cable coming from the telephone  
service or networked system is connected to the port marked “IN”. The equip-  
ment to be protected is connected to the port marked "OUT".  
NOTE: Connecting to the Network/Fax/Modem protection socket connection  
is optional. The UPS works properly without a connection.  
WARNING: The RJ45 protection sockets for the 230V models are NETWORK  
PROTECTION ONLY. Connecting a Fax/Modem/Phone line is  
PROHIBITED.  
8
 
TURNING THE UNIT ON/OFF  
ON / OFF / Test Button  
Press and release the ON/OFF/Test Button after one beep to turn the UPS ON  
and supply power to the load. The load is immediately powered while the UPS  
runs a two-second self test. Press and release the ON/OFF/Test Button after  
one beep to turn the UPS OFF. The UPS will continue to charge the batteries  
whenever it is plugged into an AC outlet and there is AC present.  
SELF TEST  
The self test feature is useful to verify the correct operation of the UPS and the  
condition of the batteries. With the UPS in the normal On-Line mode, press  
and hold the ON/OFF/Test Button for approximately 4 seconds (four beeps),  
then release the button. The UPS will perform a ten-second self test. During  
the self test, the UPS will switch to battery power and the On-Line LED will  
blink and the audible alarm will sound. The length of the test that is automati-  
cally performed every two weeks is longer than the start-up or user invoked  
test. This test will run for approximately fifteen-seconds to measure the battery’s  
capability to provide an acceptable amount of runtime. If the UPS fails a self  
test, one of the LEDs will remain illuminated indicating the type of problem.  
Note: The UPS will automatically perform a self test on start-up and every two  
weeks.  
DIP SWITCH SETTINGS  
The DIP Switch setting may be changed by the user to set the desired Inverter  
(on battery) output voltage. The DIP Switch must be set to the desired Inverter  
output voltage and then the UPS must be turned OFF and restarted to reconfigure  
the microprocessor and save the changes. The Inverter (on battery) output  
voltage setting for the 120V models can be either 120VAC (default) or 127VAC.  
Changing the Inverter output voltage to 127VAC, will also change the Buck  
setpoint from 130VAC (default) to 136VAC. The Inverter (on battery) output  
voltage setting for the 230V models can be either 230VAC (default) or 208VAC.  
Changing the Inverter output voltage to 208VAC, will also change the Boost1  
setpoint from 206VAC (default) to 198VAC.  
Inverter output voltage  
Switch  
1
2
120V (230V)  
127V (208V)  
9
 
ALARMS  
ON BATTERY  
When the UPS is operating on the batteries, the On-Battery LED will blink and  
the audible alarm will sound once every 10-seconds. The alarm will stop once  
the UPS returns to the On-Line operation.  
LOW BATTERY WARNING  
The UPS will sound two beeps every five-seconds when the battery reserve  
runs low. This condition will continue until AC returns or the UPS shuts down  
from battery exhaustion.  
WEAK/BAD BATTERY  
The UPS automatically tests the battery’s condition and will illuminate the Weak/  
Bad Battery LED and sound the alarm. This alarm will be repeated until the  
batteries pass a self test. If the battery is bad or disconnected, the Weak/Bad  
Battery LED will illuminate and the alarm will beep three times every five-min-  
utes until the battery is reconnected or replaced. If the battery is weak, the  
Weak/Bad Battery LED will illuminate and the alarm will beep one time every  
ten-minutes until the battery is recharged or replaced. It is recommended that  
the UPS be allowed to charge overnight before performing a battery test to  
confirm a Weak/Bad Battery condition.  
NOTE: If the UPS has a Weak/Bad Battery Alarm after reconnecting of replac-  
ing the batteries, the user must initiate a self test to clear the Weak/Bad Bat-  
tery Alarm. To initiate a self test see section 4 "SELF TEST".  
OVERLOAD  
When the amount of load attached to the UPS exceeds its power rating, the  
Overload LED will illuminate and the UPS will sound a constant alarm. This  
alarm will remain on until the excess load is removed or the UPS’s self protec-  
tion circuit shuts the UPS down.  
UPS FAULT  
When the UPS detects a hardware fault, the Fault LED will illuminate and the  
UPS will sound a constant alarm. The fault condition, in some instances, may  
be reset by turning the UPS OFF and then ON. (see section 5 Troubleshooting)  
FAN LOCK  
AC Mode: If the fan becomes locked, the alarm will beep one time every two-  
seconds until the fan is unlocked.  
Battery Mode: If the fan becomes locked, the alarm will beep one time every  
two-seconds for thirty-seconds, then the output will turn off, the alarm will sound  
continuously and the Fault LED will illuminate. The UPS must be turned off and  
the fan unlocked to clear the Fan lock Alarm.  
10  
 
COMMUNICATIONS PORTS (RS232 and USB)  
The RS232 communication port is a standard DB9 female with both RS232 and  
simulated contact closure capability. The PRO-E series UPS will poll the port  
and activate the port for RS232 or contact closure in accordance with the type  
of cable it finds connected to the port. To change the port configuration requires  
the unit be turned off and restarted with the desired cable connected. The  
pinout for the port is depicted per the chart below.  
Pin 1: EPO Emergency Power Off (pull and hold this pin low to turn off the UPS,  
release this pin from low to turn to restart the UPS)  
Pin 2: /TXD  
Pin 3: /RXD and receive ups shutdown command  
Pin 4: Simulated contact closure AC fail, NO  
Pin 5: Ground  
Pin 6: Simulated contact closure low battery warning, NO  
Pin 7: Simulated contact closure AC fail, NC  
Pin 8: AC fail signal (high to low signal)  
Pin 9: Not Used  
NOTE: See the SentryII CD for the Power Monitoring Software installation.  
See the USB Driver CD for the USB installation.  
11  
 
What To Do  
Possible Cause  
Symptom  
Press and release the On/Off/  
Test button to start UPS  
On/Off/Test button not  
pushed  
UPS will not turn on  
Input AC circuit breaker is Reset circuit breaker by  
UPS operates in  
battery mode only,  
even though there is  
normal AC present  
tripped  
pressing the plunger back in.  
If the AC circuit breaker trips  
after UPS starts up, reduce  
the load on the UPS  
Fault LED is  
illuminated  
UPS has detected an  
internal fault  
Call for service  
Have a Qualified Electrician  
correct the service wiring  
Disconnect the computer  
cable from the UPS and press  
the On button. If UPS works  
normally, the software has  
control of the UPS  
Incorrect service wiring  
Site Wiring Fault  
LED is illuminated  
The On-line/On- The UPS is being  
Battery LED is controlled via its  
illuminated, but communications port  
there is no output  
Charge the batteries for 8  
hours and retest. If the runtime  
is still less than expected, the  
batteries may need to be  
replaced, even though the  
Weak/Bad Battery LED is not  
illuminated  
UPS does not  
The batteries may be weak  
provide expected or at the end of useful  
runtime  
service life  
Weak/bad batteries or bad  
connections at the battery  
Weak/Bad Battery  
LED is illuminated  
Check battery connections,  
charge the batteries for 8  
hours, replace the batteries  
Normal operation  
UPS occasionally  
emits a beep  
The UPS is performing its  
intended function  
The load has exceeded the Check the specifications (see  
Overload LED is  
illuminated and a  
constant alarm  
UPS's capacity  
section 8). Remove part of the  
load  
The UPS is in either the The UPS is performing its  
Boost mode or the Buck intended function  
mode  
The On-Line LED is  
blinking and the au-  
dible alarm is silent  
12  
 
REPLACING THE BATTERY  
(AUTHORIZED SERVICE PERSONNEL ONLY)  
The PRO-E Series UPS has an easy to replace hot-swappable batteries. Please  
read all of the WARNINGS and CAUTIONS before attempting to service the  
batteries.  
NOTE: If there is a power interruption while replacing the hot-swappable  
batteries, with the UPS on, the load will not be backed up.  
This Uninterruptible Power Supply contains potentially hazardous  
voltages. Do not attempt to disassemble the UPS beyond battery  
replacement procedures below. This UPS contains no  
user serviceable parts. Repairs and Battery replacement must  
be performed by AUTHORIZED SERVICE PERSONNEL ONLY.  
WARNING!  
Do not open or mutilate batteries. Released electrolyte is harmful  
to the skin and eyes and may be toxic.  
CAUTION:  
CAUTION:  
Do not dispose of batteries in a fire. The batteries may explode.  
The batteries in this UPS are recyclable. Dispose of the batteries  
properly. The batteries contain lead and pose a hazard to the  
environment and human health if not disposed of properly. Refer  
to local codes for proper disposal requirements or return the  
battery to MINUTEMAN.  
Although battery system voltages are only 12VDC, 24VDC, and  
36VDC the battery system can still present a risk of electrical  
shock. The current capability of a battery is sufficient to burn wire  
or tools very rapidly, producing molten metal. Observe these  
precautions when replacing the batteries:  
CAUTION:  
1. Remove watches, rings, or other metal objects.  
2. Use hand tools with insulated handles.  
3. Wear protective eye gear (goggles), rubber gloves and boots.  
4. Do not lay tools or other metal parts on top of batteries.  
5. Disconnect the charging source prior to connecting or  
disconnecting the battery terminals.  
6. Determine if the battery is inadvertently grounded. If the  
battery is, remove the source of the grounding. Contact with  
any part of a grounded battery can result in an electrical shock.  
The likehood of such shock will be reduced, if such grounds  
are removed during installation and maintenance.  
13  
 
CAUTION: Replace batteries with the same number and type as originally  
installed in the UPS. These batteries have pressure operated vents.  
These UPSs contain sealed non-spillable lead acid batteries.  
PRO-E  
Model #  
PRO700E  
PRO700iE  
PRO500E  
PRO500iE  
PRO1100E  
PRO1100iE PRO1500iE  
PRO1500E  
Battery  
Model #  
3-12V7Ah  
3-12V9Ah  
1-12V9Ah  
LC-R129  
2-12V7Ah  
Panasonic  
Part #  
LC-R127  
NP 7-12  
LC-R127  
NP 7-12  
LC-R129  
Yuasa Part # REW45-12  
REW45-12  
BATTERY REPLACEMENT PROCEDURE  
PLEASE READ THE CAUTIONS AND WARNINGS BEFORE ATTEMPTING  
TO REPLACE THE BATTERIES  
Hot-swappable batteries mean that the batteries can be replaced without  
powering down the whole UPS system.  
NOTE: If there is a power interruption while replacing the hot-swappable  
batteries, with the UPS on, the load will not be backed up. To  
hot-swap the batteries start with step number 6.  
1. Turn off the equipment that is plugged into the output receptacles of the  
UPS.  
2. Press and release the On/Off/Test button on the front panel to turn the UPS  
OFF.  
3. Unplug the UPS's AC power cord from the AC wall outlet.  
4. Unplug the equipment from the output receptacles of the UPS.  
5. Unplug the computer interface cable from the rear panel of the UPS.  
6. Remove the retaining screws from the bottom of the front panel of the UPS.  
7. Grasp the bottom of the front panel and gently pull the front panel off the  
UPS.  
8. Lay the front panel on top of the UPS.  
14  
 
9. Disconnect the positive (red) wire from the battery positve terminal.  
10. Disconnect the battery negative (black) wire from the battery negative  
terminal.  
NOTE: Use CAUTION, do not touch the battery positive wire to the battery  
negative wire.  
11. Remove the battery bracket retaining screw and slide the battery bracket  
upwards.  
12. Using the pull tab, pull the batteries out completely. DO NOT pull the  
batteries out by pulling the battery jumper wires.  
13. Remove the battery jumper wires.  
14. Verify proper polarity. Re-install the battery jumper wires on the new  
batteries.  
15. Slide the new batteries into the battery compartment.  
16. Re-install the battery bracket and the battery bracket retaining screw.  
17. Verify proper polarity. Reconnect the battery negative (black) wire to the  
battery negative terminal.  
18. Verify proper polarity. Reconnect the battery positive (red) wire to the  
battery positive terminal. Some sparking may occur, this is normal.  
19. Re-install the front panel of the UPS.  
20. Re-install the retaining screws for the front panel of the UPS.  
21. Dispose of the old batteries properly at an appropriate recycling facility or  
return them to the supplier in the packing material for the new batteries.  
22. The UPS is now ready for the normal start-up operation.  
NOTE: If the UPS has a Weak/Bad Battery Alarm after replacing the batteries,  
the user must initiate a self test to clear the Weak/Bad Battery Alarm. To  
initiate a self test see section 4 "SELF TEST".  
15  
 
IF THE UPS REQUIRES SERVICE  
1.Use the TROUBLESHOOTING section to eliminate obvious causes.  
2.Verify there are no circuit breakers tripped. A tripped circuit breaker is the  
most common problem.  
3.Call your dealer for assistance. If you cannot reach your dealer, or if they  
cannot resolve the problem call or fax MINUTEMAN Technical Support at the  
following numbers; Voice phone (972) 446-7363, FAX line (972) 446-9011 or  
have the following information available BEFORE calling the Technical  
Support Department.  
A. Your name and address.  
B. Where and when the unit was purchased.  
C. All of the model information on the rear panel of your UPS.  
D. Any information on the failure, including LEDs that may be illuminated.  
E. A description of the protected equipment, including model numbers if  
possible.  
F. A technician will ask you for the above information and, if possible, help  
solve your problem over the phone. In the event that the unit requires  
factory service, the technician will issue you a Return Material  
Authorization Number (RMA #).  
G. If the UPS is under warranty, the repairs will be done at no charge. If not,  
there will be a charge for repair.  
4. Pack the UPS in its original packaging. If the original packaging is no longer  
available, ask the Technical Support Technician about obtaining a new set. It  
is important to pack the UPS properly in order to avoid damage in transit.  
Never use Styrofoam beads for a packing material.  
A. Include a letter with your name, address, day time phone number, RMA  
number, a copy of your original sales receipt, and a brief description of the  
problem.  
5. Mark the RMA # on the outside of all packages. The factory cannot accept  
any package without the RMA # marked on the outside.  
6. Return the UPS by insured, prepaid carrier to:  
Para Systems Inc.  
MINUTEMAN UPS  
1455 LeMay Drive  
Carrollton, TX 75007  
ATTN: RMA # _______  
16  
 
PRO1100E  
(PRO1100iE)  
PRO700E  
PRO500E  
(PRO500iE) (PRO700iE)  
MODEL NUMBER  
(230V Models)  
PRO1500E  
(PRO1500iE)  
Acceptable Input voltage  
0 - 165VAC (0 - 290VAC)  
Input voltage (AC Mode)  
Output voltage (AC Mode)  
Nominal input frequency  
Input protection  
Frequency limits (AC Mode)  
Transfer time  
75 - 145VAC (150 - 280VAC)  
120VAC: 105-130VAC (230VAC: 206-250VAC)  
50 or 60 Hz, autosensing  
Resettable circuit breaker  
50 or 60 Hz, +/-6Hz  
2-6 mS typical  
1100VA  
770W  
500VA  
350W  
Maximum load  
700VA  
490W  
1500VA  
1050W  
On-battery output voltage  
On-battery frequency  
On-battery waveshape  
Protection  
Default 120V (230V) / User selectable at 120/127V, (208/230V)  
50/60 Hz, +/-.5 Hz, unless synchronized to utility  
Simulated Sine Wave  
Over current, short circuit protected and latching shutdown  
Surge energy rating (one time,  
10/1000 uS waveform)  
500 J (440 J)  
Surge current capability  
(one time, 8/20 uS waveform)  
6500 Amps total  
Surge response time  
0 ns (instantaneous) normal mode; <5 ns common mode  
Surge voltage let-through (as  
a percentage of an applied  
ANSI C62.41 Cat. A +/-6 kV)  
<5%  
Noise filter  
Normal and common mode EMI/RFI suppression  
Battery type: Sealed, non-  
spillable, maintenance free,  
lead-acid  
Typical battery life  
Typical recharge time  
1-12V9Ah  
2-12V7Ah  
3-12V9Ah  
3-12V7Ah  
3-5 years, depending on discharge cycles and ambient temp  
8 hours from total discharge  
10 Base-T surge protection let-  
through (as a percentage of  
an applied +/-6 kV 1.2/50 us,  
500 a 8/20 uS test)  
Telephone line surge protec-  
tion let-through (as a percent-  
age of an applied +/-6 kV 1.2/  
50 us, 500a 8/20 uS test)  
Runtime: Half Load  
<5%  
<1%  
17-Minutes  
5-Minutes  
14-Minutes  
4.5-Minutes  
15-Minutes  
4-Minutes  
16-Minutes  
5-Minutes  
Runtime: Full Load  
Electromagnetic immunity  
Audible noise at 1 m (3 ft.)  
Size - Net  
H X D X W  
Size - Shipping  
H X D X W  
IEC 801-2 level IV, 801-4 level IV, 801 -5 level III  
<45 dBA  
7.56 x 12.56 x 6.38"  
192 x 319 x 162 mm  
13 x 18.9 x 11.4"  
8.03 x 16.18 x 6.38"  
204 x 411 x 162 mm  
13 x 22.8 x 12.6"  
330 x 480 x 290 mm  
330 x 580 x 320 mm  
39.24 (43)lb  
17.8 (19.5)Kg  
27.33 (30)lb  
42.33 (47)lb  
20.3 (23)lb  
Weight - Net (Shipping)  
12.4 (13.6)Kg  
19.2 (20.9)Kg  
9.2 (10.4)Kg  
Safety and approvals  
EMC Verification  
UL1778, cUL (CSA 22.1), TUV; 230V models  
FCC Class B, CE certified  
17  
 
(These items may require optional software or hardware)  
Description  
User Choices  
Factory  
Default  
Function  
PRO-E  
Use this function to uniquely  
identify the UPS in your network  
configuration  
UPS ID  
Up to 64  
characters  
to define  
the UPS  
Date of  
Date of battery  
Battery  
install  
date  
Enter the current date when  
replacing batteries  
manufacture replacement -  
month/day/year  
XX/XX/XXXX  
Battery 1826  
life in  
days  
Up to 5  
characters  
At first battery replacement, reset  
to reflect actual number of days  
experience in your environment or  
leave factory default  
Enable  
or  
Disable  
When enabled, the UPS will  
automatically restart from a low  
battery shutdown when normal AC  
returns  
Enable/ Enabled  
Disable  
auto  
restart  
Set  
Enabled  
Enabled, at  
low battery,  
disabled  
Enabled - the UPS will emit a  
short beep when in the battery  
mode. At Low Battery the UPS  
will emit two beeps from low  
battery warning until shutdown.  
Disabled - Use only when software  
is controlling the UPS or to  
silence the alarm  
audible  
alarm  
state  
Shut-  
down  
Type  
UPS output  
or UPS  
UPS output  
UPS Output - When the UPS is  
told to shut down, it turns off the  
UPS output only. UPS - Turns off  
the UPS which requires the UPS  
to be turned on manually  
120VAC  
(230VAC)  
120, 127VAC  
(230, 208VAC)  
Set  
Changes output voltage during  
battery mode operations  
inverter  
output  
voltage  
Enabled - the UPS will be  
completely powered OFF and  
remain OFF until EPO is disabled  
Enable/ Disabled  
Disable  
EPO  
Enable  
or  
Disable  
18  
 
Para Systems Inc. (Para Systems) warrants this equipment, when properly  
applied and operated within specified conditions, against faulty materials or  
workmanship for a period of three years from the date of purchase. For equip-  
ment sites within the United States and Canada, this warranty covers repair or  
replacement of defective equipment at the discretion of Para Systems. Repair  
will be from the nearest authorized service center. Replacement parts and  
warranty labor will be borne by Para Systems. For equipment located outside  
of the United States and Canada, Para Systems only covers faulty parts. Para  
Systems products repaired or replaced pursuant to this warranty shall be war-  
ranted for the unexpired portion of the warranty applying to the original product.  
This warranty applies only to the original purchaser who must have properly  
registered the product within 10 days of purchase.  
The warranty shall be void if (a) the equipment is damaged by the customer, is  
improperly used, is subjected to an adverse operating environment, or is oper-  
ated outside the limits of its electrical specifications; (b) the equipment is re-  
paired or modified by anyone other than Para Systems or Para Systems-ap-  
proved personnel; or (c) has been used in a manner contrary to the product’s  
User's Manual or other written instructions.  
Any technical advice furnished before or after delivery in regard to use or appli-  
cation of Para Systems’s equipment is furnished without charge and on the  
basis that it represents Para Systems’s best judgment under the circumstances,  
but it is used at the recipient’s sole risk.  
EXCEPT AS PROVIDED HEREIN, PARA SYSTEMS MAKES NO WARRAN-  
TIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF MERCHANT-  
ABILITY AND FITNESS FOR A PARTICULAR PURPOSE. Some states do not  
permit limitation of implied warranties; therefore, the aforesaid limitation(s) may  
not apply to the purchaser.  
19  
 
LIMITED PRODUCT WARRANTY  
(Continued)  
EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL PARA SYSTEMS BE  
LIABLE FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL, OR CONSEQUEN-  
TIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT, EVEN IF  
ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. Specifically, Para Sys-  
tems is not liable for any costs, such as lost profits or revenue, loss of equip-  
ment, loss of use of equipment, loss of software, loss of data, cost of substi-  
tutes, claims by third parties, or otherwise. The sole and exclusive remedy for  
breach of any warranty, expressed or implied, concerning Para Systems’s prod-  
ucts and the only obligation of Para Systems hereunder, shall be the repair or  
replacement of defective equipment, components, or parts; or, at Para Systems’s  
option, refund of the purchase price or substitution with an equivalent replace-  
ment product. This warranty gives you specific legal rights and you may also  
have other rights which vary from state to state.  
Longer term and F.O.B. job site warranties are available at extra cost. Contact  
Para Systems (1-972-446-7363) for details.  
20  
 
DECLARATION OF CONFORMITY  
Application of Council Directive(s): 89/336/EEC, 73/23/EEC  
Standard(s) to which Conformity is declared: EN50091-1-1, EN50091-2  
Manufacturer’s Name:  
Manufacturer’s Address:  
Para Systems, Inc. (MINUTEMAN UPS)  
1455 LeMay Drive  
Carrollton, Texas 75007 USA  
Type of Equipment: Uninterruptible Power Supplies (UPS)  
Model No: PRO500E (Y), PRO700E (Y), PRO1100E (Y), PRO1500E (Y)  
Year of Manufacture: Beginning April 30, 2003  
I, the undersigned, hereby declare that the equipment specified above  
conforms to the above Directive(s).  
Robert Calhoun  
Robert Calhoun  
(Name)  
(Signature)  
Manager Engineering  
(Position)  
Date: April 30, 2003  
Place: Carrollton, Texas, USA  
21  
 
Notes:  
22  
 

PYLE Audio Speaker PPHP1037UB User Guide
QSC Audio Thermometer DSP 4 User Guide
Radica Games Video Game Controller RC71103 User Guide
RCA Thermometer 63 1035 User Guide
Regency Stove U37 LP1 User Guide
Samsung Microwave Oven M197DN User Guide
Samsung Security Camera SCC B5392 User Guide
Sanyo Battery Charger N 500A User Guide
Schumacher Battery Charger SE 1 User Guide
Sears Lawn Mower 143 User Guide