Tamarack Technologies Fan HV User Manual

HV Series  
Whole House Cooling Fans  
Product Manual & Installation Guide  
HVM.02  
PLEASE LEAVE WITH HOMEOWNER  
Serial Number _________ Date of Purchase __________Point of Purchase _________________  
What the HV whole house cooling fans do  
The HV is used to assist the natural cooling process in the house. When the  
outside temperature drops below the inside temperature, the cooler outside air  
can be used to cool the house. The HV will pull the cooler air from the outside,  
through the house, up into the attic and push the hot air outside. The HV is a fan  
product and will not cool the house below the outside air temperature or create  
a noticeable breeze. The HV can be used any time, for as long as needed, to  
cool or change the air in the house.  
The best location for your HV  
The HV should be located as central as possible to the area that you want to  
cool. Above a central hallway or at the top of a stairwell provide the best airflow.  
The fan can also be mounted vertically, exhausting through a knee wall into an  
HV1000  
under-the-eaves attic space. Cooler outside air should be able to move through the window, the space that needs to be  
cooled, and exhaust out through the fan into the attic.  
Warning: Not to be used over cooking appliances.  
Before installing your HV: Read all instructions carefully  
Some state and local electrical codes require fan products be installed by a licensed electrician. Check with your local  
code officials before installation.  
Make sure that you have adequate net free exhaust area out of your attic. A minimum of 2 square feet is required for  
the HV1000 and 3-1/2 square feet for the HV1600. This can be accomplished with a combination of roof, ridge, soffit or  
gable end vents or other attic exhaust points.  
Make sure that there is enough clearance for the doors to open. Minimum requirement for the HV with R22 insulating  
doors (HV1000 and HV1600-GR) is 11” and 12” for models with R38 insulating doors (HV1000-DB and HV1600-GDR).  
Make sure that there aren’t any pipes, wires, rafters, or air conditioning or heating ducts running through the space  
where the HV will be installed and that the doors will face an unoccupied area.  
Unpacking your HV: When you have unpacked your HV carefully you will find the following:  
HV1000 (silver faced insulation)  
One (1) HV1000 Whole House Cooler  
One (1) White Metal Grille w/(6) Screws  
One (1) Package of Foam Gasket  
One (1) Metal Electrical Box Cover w/(2) Screws Four (4) #8x3/4 Screws  
One (1) Wall Switch (SPST)  
Four (4) #8x3/4 Screws  
HV1600 (gold faced insulation)  
One (1) HV1600 Whole House Cooler  
One (1) White Metal Grille w/(6) Screws  
One (1) Package of Foam Gasket  
DO NOT  
PULL ON,  
CARRY BY  
OR STRESS  
THE DOORS  
One (1) Hand Held Remote Transmitter  
One (1) Grounding Screw (green)  
Please note the serial number, date of purchase and the point of purchase on the top of this page for handy  
reference. The serial number is located on a label affixed to the HV next to the junction/utility box.  
©Tamarack Technologies, Inc.• 320 Main Street • Buzzards Bay, MA 02532  
508-759-4660 • 800-222-5932 • Fax 508-759-6001  
 
Wiring  
Important - Because of the motorized doors, wiring the HV is different than a normal ON/OFF fan. Please follow the  
instructions carefully. Be sure to turn off power before wiring the HV Whole House Fan It is recommended that the  
wiring of the HV be done by a licensed electrician.  
The HV requires a constant source of power. Because the doors are motorized, they need power to open and power to  
close. The fan operation is controlled internally.  
HV1000  
HV1600  
There are three wires in the electrical box:  
WHITE, RED, and BLACK.  
The HV1600 is connected to power through the line cord  
and must be plugged into a constant, grounded power  
source. When connected to power, it will be fully functional  
with the hand held remote control unit. When any of the  
buttons on the remote control are pushed, the red indicator  
light should momentarily flash.  
Connect the WHITE wire to Line Neutral  
Connect the RED wire to Line Hot  
Connect the BLACK wire to a Switched Hot Feed  
When 115 VAC Hot is applied to it, the doors will  
open. When 115 VAC Hot is removed, the doors will  
close.  
Optional Controls:  
• Connect the ground wire to the screw in the electrical  
box  
Hardwiring the unit to wall switches using the BLUE and  
YELLOW wires will provide additional, manual control. The  
BLUE wire will provide on/off control and the YELLOW wire  
will provide high or low speed control. Using a switch in the  
ON position will override the remote control function.  
Use only SPST (single pole, single throw) switches.  
Drawing is not to scale  
Drawing is not to scale  
The HV whole house cooling fans are not for use with solid state speed controls  
A Remote Control Kit for the HV1000 is available and may be purchased separately. Installation is quick and easy  
and it may be installed at any time.  
Care  
All the motors in the HV are permanently sealed and do not require oiling. To keep dirt, dust and debris from the fans we  
recommend that you periodically remove the grille from within the living space and dust the fan blades. Please remember  
to make sure that the fan is OFF before dusting the fan blades.  
Specifications  
Voltage ……………………………. 115VAC 60 Hz  
Power  
R-Value  
HV1000 & HV1600-GR  
HV1000-DB & HV1600-GDR  
Weight  
R-22  
R-38  
HV1000…………..…....... 112 Watts  
HV1600…………..…....... 276 Watts  
HV1000………………….17 Lbs.  
HV1600………………… 21 Lbs.  
Airflow @ .03” (System)  
HV1000 …………...……. 1000 CFM  
HV1600 High……..…….1600 CFM  
HV1600 Low …………… 900 CFM  
Rough Opening…………………… 14 ½” x 22 ½”  
Grille Dimensions…………………. 15 ¾” x 25 ¾”  
Grille Color ………………………... White  
 
Troubleshooting  
HV1000: The most common problem with the HV1000 is caused by incorrect wiring. Before you check anything else make sure:  
WHITE wire in HV1000 is connected to 115 VAC Line Neutral; RED wire in HV1000 is connected to 115 VAC Line Hot (Constant Hot  
Feed); BLACK wire in HV1000 is connected to a switch that will make it hot when the switch is closed.  
HV1600: If the wireless remote fails to activate the fan, the batteries may need replacing. The transmitter uses two type CR2016 3V  
coin cell batteries. Remove the back plate from the transmitter and remove the batteries. Following the markings above the battery  
holders, replace the batteries. Secure the back plate to the transmitter.  
Switch  
On  
Doors  
Do Not Open  
Fans  
Do Not Run  
Possible Cause  
No Power  
Try  
Check connections and circuit breakers  
On  
Do Not Open  
Do Not Run  
No constant power on RED  
Check wiring connections. There must be  
constant power on the red wire.  
(audible “click”)  
Off  
On  
On  
Do Not Close  
Both Open  
Stop  
RED and BLACK are connected  
together  
Check wiring connections. Connections at the  
fan must be made individually.  
One Fan Runs  
One Fan Runs  
Something blocking fan rotation  
Turn the power off and check for foreign  
matter blocking blade rotation.  
Both Open- One  
closes then  
opens ...  
Door motor gears or switch may  
have been stressed during  
installation. Framing opening may  
be too small.  
Remove fan from between joists and test  
operation while fan is sitting on top of joists. If  
the fan operates, enlarge the opening and  
return the fan to installed position.  
Off  
Both Closed-  
One opens then  
closes…  
Stop  
Door motor gears or switch may  
have been stressed during  
installation. Framing opening may  
be too small.  
Remove fan from between joists and test  
operation while fan is sitting on top of joists. If  
the fan operates, enlarge the opening and  
return the fan to installed position.  
Our unique energy saving system, the R-Gardian, is designed for homes with blown in insulation and will protect  
your insulation when using an HV Whole House Cooler. The R-Gardian may be purchased separately.  
LIMITED WARRANTY  
If, within the period of three years from the date of purchase, the HV 1000 or HV 1600 (the Product) is defective or  
malfunctions in normal home use, Tamarack Technologies, Inc. will repair or replace the Product at its discretion without  
charge for labor or materials. Customer is responsible for shipping charges. NOTE: Some states codes require fans to be  
hardwired. Hardwiring of the HV1600 will not void warranty provided the wiring is performed by a licensed electrician.  
Conditions, Exclusions, and Limitations-This Warranty is subject to the following conditions, exclusions and limitations:  
THIS WARRANTY DOES NOT COVER PROBLEMS RESULTING FROM INSTALLATION, OPERATION OR MAINTENANCE THAT HAS BEEN  
UNDERTAKEN OTHER THAN IN ACCORDANCE WITH THE INSTRUCTIONS. THIS WARRANTY DOES NOT COVER PROBLEMS RESULTING  
FROM DEFECTS IN OR CAUSED BY ASSOCIATED EQUIPMENT (FURNACES, SOLARIA, ETC.); FROM REPAIRS OR MODIFICATIONS  
ATTEMPTED BY PERSONS OTHER THAN TAMARACK TECHNOLOGIES, INC.; FROM ABUSE, ACCIDENTAL OR SHIPPING DAMAGE OR ACTS  
OF GOD. THIS WARRANTY DOES NOT APPLY TO THE PRODUCT USED OUTSIDE THE UNITED STATES, ITS TERRITORIAL POSSESSIONS,  
AND CANADA. EXCEPT AS SET FORTH ABOVE, NO EXPRESS OR IMPLIED WARRANTY IS GIVEN OR AUTHORIZED BY TAMARACK  
TECHNOLOGIES, INC. AND ALL OTHER SUCH WARRANTIES ARE EXPRESSLY DISCLAIMED. ANY WARRANTY OR MERCHANTABILITY OF  
FITNESS FOR ANY PARTICULAR PURPOSE SHALL BE LIMITED TO THE WARRANTY HEREUNDER. MOREOVER, ANY LIABILITY OF  
TAMARACK TECHNOLOGIES, INC. FOR THE PRODUCT SHALL BE LIMITED TO THE REPLACEMENT VALUE OF THE PRODUCT. IN NO EVENT  
SHALL TAMARACK TECHNOLOGIES, INC. BE LIABLE FOR ANY INCIDENTAL DAMAGES OR FOR ANY CONSEQUENTIAL PROPERTY OR  
COMMERCIAL DAMAGES, IRRESPECTIVE OF THE CAUSE THEREOF, OCCURRING EITHER DURING OR AFTER THE WARRANTY PERIOD,  
INCLUDING WITHOUT LIMITATION ANY DAMAGES TO ANY PART OF A BUILDING OR ITS CONTENTS.  
NOTE: SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES AND SOME  
STATES DO NOT ALLOW LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY LASTS, SO THE ABOVE LIMITATIONS OR EXCLUSIONS MAY  
NOT APPLY TO YOU. THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS AND YOU MAY ALSO HAVE OTHER RIGHTS THAT VARY FROM  
STATE TO STATE.  
©Tamarack Technologies, Inc.• 320 Main Street • Buzzards Bay, MA 02532  
508-759-4660 • 800-222-5932 • Fax 508-759-6001  
 

SIIG Computer Drive 5090S User Manual
Sony Clock Radio ICF C215 User Manual
Sony Personal Computer PCG GRT200 User Manual
Sony Portable CD Player Model D EJ715 User Manual
SOYO Computer Hardware SY 6BA+ III User Manual
Spalding Fitness Equipment M800001 User Manual
Speco Technologies Portable Speaker SP6MAT User Manual
StarTechcom Network Card PEX4S952 User Manual
Sunbeam Blender 4141 User Manual
Sylvania MP3 Player SMPK7954 User Manual