Installation Guide Smart-UPS™ X
2000/2200/3000 XL Tower/Rack-Mount 4U
Important Safety Messages
Read the instructions carefully to become familiar with the equipment before trying to install, operate,
service or maintain it. The following special messages may appear throughout this manual or on the
equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a
procedure.
The addition of this symbol to a Caution product safety label indicates that a hazard exists that can result in
injury and product damage if the instructions are not followed.
The following safety messages may appear throughout this manual to warn of potential hazards.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, can result in equipment damage and minor or
moderate injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, can result in equipment damage.
Safety and General Information
Inspect the package contents upon receipt. Notify the carrier and dealer if there is any
damage.
Read the Safety Guide supplied with this unit before installing the UPS.
• Adhere to all local and national electrical codes.
• This UPS is intended for indoor use only.
• Do not operate this UPS in direct sunlight, in contact with fluids, or where there is excessive dust or
humidity.
• Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation.
• The battery typically lasts for two to five years. Environmental factors impact battery life. Elevated
ambient temperatures, poor quality utility power, and frequent short duration discharges will shorten
battery life.
• Connect the UPS power cable directly to a wall outlet. Do not use surge protectors or extension cords.
• The batteries are heavy. Remove the batteries prior to installing the UPS in a rack.
• Always install external battery packs (XLBPs) at the bottom of the rack. The UPS must be installed
above the XLBPs.
• The UPS display interface will recognize as many as 10 external battery packs connected to the UPS.
However there is no limit to the number of XLBPs that can be used with the UPS.
• Refer to Specifications in the Operation manual for UPS and battery weight.
Product Overview
Front panel features
1 Online LED
2 Power ON/OFF button
3 On Battery LED
4 Site Wiring Fault LED
5 Replace Battery LED
6 LCD display screen
7 UP/DOWN arrow keys
8 ENTER key
APC by Schneider
Electric
9 ESC key
su0343a
Rear panel features
1 SmartSlot
7 Controllable Outlet Group 3
8 External battery pack connector
9 EPO connector
2 Chassis ground screw
3 UPS utility power input
4 Circuit Breaker reset
5 Controllable Outlet Group 1
6 Controllable Outlet Group 2
: Serial port
; USB port
2000 VA, 120 Vac Low Voltage
3000 VA, 120 Vac Low Voltage
GROUP 2
GROUP 1
GROUP 3
su0756a
su0757a
Smart-UPS X 2000/2200/3000 VA XL Tower/Rack-Mount 4U
3
2200/3000 VA, 230 Vac High Voltage
3000 VA, 208 Vac High Voltage
su0754a
su0755a
Remove Battery
CAUTION
DAMAGE TO EQUIPMENT OR PERSONNEL
• The equipment is heavy. Always practice safe lifting techniques adequate for the weight of the equipment.
• The UPS + the battery weighs 41 kg (90.4 lb).
• The battery weighs 23.8 kg (52.4 lb). Remove the battery before installing the unit in a rack.
• Use the battery handle to lift and slide the battery out of the UPS.
Failure to follow these instructions can result in equipment damage and minor or moderate injury
1
2
3
4
Smart-UPS X 2000/2200/3000 VA XL Tower/Rack-Mount 4U
Tower Configuration
1
2
3
4
5
Smart-UPS X 2000/2200/3000 VA XL Tower/Rack-Mount 4U
5
Rack-Mount Configuration
CAUTION
DAMAGE TO EQUIPMENT OR PERSONNEL
• The equipment is heavy. Always practice safe lifting techniques adequate for the weight of the equipment.
• The UPS + the battery weighs 41 kg (90.4 lb).
• The battery weighs 23.8 kg (52.4 lb). Remove the battery before installing the unit in a rack.
• Use the battery handle to lift and slide the battery out of the UPS.
Failure to follow these instructions can result in equipment damage and minor or moderate injury
Tower to rack-mount conversion
1
2
3
5
4
6
s
u
0
7
6
9
a
6
Smart-UPS X 2000/2200/3000 VA XL Tower/Rack-Mount 4U
CAUTION
DAMAGE TO EQUIPMENT OR PERSONNEL
• When installing equipment in a rack, always install external battery packs at the bottom of the rack.
• The UPS should always be installed above the external battery packs in rack or stack configurations.
Failure to follow these instructions can result in equipment damage and minor or moderate injury
Two post rack installation
1
2
3
4
5
6
Smart-UPS X 2000/2200/3000 VA XL Tower/Rack-Mount 4U
7
Four post rack installation
Use an APC by Schneider Electric four post rail kit. To order the rail kit go to the APC by Schneider Electric
Web site apc.com.
1
2
3
4
5
6
7
UPS Configuration
Connect Emergency Power Off feature
For instructions on how to connect the Emergency Power Off (EPO) switch, refer to the Operation and
Maintenance manual on the Documentation CD (supplied).
Configure controllable outlet groups
The outlets on the UPS are configured into groups. To utilize the controlled outlet features, use the
Advanced menus on the display interface and navigate to: Main Menu > Control > Outlet1 Control.
8
Smart-UPS X 2000/2200/3000 VA XL Tower/Rack-Mount 4U
Electrical connections
CAUTION
RISK OF EQUIPMENT DAMAGE
• Adhere to all local and national electrical codes.
• Wiring should be performed by qualified electrician.
• Always connect the UPS to a grounded outlet.
Failure to follow these instructions can result in equipment damage
S
P
U
e
c
i
v
e
D
c
i
n
o
r
t
c
e
l
E
Smart-UPS X 2000/2200/3000 VA XL Tower/Rack-Mount 4U
9
®
Select models are ENERGY STAR qualified.
© 2013 APC by Schneider Electric. APC, the APC logo, Smart-UPS and PowerChute are owned by
Schneider Electric Industries S.A.S., or their affiliated companies. All other trademarks are property of
their respective owners.
EN 990-4651A-002
03/2013
|