Bunn H10X User Manual

®
BUNN  
H10X  
WARNING  
!
Very Hot Water  
Use With Care!  
OPERATING & SERVICE MANUAL  
BUNN-O-MATIC CORPORATION  
POST OFFICE BOX 3227  
SPRINGFIELD, ILLINOIS 62708-3227  
PHONE: (217) 529-6601 FAX: (217) 529-6644  
10889.0000C 7/00 ©1995 Bunn-O-Matic Corporation  
USER NOTICES  
Carefully read and follow all notices on the equipment and in this manual. They were written for your protec-  
tion. All notices are to be kept in good condition. Replace any unreadable or damaged labels.  
00656.0000  
#00831.0000  
10044.0000  
NOTICE  
ALL COMPONENTS ARE  
200 TO 240 VOLT A.C.  
Replace only with  
components listed in the  
accompaning literature  
rated for the same  
voltage  
12537.0000  
12593.0000  
10889 072700  
3
ELECTRICAL REQUIREMENTS  
CAUTION - The dispenser must be disconnected from the power source until specified in Initial Set-Up.  
This dispenser requires 2-wire, grounded service rated 208 or 240 volts ac, 40 amp, single phase.  
(Refer to the dispensers dataplate for exact voltage requirement.)  
Electrical Hook-Up  
CAUTION Improper electrical installation will damage electronic components.  
1. An electrician must provide electrical service as specified.  
2. Using a voltmeter, check the voltage and color coding of each conductor at  
L2 RED  
the electrical source.  
3. Remove the side panel.  
208 or 240V.A.C.  
4. Install the proper electrical wiring to the terminal block.  
5. Connect the dispenser to the power source and verify the voltage at the termi-  
nal block before proceeding. Reinstall the side panel.  
L1 BLACK  
6. If plumbing is to be hooked-up later be sure the dispenser is disconnected  
from the power source. If Plumbing has been hooked-up, the dispenser is  
ready for Initial Set-Up.  
PLUMBING REQUIREMENTS  
This dispenser must be connected to a COLD WATER system with operating pressure between 20 and 90 psi  
1
(138 and 620 kPa) from a 2" or larger supply line. A shut-off valve should be installed in the line before the  
dispenser. Install a regulator in the line when pressure is greater than 90 psi (620 kPa) to reduce it to 50 psi (345  
kPa). The water inlet fitting is 14" flare.  
NOTE - Bunn-O-Matic recommends 14" copper tubing for installations of less than 25 feet and 3/8" for more than  
25 feet from the 12" water supply line. At least 18 inches of an FDA approved flexible beverage tubing, such as  
reinforced braided polyethylene or silicone, before the dispenser will facilitate movement to clean the countertop.  
It can be purchased direct from Bunn-O-Matic (P.N. 00326-0000). Bunn-O-Matic does not recommend the use  
of a saddle valve to install the dispenser. The size and shape of the hole made in the supply line by this type of  
device may restrict water flow.  
This equipment must be installed to comply with the Basic Plumbing Code of the Building  
Officials and Code Administrators International, Inc. (BOCA) and the Food Service Sanitation  
Manual of the Food and Drug Administration (FDA).  
Plumbing Hook-Up  
1. Flush the water line and securely attach it to the flare fitting at the rear of the dispenser.  
2. Turn on the water supply.  
10889 072700  
4
INITIAL SET-UP  
CAUTION - The dispenser must be disconnected from the power source throughout the initial set-up, except  
when specified in the instructions.  
1. Connect the dispenser to the power source and turn on the water supply.  
2. The HEATERLED will glow for approximately five seconds. During this time, the electronic circuitry will  
check for a full tank of water.  
3. If the tank is not full of water, the refill circuit will energize, indicated by the REFILLLED glowing. Water  
will automatically flow into the tank to the proper level and then shut off.  
4. When the tank is full of water, the heater circuit will energize, indicated by the HEATERLED glowing  
intermittently until the proper temperature is achieved. A completely cold tank will take approximately  
twenty minutes for the water to heat.  
5. The READYLED will glow when the proper water temperature is achieved.  
NOTE - Stop dispensing if the READYLED is off. Dispense only when the READYLED glows.  
DRAINING THE DISPENSER  
CAUTION - The dispenser must be disconnected from the power source throughout these steps.  
1. Disconnect the dispenser from the power source.  
2. Shut-off and disconnect the incoming water supply  
3. Remove the small screws from the sides and front of the top panel.  
4. Gently remove one of the grommets from the tank lid.  
5. Insert a tube to the bottom of the tank and syphon ALL of the water out.  
NOTE - The dispenser must be refilled using the INITIAL SET-UP steps before reconnecting to the power source.  
CLEANING  
The use of a damp cloth rinsed in any mild, non-abrasive, liquid detergent is recommended for cleaning all  
surfaces on Bunn-O-Matic equipment.  
10889 091599  
5
TROUBLESHOOTING  
A troubleshooting guide is provided to suggest probable causes and remedies for the most likely problems  
encountered. If the problem remains after exhausting the troubleshooting steps, contact the Bunn-O-Matic  
Technical Service Department.  
Inspection, testing, and repair of electrical equipment should be performed only by qualified service person-  
nel.  
All electronic components have 200-240 volt ac and low voltage dc potential on their terminals. Shorting of  
terminals or the application of external voltages may result in board failure.  
Intermittent operation of electronic circuit boards is unlikely. Board failure will normally be permanent. If an  
intermittent condition is encountered, the cause will likely be a switch contact or a loose connection at a  
terminal or crimp.  
Solenoid removal requires interrupting the water supply to the valve. Damage may result if solenoids are  
energized for more than ten minutes without a supply of water.  
The use of two wrenches is recommended whenever plumbing fittings are tightened or loosened. This will  
help to avoid twists and kinks in the tubing.  
Make certain that all plumbing connections are sealed and electrical connections tight and isolated.  
This dispenser is heated at all times. Keep away from combustibles.  
WARNING  
Exercise extreme caution when servicing electrical equipment.  
Disconnect the dispenser from the power source when servicing, except when electrical tests are speci-  
fied.  
Follow recommended service procedures.  
Replace all protective shields or safety notices.  
PROBABLE CAUSE  
REMEDY  
PROBLEM  
1. No power or incorrect voltage  
(A) Check the terminal block for the  
correct voltage. It should be 200 to  
240 volts ac across the red and black  
terminals for 200 to 240 volt mod-  
els.  
Equipment will not operate.  
(B) Check circuit breakers or fuses.  
Refer to Service - Overflow protec-  
tion switch for testing procedures.  
See page 16.  
2. Overflow protection switch  
10889 091599  
6
TROUBLESHOOTING (cont.)  
PROBLEM  
PROBABLE CAUSE  
REMEDY  
Automatic refill will not operate af-  
ter drawing hot water.  
1. No water  
Check plumbing and shut-off valves.  
(A) Direction of flow arrow must be  
pointing towards dispenser.  
2. Water strainer/flow control  
(B) Remove the strainer/flow con-  
trol and check for obstructions. Clear  
or replace.  
Refer to Service - Overflow protec-  
tion switch for testing procedures.  
See page 16.  
3. Overflow protection switch  
4. Liquid level system  
Refer to Service - Electronic controls  
for testing procedures. See page 11.  
Refer to Service - Solenoid valve for  
testing procedures. See page 17.  
5. Solenoid valve  
Refer to Service - Solenoid valve for  
testing procedures. See page 17.  
Water flows into the tank continu-  
ously. (Dispenser disconnected from  
power source).  
1. Solenoid valve  
Refer to Service - Electronic controls  
for testing procedures. See page 11.  
Refer to Service - Overflow protec-  
tion switch for testing procedures.  
See page 16.  
Water flows into the tank continu-  
ously (Dispenser connected to  
power source).  
1. Liquid level system  
1. Overflow protection switch  
2. Limit thermostat  
Refer to Service - Limit thermostat  
for testing procedures. See page 15.  
Water is cold.  
CAUTION - Do not eliminate or bypass limit thermostat. Use only B.O.M. replacement part #23717.0001.  
10889 091599  
7
TROUBLESHOOTING (cont.)  
PROBLEM  
PROBABLE CAUSE  
REMEDY  
3. Tank heater  
Refer to Service - Tank heater for  
testing procedures. See page 19.  
Water is cold (cont.)  
4. Temperature control  
5. Dry plug protection  
Refer to Service - Electronic controls  
for testing procedures. See page 12.  
Check connections to Interlock  
board and sheath of tank tempera-  
ture probe.  
Refer to Service - Electronic controls  
for testing procedures. See page 12.  
1. Temperature control  
2. Lime build-up  
Water boils continuously.  
Inspect the tank assembly for excess  
lime deposits. Delime as required.  
CAUTION - Tanks and tank components should be delimed regularly depending on local water conditions. Exces-  
sive mineral build-up on stainless steel surfaces can initiate corrosive reactions resulting in serious leaks.  
Dispenser is making unusual noises. 1. Solenoid valve  
The nut on top of the solenoid valve  
must be tight or it will vibrate dur-  
ing operation.  
2. Plumbing lines  
3. Water supply  
Plumbing lines should not be rest-  
ing on the counter top.  
(A) the dispenser must be connected  
to a cold water line.  
(B) Water pressure to the dispenser  
must not be higher than 90 psi. In-  
stall a regulator if necessary to lower  
the working pressure to approxi-  
mately 50 psi.  
Ready indicator will not light. (when  
temperature is within 4˚ of its se- 1. Temperature control  
lected setting.)  
Refer to Service - Electronic controls  
for testing procedures. See page 12.  
Replace the indicator LED.  
2. Ready Indicator LED  
10889 072700  
8
SERVICE  
This section provides procedures for testing and  
replacing various major components used in this dis-  
penser should service become necessary. Refer to  
Troubleshooting for assistance in determining the cause  
of any problem.  
Component Access  
WARNING - Disconnect the dispenser from the power  
source before the removal of any panel or the replace-  
ment of any component.  
WARNING  
!
Very Hot Water  
Use With Care!  
P878  
The limit thermostat, liquid level probe, tank  
heater, and temperature sensor are located at the top  
of the dispenser. Access is gained by removing the top  
lid, attached with four 4-40 slotted-head screws.  
WARNING  
!
Very Hot Water  
Use With Care!  
WARNING - Inspection, testing, and repair of electri-  
cal equipment should be performed only by qualified  
service personnel. Disconnect the dispenser fromthe  
power source when servicing, except when electrical  
tests are required and the test procedure specifically  
states to connect the dispenser to the power source.  
P878  
Electronic Controls ..................................... 10-14  
Limit Thermostat ............................................. 15  
Safety Overflow Switch.................................... 16  
Solenoid Valve ................................................. 17  
Tank Heater...................................................... 19  
Electrical Schematic......................................... 20  
The check valve, electronic control assembly,  
overflow protection switch, solenoid valve, overflow  
tube temperature sensor, triac assembly and terminal  
block are located on the side of the dispenser. Access  
is gained by removing the side panel. The panel is at-  
tached with eight 8-32 slotted-head screws.  
10889 091599  
9
SERVICE (cont.)  
H10X LIQUID LEVEL CONTROL  
PROBLEM: Does Not Refill  
Electronic Control Assembly Troubleshooting:  
Check these items first  
Is circuit board popped out of bracket?  
Is circuit board wet due to misaligned overflow  
tube?  
Yes  
Overflow Cup Full  
Remove Power  
?
Drain cup  
Retry  
No  
Disconnect Level Probe  
Is water in overflow cup activating float switch?  
Is overflow cup not making good contact with tank?  
Is dispenser being operated with panels removed?  
Yes  
Yes  
Voltage present at  
Solenoid Valve  
?
Does Water Flow  
?
Replace Probe  
No  
No  
Replace Solenoid Valve  
Unplug P2 from Circuit Board  
Yes  
Voltage present at  
Solenoid Valve  
?
Repair shorted wires  
leading to P2.  
No  
Replace Control Assembly  
Triac Assy  
H10X LIQUID LEVEL CONTROL  
PROBLEM: Overflows  
H
o
A
t
a
u
W
tic  
to  
a
a
e
m
te  
r
S
C
ll  
y
s
o
o
y
te  
ff  
rd  
il  
W
A
e
a
u
m
c
h
w
W
s
c
B
e
e
it  
n
it  
W
at  
re  
U
nc  
n
F
a
e
rs  
I
er  
n
s
T
a
C
r
F
o
e
n
k
e
h
il  
T
T
l
T
n
e
W
i
o
h
e
h
c
a
te  
ll  
ill  
C
In  
p
d
F
P
o
s
ly  
W
T
o
an  
m
ta  
V
l
l
a
t
e
r
ti  
T
o
o
we  
n
s
o
In  
W
k
r!  
id  
s
In  
o
tr  
u
c
ti  
a
n
r
s
r
!
!
a
n
ty  
Electronic  
Control  
W
Drain cup  
Unplug P2 from Circuit Board  
Retry  
A
R
N
IN  
G
H
A
Z
O
A
L
R
T
V
D
A
O
G
U
S
D
E
IS  
P
C
O
N
O
N
B
W
E
E
E
C
T
F
R
O
F
R
R
S
E
O
O
M
U
R
R
E
C
M
E
O
V
IN  
G
!
No  
Overflow  
Repair shorted wires  
leading to P2  
?
Yes  
P1991  
Drain cup  
FIG. 1 ELECTRONIC CONTROL AND TRIAC  
Disconnect wire from  
Refill Probe  
Short Probe Wire  
To Chassis  
Retry  
Location:  
The electronic control assembly is located inside  
the side of the dispenser. Access will also be needed  
to the temperature sensor, overflow tube temperature  
sensor, and liquid level probe located on the tank lid  
and to the triac assembly located on the inside of the  
rear wall.  
No  
Overflow  
Replace Probe  
?
Yes  
Drain cup  
Disconnect Wire From  
Solenoid Valve  
Retry  
General:  
This system controls the liquid level and water tem-  
perature of the dispenser. These two functions act in-  
dependently of each other and should be tested sepa-  
rately.  
Yes  
Overflow  
Replace Solenoid Valve  
?
No  
Replace Control Assembly  
10889 091599  
10  
SERVICE (cont.)  
9. Check the voltage across the terminals 1 & 4 of the  
electronic control assembly with a voltmeter. Con-  
nect the dispenser to the power source. The indi-  
cation must be 200 to 240 volts ac for 200 to 240  
volt models after a delay of approximately 5 sec-  
onds.  
Electronic Controls (cont.)  
Liquid Level Control Test Procedure  
1. Disconnect the dispenser from the power source.  
2. Check the voltage across terminals 3 & 4 of the  
10. Touch the screw head end of the probe to the dis-  
penser housing. The indication must be 0.  
electronic control assembly with a voltmeter. Con- 11. Move the probe away from the dispenser housing.  
nect the dispenser to the power source. The indi-  
cation must be 200 to 240 volts ac for 200 to 240  
volt models.  
The indication must again be 200 to 240 volts ac  
for 200 to 240 volt models after a delay of approxi-  
mately 5 seconds.  
3. Disconnect the dispenser from the power source. 12. Disconnect the dispenser from the power source.  
If voltage was present as described, proceed to #4.  
If voltage was not present as described, refer to If voltage was present as described, reinstall the probe,  
the Wiring Diagrams and check the dispenser wir- the sensing function of the system is operating prop-  
ing harness.  
4. Remove the pink wire from terminal 5 of the elec- If voltage was not present as described, check the pink  
tronic control assembly. probe wire and the green ground wire for continuity  
erly.  
5. Check the voltage across terminals 1 & 4 of the and/or replace the probe.  
electronic control assembly with a voltmeter. Con-  
nect the dispenser to the power source. The indi- Temperature control Flow Charts  
cation must be 200 to 240 volts ac for 200 to 240  
volt models after a delay of approximately 5 sec-  
onds.  
6. Disconnect the dispenser from the power source.  
H10X THERMOSTAT  
PROBLEM:Water Not Hot Enough  
Jumper JP1  
No  
Reposition Jumper  
In Boil Position  
?
If voltage was present as described, the liquid level  
control of the system is operating properly, proceed to  
#7.  
If voltage was not present as described, replace the  
electronic control assembly and the temperature sen-  
sor in the tank lid.  
Yes  
No  
Heater Light On  
Constantly  
?
Replace Steam Sensor  
Yes  
Heater Light On  
Yes  
Constantly  
?
Measure Voltage  
At Tank Heater  
Recheck Water Temperature  
No  
Replace Control Assembly  
Replace Tank Heater  
NOTE - Each electronic control assembly is calibrated  
to a temperature sensor. Both components MUST be  
replaced as a set.  
Yes  
Voltage Present  
?
No  
No  
Replace Limit Thermostat  
Limit Thermostat OK  
?
7. Reconnect the pink wire to terminal 5 of the elec-  
tronic control assembly.  
Yes  
8. Loosen the compression fitting, remove the probe  
from the tank lid, and inspect it for mineral depos-  
its. Replace it if necessary. Keep the exposed ends  
of the probe away from any metal surface of the  
dispenser.  
Replace Control Assembly  
Measure Voltage  
At Tank Heater  
Replace Triac  
No  
Voltage Present  
?
Check For Split Tank Heater  
Reinstall Original  
Control Assembly  
Yes  
Recheck Water Temperature  
10889 091599  
11  
SERVICE (cont.)  
If the indicator was on or blinking, the temperature  
sensor is operating properly, proceed to #7.  
If the indicator was off, check the sensor connection  
on the electronic control circuit board and/or replace  
the temperature sensor and the electronic control as-  
sembly.  
Electronic Controls (cont.)  
Temperature Control Flow Charts (cont.)  
H10X THERMOSTAT  
NOTE - Each temperature sensor is calibrated to an  
electronic control assembly. Both components MUST  
be replaced as a set.  
PROBLEM: Boils Excessively - Fills Cup  
Drain cup  
Retry  
7. Check the voltage across the tank heater terminals  
with a voltmeter. Connect the dispenser to the  
power source. The indication must be 200 to 240  
volts ac for 200 to 240 volt models while the red  
indicator on the circuit board is on or blinking.  
8. Disconnect the dispenser from the power source.  
Yes  
Heater Light On While  
Replace Steam Sensor  
Boiling  
?
No  
Yes  
Disconnect Blue Wire From  
Control Board Pin 7  
Still Boiling  
?
Replace Control Assembly  
Retry  
No  
Finished  
Yes  
Still Boiling  
?
If voltage was present as described, the temperature  
control of the system is operating properly.  
If voltage was not present as described, contact Bunn-  
O-Matic to order an electronic control assembly tem-  
perature sensor, and triac assembly for evaluation and  
proceed to #9.  
Replace Triac Assembly  
Check For Split  
Tank Heater  
No  
Replace Control Assembly  
9. Replace the electronic control assembly and tem-  
perature sensor.  
Temperature Control Test Procedure  
1. Disconnect the dispenser from the power source.  
2. Check the voltage across terminals 3 & 4 of the  
electronic control circuit board with a voltmeter.  
Connect the dispenser to the power source. The  
indication must be 200 to 240 volts ac for 200 to  
240 volt models.  
NOTE - Each electronic control assembly is calibrated  
to a temperature sensor. Both components MUST be  
replaced as a set.  
10. Check the voltage across the tank heater terminals  
with a voltmeter. Connect the dispenser to the  
power source. The indication must be 200 to 240  
volts ac for 200 to 240 volt models while the red  
indicator on the circuit board is on or blinking.  
3. Disconnect the dispenser from the power source.  
If voltage was present as described, proceed to #4.  
If voltage was not present as described, refer to the  
Wiring Diagram and check the dispenser wiring har-  
ness.  
4. Connect the dispenser to the power source .  
5. Observe the red indicator on the electronic control  
circuit board.  
6. Disconnect the dispenser from the power source.  
10889 091599  
12  
SERVICE (cont.)  
5. Install the new temperature sensor into the grom-  
met on the tank lid. Route the wires to the location  
of the new electronic control assembly.  
Electronic Controls (cont.)  
6. Attach the temperature sensor, overflow tube tem-  
perature sensor, and indicator wires to the elec-  
tronic control assembly.  
11. Disconnect the dispenser from the power source.  
If voltage was present as described, return the new 7. Fasten the new electronic control assembly to its  
triac assembly to Bunn-O-Matic for credit. The tem- bracket.  
perature control of the system is operating properly. If 8. Reconnect the wires.  
voltage was not present as described, reinstall your 9. Review the initial set-up procedures.  
existing electronic control assembly and temperature  
sensor, and proceed to #12  
12. Replace the triac assembly.  
13. Check the voltage across the tank heater terminals  
BLU to Triac Assy  
TAN to Triac Assy  
with a voltmeter. Connect the dispenser to the  
power source. The indication must be 200 to 240  
BLU to Triac Assy  
TAN to Triac Assy  
PNK to Liquid Level Probe  
RED to Terminal block  
RED to Solenoid  
BLK to Overflow Safety Switch  
GRN to Chassis Ground  
WHI/BLU to Solenoid  
volts ac for 200 to 240 volt models while the red  
indicator on the circuit board is on or blinking.  
14. Disconnect the dispenser from the power source.  
If voltage was present as described, the temperature  
control of the system is operating properly. Return the  
new electronic control assembly and temperature sen-  
sor to Bunn-O-matic for credit.  
P1992  
FIG. 2 WIRING CONNECTIONS  
Electronic Control Removal and Replacement  
NOTE - Each electronic control assembly is calibrated  
to a temperature sensor probe. Both components  
MUST be replaced as a set.  
WHI & WHI to  
Temperature Sensor  
P1  
P2  
1. Remove all wires from the electronic control as-  
sembly terminals.  
PNK & GRY to  
Heater Indicator  
Refill Indicator  
Power Indicator  
Ready Indicator  
2. Remove the two 8-32 screws holding the electronic  
control assembly to the component bracket.  
3. Disconnect the temperature sensor, overflow tube  
temperature sensor, and indicator wires from the  
left side of the electronic control assembly board.  
4. Remove the temperature sensor from the grom-  
met in the tank lid.  
GRY & GRY  
to Thermistor  
P101  
P1992  
FIG. 3 WIRING CONNECTIONS  
10889 091599  
13  
SERVICE (cont.)  
3. Securely fasten the new triac assembly to the rear  
panel in the same relative position as the one re-  
moved. Bunn-O-matic recommends tightening the  
nut to a torque setting of approximately 18 inch-  
pounds.  
4. Disconnect the other ends of the old triac assem-  
bly wires.  
5. Connect the TAN and BLU wires with spade termi-  
nals of the new assembly to the electronic control  
assembly, FIG. 2.  
Electronic Controls (cont.)  
Triac Assembly Removal and Replacement  
NOTE - Each triac installation requires the use of an  
approved silicone heat sink compound. Bunn-O-Matic  
recommends the use of Dow Corning 340 compound  
or equivalent. It can be purchased direct from Bunn-O-  
Matic (P.N. M2522.1000)  
6. Connect the BLU wire with the ring terminal to the  
tank heater, FIG. 12.  
7. Connect the WHI/VIO wire of the new assembly to  
the RED terminal at the terminal block.  
1. Remove the existing triac assembly held in place  
with a 10-32 hex keps nut.  
2. Apply a small amount of the silicone heat sink com-  
pound to the copper heat sink.  
10889 091599  
14  
SERVICE (cont.)  
Limit Thermostat  
If voltage was present as described, reconnect the black  
wire and proceed to #5.  
If voltage was not present as described, refer to the  
Wiring Diagrams and check the dispenser wiring har-  
ness.  
Limit Thermostat  
Location:  
The limit thermostats are located on the tank lid. To  
test the limit thermostats, access will also be needed  
to the terminal block located on the side of the dis-  
penser.  
5. Check for continuity across the terminals of the  
limit thermostat.  
If continuity is not present as described, the circuit is  
broken. Press the reset button of the limit thermostat  
and recheck for continuity.  
If continuity is not present as described, replace the  
limit thermostat.  
Removal and Replacement:  
1. Remove both wires from the limit thermostat ter-  
minals.  
2. Remove the two #10-32 nuts attaching the limit  
thermostat to the top of the tank.  
3. Install the new limit thermostat and secure into  
place with two #10-32 nuts.  
P1993  
FIG. 5 LIMIT THERMOSTAT  
Test Procedure:  
4. Refer to FIG. 6 when reconnecting the wires.  
1. Disconnect the dispenser from the power source.  
2. There are two black wires on the limit thermostat  
terminals. One comes from the terminal block. The  
other goes directly to the tank heater terminal. Re-  
move the black wire at the limit thermostat coming  
from the terminal block.  
BLK to Terminal Block  
Reset  
3. Check the voltage across the black wire removed  
from the limit thermostat and the red wire of the  
terminal block with a voltmeter. Connect the dis-  
penser to the power source. The indication must  
be 200 to 240 volts ac for 200 to 240 volt models.  
4. Disconnect the dispenser from the power source.  
BLK to Tank Heater  
P1776  
FIG. 6 LIMIT THERMOSTAT WIRING  
10889 091599  
15  
SERVICE (cont.)  
Overflow Protection Switch  
Removal and Replacement:  
1. Disconnect the black wires from the overflow pro-  
tection switch.  
2. Remove the nut beneath the copper overflow cup.  
3. Remove the entire switch assembly from the cup.  
4. Place the new switch assembly into the cup, wires  
first. Make sure that a gasket is in place around the  
threaded switch stem.  
NOTE - The magnets must be at the top of the float and  
there must be NO stainless steel washers installed for  
the overflow protection switch to operate properly.  
P1993  
5. Install the nut beneath the copper overflow cup.  
Be sure not to overtighten.  
FIG. 7 OVERFLOW PROTECTION SWITCH  
Location:  
6. Reconnect the wires, FIG. 8.  
The overflow protection switch is located within the  
side of the dispenser inside the copper overflow cup.  
For testing or removal of the overflow protection switch,  
access may also be needed by removing the two screws  
attaching the electronic control assembly to its mount-  
ing bracket.  
Test Procedure:  
1. Once voltage is verified at the power source, check  
for continuity across the overflow protection switch  
red wires only until the plastic float is raised and  
check that continuity returns when the plastic float  
is again lowered.  
RED to BLK Wire from  
Terminal Block  
RED to BLK Wire from  
Electronic Control #3  
If continuity is present as described, reconnect each  
of the red wires to the black wires, the overflow pro-  
tection switch is operating properly.  
If continuity is not present as described, replace the  
overflow protection switch.  
P1777  
FIG. 8 OVERFLOW PROTECTION WIRING  
10889 091599  
16  
SERVICE (cont.)  
Solenoid Valve  
If voltage was present as described, proceed to #5.  
If voltage was not present as described, refer to the  
Wiring Diagrams and check the dispenser wiring har-  
ness.  
Location:  
The solenoid valve is located within the side of the dis-  
penser on the right side near the bottom.  
To test the solenoid valve, access will also be needed  
to the electronic control assembly.  
5. Remove both wires from the solenoid valve coil  
terminals.  
6. Check for continuity across the solenoid valve coil  
terminals.  
If continuity is present as described, reconnect the  
wires and proceed to #7.  
If continuity is not present as described, replace the  
solenoid valve coil.  
7. Check the solenoid valve for coil action. Connect  
the dispenser to the power source. Listen carefully  
in the vicinity of the solenoid valve for a clicking”  
sound after approximately 5 seconds, as the coil  
magnet attracts the plunger.  
8. Disconnect the dispenser from the power source.  
9. Reconnect the pink wire to terminal 5 of the elec-  
tronic control assembly.  
H
A
o
t
a
u
W
a
to  
m
te  
ti  
r
W
r
C
c
a
S
o
ll  
y
s
A
ff  
y
B
te  
c
e
m
s
c
e
h
o
e
rd  
n
r
e
U
a
W
a
n
w
c
e
th  
n
F
e
it  
t
n
a
W
s
T
Is  
er  
n
W
ilu  
i
e
C
T
e
a
F
o
e
a
n
r
il  
ns  
e
l
k
e
T
h
T
ta  
W
h
ct  
o
I
i
ll  
il  
C
d
r
F
ow  
In  
o
T
a
ru  
m
l
l
a
t
e
o
l
p
ti  
o
T
s
P
ly  
n
n
V
I
n
k
e
r!  
o
t
id  
s
ct  
io  
W
n
a
s!  
rr  
a
n
t
y
!
W
A
R
N
IN  
G
HAZARDO
VOLTAGE  
DISCONNECT FROM  
POWER SOURCE  
BEFORE REMOVING!  
.570gpmFLOW  
90mxoatingpsure  
BNU  
Saei/FwCntlor#23.750  
                  )
(RlpScrne3#721.)0  
If the sound was heard as described and water will not  
pass through the solenoid valve, there may be a block-  
age in the water line before or after the solenoid valve  
or the solenoid valve may require inspection for wear  
and removal of waterborne particles.  
If the sound was not heard as described, replace the  
solenoid valve.  
P1994  
FIG. 9 SOLENOID VALVE  
Test Procedure:  
1. Disconnect the dispenser from the power source  
and turn off the water supply to the dispenser.  
2. Remove the pink wire from terminal 5 of the elec-  
tronic control assembly.  
3. Check the voltage across the solenoid valve coil  
terminals with a voltmeter. Connect the dispenser  
to the power source. The indication must be 200  
to 240 volts ac for 200 to 240 volt models after a  
delay of approximately 5 seconds.  
Removal and Replacement:  
1. Remove all wires from the solenoid valve coil.  
2. Turn off the water supply to the dispenser.  
3. Disconnect the water lines to and from the sole-  
noid valve.  
4. Remove the two 8-32 slotted-head screws holding  
the solenoid valve and mounting bracket to the  
component bracket.  
4. Disconnect the dispenser from the power source.  
10889 091599  
17  
SERVICE (cont.)  
Solenoid Valve (cont.)  
5. Lift out the solenoid valve.  
6. Remove the two 10-32 slotted-head screws hold-  
ing the solenoid valve to its mounting bracket.  
7. Securely install the new solenoid valve to its mount-  
ing bracket. The direction of flow arrow must be  
pointing towards the tank lid.  
WHI/BLU to Electronic  
Contol #1  
RED to Terminal Block  
RED to Electronic Control #5  
8. Attach the solenoid valve and mounting bracket to  
the component bracket.  
9. Securely fasten the water lines to and from the  
solenoid valve.  
10. Reconnect the wires, FIG. 10.  
P1779  
FIG. 10 SOLENOID VALVE WIRING  
10889 091599  
18  
SERVICE (cont.)  
If voltage is present as described, proceed to #4.  
If voltage is not present as described, replace the tank  
heater.  
Tank Heater  
Location:  
4. Remove the tank heater from the tank lid and in-  
spect it for cracks in the sheath.  
The tank heater is located in the tank lid.  
If continuity is present as described, reinstall the tank  
heater. The tank heater is operating properly.  
If continuity is not present as described, replace the  
tank heater.  
Removal and Replacement:  
1. Remove the wires to the tank heater.  
2. Remove the 8-32 nuts from the tank heater flange.  
3. Remove the tank heater.  
4. Inspect the tank heater gasket and replace if nec-  
essary.  
5. Securely install the new tank heater. Be certain of a  
watertight seal.  
6. Reconnect the wires, FIG. 12.  
P1993  
FIG. 11 TANK HEATER  
Test Procedure:  
1. Disconnect the dispenser from the power source.  
2. Check the voltage across the terminals of the tank  
heater with a voltmeter. Connect the dispenser to  
the power source. The indication must be 200 to  
240 volts ac for 200 to 240 volt models.  
BLK to Limit Thermostat  
BLU to Triac Assy  
3. Disconnect the dispenser from the power source.  
P1780  
FIG. 12 TANK HEATER WIRING  
10889 091599  
19  
WIRING DIAGRAM  
10889 091599  
20  

Motorola r750plus User Manual
Motorola C300 User Manual
Magnavox AZ6840 User Manual
Fujitsu MAC3045 User Manual
DeLonghi Coffeemaker EC270 User Manual
Black & Decker DCM90M User Manual
Black & Decker AM8 User Manual
Audiovox CTX5000 User Manual
Asus Cell Phone P505 User Manual
AMX Corporation Computer Accessories 68000 User Manual