Fire Alarm Systems | FPA‑1000 Analog Addressable Fire Panels
FPA‑1000 Analog Addressable Fire Panels
u Support for up to 508 points on two analog
addressable loops
u Built-in Ethernet connector for web-browser based
programming and Conettix Alarm-over-IP
communication
u Two on-board NACs and dual-line PSTN DACT
u Peer-to-peer networking of up to eight panels in a
single group
u Simple system management and free online training
The FPA‑1000 Analog Addressable Fire Panels are a
scalable solution for fire detection. Protect your small
office with a single system or connect multiple panels
together as your needs grow. Networking capabilities
support the monitoring of up to 2,000 addressable
points in one system for campuses or other large
commercial environments.
The FPA‑1000 panels combine complete built-in Fire
Alarm Control Panel (FACP) equipment such as
Notification Appliance Circuits (NACs), Signaling Line
Circuits (SLCs), relays, power supply, Digital Alarm
Communicator Transmitter (DACT), and Ethernet
connection with expandability using the option bus or
plug‑in boards. The two integrated NACs can be
expanded with remote addressable NAC power
boosters and programmed with specific activation
patterns.
The standard control panel includes one SLC that
supports 254 addressable points (254 analog
detectors or modules, or 127 analog sounder bases in
combination with a suitable detector). The control
panel is easily expandable with the FPE‑1000‑SLC
Signaling Line Circuit Plug-in Module, doubling the
address points to 508.
The panel has a compact and solid metal housing with
a keyed lock and a removable dead front door to
access electronics. It features surface and semi-flush
mounting options. On the front of the panel, six light-
emitting diodes (LEDs) show Fire, Carbon Monoxide
(Gas) Alarm, Power, Supervisory, Silenced, and
Trouble conditions. The built‑in keypad can be used
for total system control and programming even when
wearing fireman gloves. In addition, a large 4‑line by
20‑character alphanumeric LCD display shows
programmed device point information. Four keys
enable Drill, Reset, Silence, and Acknowledge
functions.
The FPA‑1000 panels enable various programming
approaches:
• Front panel programming
• On-site programming, using a laptop with the
possibility of pre-programming at the office
• Off-site programming, with remote access via
Ethernet (browser-based).
Front panel programming provides an auto‑learn
function, allowing the installer to configure the system
quickly and easily in default mode. Using a local laptop
or remote access communication, the programming is
carried out by means of a browser‑based user
3 | FPA‑1000 Analog Addressable Fire Panels
On-board Relays
Signaling Line Circuits (SLCs)
Three programmable on-board relays default to global
alarm (zone 226), global system trouble (zone 227),
and global system supervisory (zone 228). They can be
programmed to activate on a variety of conditions
including gas alarm.
The FPA‑1000 Fire Panels communicate with each of
the analog addressable devices located on the SLCs.
The SLCs allow the use of standard non‑twisted,
non‑shielded wiring. Each panel supports two Class B,
Style 4 or one Class A, Style 6 or 7 per SLC.
Option Bus
Certifications and Approvals
On the Option Bus, the FPA-1000 supports:
• up to eight FMR-1000-RCMD Remote Command
Centers and FMR-1000-RA Remote Annunciators in
any combination
Region
Certification
USA
UL
FSZI.S1871: Emergency Alarm System
Control Units (ANSI/UL 2017); UOJZ:
Control Units, System (ANSI/UL 864)
• up to eight D7030X Series LED Annunciators with
eight LED zones each,
• up to eight D7030X Series/D7032 combinations
• up to two Octal Relay Modules or Octal Driver
Modules
• up to four FPP‑RNAC‑8A‑4C Remote Notification
Appliance Circuit Power Supplies.
The outputs of the Octal Relay Modules or Octal Driver
Modules are fully programmable, and can be activated
by system events. These outputs have the same
programming options as the local relays. Each output
operates independently of the other seven to provide
complete flexibility. Communication with the D7035/B
or D7048/B is supervised.
CSFM
7165-1615:0229
#6101
FDNY-
CoA
Installation/Configuration Notes
Mounting Considerations
The cabinet can be either semi-flush (requires optional
FPM‑1000‑SFMK Semi-flush Mounting Kit) or surface
mounted.
Depending on the configuration and the battery
selection, the FPA‑1000 can be quite heavy. When
attaching the enclosure to a surface, use mounting
hardware (not supplied) capable of supporting this
weight, and reinforce the wall as necessary.
Power
A transformer working with 120 VAC or 240 VAC is
supplied standard with the control panel. Two backup
batteries with 7 Ah to 18 Ah each fit inside the fire
panel cabinet. A separate battery box can provide
higher capacity. An automated battery calculator sheet
is available online to aid in battery selection and
submittal paperwork.
Wiring Considerations
The length of wire allowed between the control panel
and the last device on a wiring run depends on the
current drawn on that wiring run. Reducing the
number of devices on a wiring run allows the
individual runs to be longer.
The FPA-1000 panels provide two auxiliary power
supplies (one FWR and one DC) with 0.5 A at 24 V
each, with switchable AUX/RST. This auxiliary power
can run expansion boards or other low current
auxiliary devices.
If not otherwise specified, use wire gauge 12 AWG to
18 AWG (3.3 mm2 to 0.8 mm2).
Notice
For installations requiring battery capacity higher than
40 Ah, a regulated and UL1481 Listed external power
supply can be used. The external power supply
connects through the panel's battery terminals and is
supervised for AC and battery fault by an input module
on the SLC.
The FPP-RNAC-8A-4C Remote NAC Booster adds four
additional Notification Appliance Circuits (NFPA 72,
Class A Style Z or Class B Style Y) to the fire panel or
serves as a power supply for fire protective signaling
systems. This regulated power supply provides up to
8 A of power that is used to recharge batteries and
operate continuous and intermittent alarm loads. This
8 A of power can be distributed through the four NAC
Power Supply circuits that are part of the FPP-
RNAC-8A-4C. The FPP-RNAC-8A-4C is UL Listed for use
in commercial fire alarm applications.
Shared cable is not recommended for the Option
Bus, addressable‑points bus, telephone, or NAC
wiring. Do not run wiring for NAC, Option Bus,
and SLC in the same conduit. Avoid shielded or
twisted-pair wire except for network connections
and special applications where a reduced length
of wiring (roughly 50%) is acceptable for
tolerating a harsh electrical environment.
Point Capacity/Configuration
Each FPA-1000-V2 panel supports up to 508
addresses, 254 per loop. For addresses above 127 on
each loop, only the FAA‑325‑B6S Sounder base,
FAP‑325‑V2F Smoke Detector, FLM‑325-I4‑A,
FLM‑325‑I4‑AI, and FLM-325-IM Contact Monitors,
FLM‑325‑NA4 and FLM‑325‑NAI4 Supervised Output
Modules, FLM-325-2R4-2A and FLM‑325‑2R4‑2AI 2 A
Dual Relay Modules, and FLM‑325‑2R4‑8A and
FLM‑325‑2R4‑8AI 8 A Dual Relay Modules can be used.
For systems requiring more than 127 points per loop,
4 | FPA‑1000 Analog Addressable Fire Panels
Non‑switched, power‑limited, unfiltered,
unsupervised
use these devices on addresses above 127 and other
devices below address 127. All compatible detectors
and modules are addressed using the D5070
Programmer.
•
AUX/RST:
0.5 A at 24 VDC
Switched, power‑limited, filtered,
unsupervised
Parts Included
Environmental
Quant.
Component
Environment:
Indoor, dry
1
1
1
1
3
FPA‑1000‑V2 main board
Enclosure with transformer
Enclosure lock and two keys1 (replacement key: D102)
Hardware pack
Protection Class:
IP 30
Relative Humidity:
Temperature (operating):
Temperature (storage):
Up to 95%, non-condensing
+32°F to +120°F (0°C to +49°C)
+14°F to +131°F (-10°C to +55°C)
Wiring labels (one each in English, Spanish, and
Portuguese)
Mechanical
2
2.21 kΩ EOL resistors (replacement resistors: EOL‑2.2K, 8
per package)
Operating Elements
•
•
LCD:
4‑line x 20‑character display, backlit
Tabs with different language versions for LED and key text
Literature (in English, Spanish, and Portuguese)
LEDs:
Six total: Fire, Gas Alarm, Power,
Supervisory, Silenced, and Trouble
•
•
•
Installation and Operation Guide
Operating Instruction Sheet
Release Notes
•
•
Operation Keys:
Drill, Reset, Silence, and Acknowledge
1 Key code stamped on both lock and key
Alphanumeric
Keypad:
12 alphanumeric keys, escape, enter,
and navigation buttons (left, right, up,
down)
Technical Specifications
Electrical
Interfaces
•
•
•
PSTN/DACT:
2 lines, RJ45
1 x RJ45
Power supply (primary)
Ethernet:
•
Current:
120 VAC: 2 A maximum
240 VAC: 1 A maximum
Peer-to-peer
communication:
Each interconnected panel requires one
of the following:
•
Voltage:
120 VAC, 60 Hz or 240 VAC, 50 Hz
•
•
•
FPE‑1000‑NE Networking Card
3‑Ethermet
FPE‑1000‑NF Networking Card
1‑Ethernet 2‑Fiber Optic
FPE‑1000‑NW Networking Card
1‑Ethernet 2‑Wired
Power supply (secondary)
•
Current (alarm):
•
•
Panel < 0.240 A
SLC = 0.63 A maximum
•
Current (load):
Standby: < 1.25 A
Network Connections
Alarm: 4 A Shared maximum
•
Ethernet:
minimum of CAT 5 cable at a maximum
length of 328 ft (100 m)
•
•
•
•
•
NAC 1 = 2.5 A maximum
NAC 2 = 2.5 A maximum
AUX/FWR = 0.5 A maximum
AUX/RST = 0.5 A maximum
Option bus = 0.5 A maximum
•
Fiber Optics:
multi-mode fiber optic cable (62.5 μm/
125 μm fiber size; 1270 nm to 1380 nm
wavelength) with LC connectors at a
maximum length of 6560 ft (2000 m or a
10 db loss, whichever occurs first)
•
Voltage:
24 VDC
Batteries
•
Wired:
12 AWG (2.05 mm) to 26 AWG
(0.41 mm) twisted pair wire (shielded or
unshielded) at a maximum length of
2952 ft (900 m) or CAT 5 cable or better
at a maximum length of 3280 ft
(1000 m)
•
•
Voltage:
2 x 12 VDC in series
maximum 40 Ah
Capacities:
•
•
in cabinet: 7 Ah to 18 Ah
in additional battery box: 24 Ah
to 40 Ah
Wiring
•
•
Fuses:
15 A blade type
Cable Entries:
Triple knock-outs (3/4, 1/2, 1 in)
Auxiliary power supply (AUX)
AUX/FWR:
•
0.5 A at 24 V FWR
5 | FPA‑1000 Analog Addressable Fire Panels
•
•
Connections:
Wire Gauge:
Pluggable terminal blocks for AUX,
Option Bus, SLC, NAC, Main Board
Relays
D5070 Analog Device Programmer
Programs address settings on EEPROM‑programmable
analog devices
Order number D5070
12 AWG to 18 AWG (0.75 mm2 to
3.25 mm2)
D7030X LED Annunciator
Eight zone LEDs indicate alarm conditions.
Order number D7030X
Enclosure
•
•
Material:
Color:
Cold rolled steel, 19 gauge (1.2 mm)
Red
D7030X‑S2 LED Annunciator
Two LEDs indicate supervisory conditions; six indicate
alarm conditions.
Dimensions
Order number D7030X-S2
•
•
•
Enclosure (W x H x
14.5 in. x 4.3 in. x 22.7 in.
(36.8 cm x 10.9 cm x 57.7 cm)
D):
D7030X‑S8 LED Annunciator
All eight zone LEDs indicate supervisory conditions.
Order number D7030X-S8
with trim ring (W x
D):
17.5 in. x 25.6 in.(44.5 cm x 65.0 cm)
3.25 in. / 1.05 in. (8.25 cm / 2.7 cm)
D7032 Eight‑zone LED Annunciator Expander
Use with D7030X Series LED Annunciators
Order number D7032
Semi-flush
mounted (H
recessed / H
flush):
D7035 Octal Relay Module
Weight (enclosure):
18.1 lb (8.32 kg)
Provide eight Form C relay outputs (w/o enclosure) for
the D7024, FPD-7024, or FPA‑1000 Fire Alarm Control
Panels (FACP)
Ordering Information
Order number D7035
FPA-1000-V2 Analog Addressable Fire Panel
Order number FPA-1000-V2
D7035B Octal Relay Module with Enclosure
Provide eight Form C relay outputs (w/ enclosure) for
the D7024, FPD-7024, or FPA‑1000 Fire Alarm Control
Panels (FACP)
FPA-1000-LC FPA-1000 Analog Addressable Fire Panel
less enclosure
Analog Addressable Fire Panel without enclosure
Order number FPA-1000-LC
Order number D7035B
D7048 Octal Driver Module
Module and hardware
Order number D7048
FPA-1000-LT Analog Addressable Fire Panel less trans-
former
Analog Addressable Fire Panel without transformer for
Latin America only
D7048B Octal Driver Module with Fire Enclosure
Module, mounting plate, metal enclosure, and
hardware
Order number FPA-1000-LT
Accessories
Order number D7048B
BATB-40 Battery Box
The BATB-40 Battery Box holds two dry or wet cell
batteries. The box can be used with fire alarm systems
or intrusion systems. It measures 21 in. x 20.75 in. x
7.25 in. (53.3 cm x 52.7 cm x 18.4 cm).
Order number BATB-40
FAA‑325‑2.5 Sampling Tube (2.5 ft)
2.5 ft (762 mm) long sample tube for use with the
FAD‑325 and FAD‑325‑R Analog Duct Detectors
Order number FAA-325-2.5
FAA‑325‑5 Sampling Tube (5 ft)
BATB-80 Battery Box with Shelf
5 ft (1.52 m) long sample tube for use with the
FAD‑325 and FAD‑325‑R Analog Duct Detectors
Order number FAA-325-5
The BATB-80 Battery Box holds up to four dry or wet
cell batteries. The box can be used with fire alarm
systems or with intrusion systems. It measures
12.25 in. x 20.75 in. x 7.25 in. (31.1 cm x 52.7 cm x
18.4 cm) on the bottom and 9.2 in. x 20.75 in. x
7.25 in. (23.2 cm x 52.7 cm x 7.25 cm) on the shelf.
Order number BATB-80
FAA‑325‑10 Sampling Tube (10 ft)
10 ft (3.05 m) long sample tube for use with the
FAD‑325 and FAD‑325‑R Analog Duct Detectors
Order number FAA-325-10
FAA‑325‑B4 4‑inch Analog Sensor Base
Is combined with analog addressable detectors that
use the advanced digital communication protocol to
provide early fire warning for life safety and property
protection
BATB-SHELF Optional Battery Shelf
An optional battery shelf for the BATB-40. It allows
two additional batteries to be placed in the battery
box.
Order number BATB-SHELF
Order number FAA-325-B4
6 | FPA‑1000 Analog Addressable Fire Panels
FAA‑325‑B6 6‑inch Analog Sensor Base
6‑inch (152.4 mm) base for FAH‑325, FAI‑325, and
FAP‑325 sensors. US sales only!
FAP-325-V2F Analog Photoelectric Smoke Detector Flat
Used to detect fast‑flaming fires and dense smoke
typically given off by plastic, foam, paper, wood, and
other materials that tend to smolder
Order number FAA-325-B6
Order number FAP-325-V2F
FAA‑325‑B6S Analog Sounder Base
Contains an addressable sounder which provides an
audible alarm in the immediate vicinity and only works
in combination with one of the FAH‑325, FAI-325, or
FAP‑325 series analog sensors
FAP-440 Analog Photoelectric Detector
Order number FAP-440
FAP-440-D Analog Dual-Photoelectric Detector
Order number FAP-440-D
Order number FAA-325-B6S
FAP-440-DT Analog Multisensor Detector Dual-Photo/
Heat
Order number FAP-440-DT
FAA-440-B4 Analog Standard Base 4-inch
Order number FAA-440-B4
FAA-440-B4-ISO Analog Isolator Base 4-inch
Order number FAA-440-B4-ISO
FAP-440-DTC Analog Multicriteria Detector Dual-Photo/
Heat/CO
Order number FAP-440-DTC
FAA-440-B6 Analog Standard Base 6-inch
Order number FAA-440-B6
FAP-440-T Analog Multisensor Detector Photo/Heat
Order number FAP-440-T
FAA-440-B6-ISO Analog Isolator Base 6-inch
Order number FAA-440-B6-ISO
FAP-440-TC Analog Multicriteria Detector Photo/
Heat/CO
Order number FAP-440-TC
FAD-325-DH Analog Duct Smoke Detector Replacement
Head
Replacement detector for the FAD-325 and the
FAD‑325‑DH Analog Duct Smoke Detectors for use in
heating, ventilation, and air conditioning systems
Order number FAD-325-DH
FCC‑380 Carbon Monoxide Detector (Macurco CM‑E1)
Carbon monoxide detector
Order number FCC-380
FLM‑325‑2I4 Dual Input Monitor
FAD‑325 Analog Duct Detector
Provides two independent contact monitoring circuits
to monitor Normally Open (NO) or Normally Closed
(NC) dry contact types of fire alarm devices
Order number FLM-325-2I4
Housing for use in heating, ventilation and air
conditioning systems (HVAC) that comes with an
FAD‑325‑DH Analog Duct Smoke Detector
Replacement
Order number FAD-325
FLM‑325‑N4 Supervised Output Module
Provides a supervised pole reversal output used for
acoustic and optical signaling devices or to trigger a
remote NAC power expander; compatible with 127
addresses
FAD‑325‑R Analog Duct Detector with Relay
Housing with two Form C alarm contacts for use in
heating, ventilation and air conditioning systems
(HVAC) that comes with an FAD‑325‑DH Analog Duct
Smoke Detector Replacement. US sales only!
Order number FAD-325-R
Order number FLM-325-N4
FLM-325-NA4 Supervised Output Module (Class A and
B)
Can be wired for Class A or Class B circuits;
compatible with 254 addresses
Order number FLM-325-NA4
FAH‑325 Analog Heat Detector
Used in indoor environments with high ambient
temperatures such as kitchens, boiler rooms, or drying
rooms; compatible with 127 addresses
Order number FAH-325
FLM-325-NAI4 Supervised Output Module (Class A and
B, with isolator)
Built-in short circuit isolator circuitry; can be wired for
Class A or Class B circuits; compatible with 254
addresses
FAH-440 Analog Heat Detector
Use with FAA‑440 Series bases and FAP-1000 Analog
Addressable Fire Panels to provide general property
protection
Order number FLM-325-NAI4
Order number FAH-440
FLM‑325‑2R4 Dual Relay Module
FAI‑325 Analog Ionization Smoke Detector
For early warning of trouble from superheated or
flaming combustibles where outside RFI and other
electrical interference is expected. US sales only!
Order number FAI-325
Provides two independently-controlled Form C
contacts for a variety of Normally Open and Normally
Closed applications; compatible with 127 addresses
Order number FLM-325-2R4
7 | FPA‑1000 Analog Addressable Fire Panels
FLM‑325‑2R4‑2A Dual Relay Module 2 A
Provides 2 A current at two independently-controlled
Form C contacts for a variety of Normally Open and
Normally Closed applications; compatible with 254
addresses
FLM‑325‑ISO Short Circuit Isolator
Isolates a shorted section on a specific polling circuit
from the rest of the system to minimize the loss of
communication
Order number FLM-325-ISO
Order number FLM-325-2R4-2A
FMM‑325A Single‑action Manual Station
FLM‑325‑2R4‑2AI Dual Relay Module 2 A with Isolator
Provides 2 A current with built-in short circuit isolator
circuitry at two independently-controlled Form C
contacts for a variety of Normally Open and Normally
Closed applications; compatible with 254 addresses
Order number FLM-325-2R4-2AI
Communicates with the FPA‑1000 Analog Addressable
Fire Panels, D9024, D8024, and D10024A FACPs (both
power and data) over a two‑wire polling circuit
Order number FMM-325A
FMM‑325A‑D Double‑action Manual Station
Communicates with the FPA‑1000 Analog Addressable
Fire Panels, D9024, D8024, and D10024A FACPs (both
power and data) over a two‑wire polling circuit
Order number FMM-325A-D
FLM‑325‑2R4‑8A Dual Relay Module 8 A
Provides 8 A current at two independently-controlled
Form C contacts for a variety of Normally Open and
Normally Closed applications; compatible with 254
addresses
FMR‑1000‑RA Remote Annunciator
LCD annunciator without system control capability for
use with the FPA‑1000 Analog Addressable Fire Panels
Order number FMR-1000-RA
Order number FLM-325-2R4-8A
FLM‑325‑2R4‑8AI Dual Relay Module 8 A with Isolator
Provides 8 A current with built-in short circuit isolator
circuitry at two independently-controlled Form C
contacts for a variety of Normally Open and Normally
Closed applications; compatible with 254 addresses
Order number FLM-325-2R4-8AI
FMR‑1000‑RCMD Remote Command Center
LCD annunciator with system control capability for use
with FPA‑1000 Analog Addressable fire Panels
Order number FMR-1000-RCMD
FPE‑1000‑CITY City Tie Plug‑in Module
Provides the FPA‑1000 Analog Addressable Fire Panels
with two supervised City Tie Local Energy circuits or
Reverse Polarity circuits
FLM‑325‑CZM4 Conventional Zone Module
Enables the FACP to interface and monitor up to 25
conventional devices depending on the device type
such as two‑wire smoke detectors or pull stations
Order number FLM-325-CZM4
Order number FPE-1000-CITY
FPE‑1000‑NE Networking Card 3‑Ethermet
Ethernet Networking Card for peer‑to‑peer
communication in an FPA‑1000‑V2 networked system
Order number FPE-1000-NE
FLM‑325‑I4 Contact Monitor 4‑inch
Mounted to a cover plate for a 4‑inch square or double
gang electrical back box; a bi‑colored LED provides
module status; compatible with 127 addresses
Order number FLM-325-I4
FPE‑1000‑NF Networking Card 1‑Ethernet 2‑Fiber Optic
Fiber Optic Networking Card for peer‑to‑peer
communication in an FPA‑1000 networked system
Order number FPE-1000-NF
FLM-325-I4-A Contact Monitor 4-inch Class A
Can be wired for Class A or Class B circuits; mounted
to a cover plate for a 4‑inch square or double gang
electrical back box; bi‑colored LED provides module
status; compatible with 254 addresses
FPE‑1000‑NW Networking Card 1‑Ethernet 2‑Wired
Wired Networking Card for peer‑to‑peer
communication in an FPA‑1000 networked system
Order number FPE-1000-NW
Order number FLM-325-I4-A
FLM-325-I4-AI Contact Monitor 4-inch Class A with Isola-
tor
FPE‑1000‑SLC Signaling Line Circuit Plug‑in Module
Provides a Signaling Line Circuit (SLC) for connection
of analog devices to the FPA‑1000 Analog Addressable
Fire Panels
Can be wired for Class A or Class B circuits; has
built‑in short circuit isolator circuitry; mounted to a
cover plate for a 4‑inch square or double gang
electrical back box; bi‑colored LED provides module
status; compatible with 254 addresses
Order number FLM-325-I4-AI
Order number FPE-1000-SLC
FPM‑1000‑ENC Enclosure with Dead Front Door
Enclosure with dead front door
Order number FPM-1000-ENC
FLM‑325‑IM Contact Module
Allows compatible fire alarm control panels (FACP) to
supervise Form A or B dry contact devices in a polling
circuit
FPM-1000-SFMK Semi-flush Mounting Kit
The FPM-1000-SFMK Semi-flush Mounting Kit includes
a trim ring and mounting hardware.
Order number FLM-325-IM
Order number FPM-1000-SFMK
8 | FPA‑1000 Analog Addressable Fire Panels
FPP‑RNAC‑8A‑4C Remote Notification Appliance Circuit
(RNAC) Power Supply
Adds four additional notification appliance circuits to a
fire alarm control panel
Order number FPP-RNAC-8A-4C
Represented by:
Americas:
Europe, Middle East, Africa:
Bosch Security Systems B.V.
P.O. Box 80002
5617 BA Eindhoven, The Netherlands
Phone: + 31 40 2577 284
Fax: +31 40 2577 330
Asia-Pacific:
Robert Bosch (SEA) Pte Ltd, Security
Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6571 2808
Fax: +65 6571 2699
China:
Bosch (Shanghai) Security Systems Ltd. Robert Bosch Ltda Security Systems Division
America Latina:
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 800 289 0096
Fax: +1 585 223 9180
201 Building, No. 333 Fuquan Road
North IBP
Via Anhanguera, Km 98
CEP 13065-900
Changning District, Shanghai
200335 China
Campinas, Sao Paulo, Brazil
Phone: +55 19 2103 2860
Fax: +55 19 2103 2862
Phone +86 21 22181111
Fax: +86 21 22182398
© Bosch Security Systems 2012 | Data subject to change without notice
2690096139 | en, V5, 03. Aug 2012
|