Bosch Appliances Smoke Alarm FPA 1000 User Manual

Fire Alarm Systems | FPA‑1000 Analog Addressable Fire Panels  
FPA‑1000 Analog Addressable Fire Panels  
u Support for up to 508 points on two analog  
addressable loops  
u Built-in Ethernet connector for web-browser based  
programming and Conettix Alarm-over-IP  
communication  
u Two on-board NACs and dual-line PSTN DACT  
u Peer-to-peer networking of up to eight panels in a  
single group  
u Simple system management and free online training  
The FPA‑1000 Analog Addressable Fire Panels are a  
scalable solution for fire detection. Protect your small  
office with a single system or connect multiple panels  
together as your needs grow. Networking capabilities  
support the monitoring of up to 2,000 addressable  
points in one system for campuses or other large  
commercial environments.  
The FPA‑1000 panels combine complete built-in Fire  
Alarm Control Panel (FACP) equipment such as  
Notification Appliance Circuits (NACs), Signaling Line  
Circuits (SLCs), relays, power supply, Digital Alarm  
Communicator Transmitter (DACT), and Ethernet  
connection with expandability using the option bus or  
plug‑in boards. The two integrated NACs can be  
expanded with remote addressable NAC power  
boosters and programmed with specific activation  
patterns.  
The standard control panel includes one SLC that  
supports 254 addressable points (254 analog  
detectors or modules, or 127 analog sounder bases in  
combination with a suitable detector). The control  
panel is easily expandable with the FPE‑1000‑SLC  
Signaling Line Circuit Plug-in Module, doubling the  
address points to 508.  
The panel has a compact and solid metal housing with  
a keyed lock and a removable dead front door to  
access electronics. It features surface and semi-flush  
mounting options. On the front of the panel, six light-  
emitting diodes (LEDs) show Fire, Carbon Monoxide  
(Gas) Alarm, Power, Supervisory, Silenced, and  
Trouble conditions. The built‑in keypad can be used  
for total system control and programming even when  
wearing fireman gloves. In addition, a large 4‑line by  
20‑character alphanumeric LCD display shows  
programmed device point information. Four keys  
enable Drill, Reset, Silence, and Acknowledge  
functions.  
The FPA‑1000 panels enable various programming  
approaches:  
• Front panel programming  
• On-site programming, using a laptop with the  
possibility of pre-programming at the office  
• Off-site programming, with remote access via  
Ethernet (browser-based).  
Front panel programming provides an auto‑learn  
function, allowing the installer to configure the system  
quickly and easily in default mode. Using a local laptop  
or remote access communication, the programming is  
carried out by means of a browser‑based user  
 
3 | FPA‑1000 Analog Addressable Fire Panels  
On-board Relays  
Signaling Line Circuits (SLCs)  
Three programmable on-board relays default to global  
alarm (zone 226), global system trouble (zone 227),  
and global system supervisory (zone 228). They can be  
programmed to activate on a variety of conditions  
including gas alarm.  
The FPA‑1000 Fire Panels communicate with each of  
the analog addressable devices located on the SLCs.  
The SLCs allow the use of standard non‑twisted,  
non‑shielded wiring. Each panel supports two Class B,  
Style 4 or one Class A, Style 6 or 7 per SLC.  
Option Bus  
Certifications and Approvals  
On the Option Bus, the FPA-1000 supports:  
• up to eight FMR-1000-RCMD Remote Command  
Centers and FMR-1000-RA Remote Annunciators in  
any combination  
Region  
Certification  
USA  
UL  
FSZI.S1871: Emergency Alarm System  
Control Units (ANSI/UL 2017); UOJZ:  
Control Units, System (ANSI/UL 864)  
• up to eight D7030X Series LED Annunciators with  
eight LED zones each,  
• up to eight D7030X Series/D7032 combinations  
• up to two Octal Relay Modules or Octal Driver  
Modules  
• up to four FPP‑RNAC‑8A‑4C Remote Notification  
Appliance Circuit Power Supplies.  
The outputs of the Octal Relay Modules or Octal Driver  
Modules are fully programmable, and can be activated  
by system events. These outputs have the same  
programming options as the local relays. Each output  
operates independently of the other seven to provide  
complete flexibility. Communication with the D7035/B  
or D7048/B is supervised.  
CSFM  
7165-1615:0229  
#6101  
FDNY-  
CoA  
Installation/Configuration Notes  
Mounting Considerations  
The cabinet can be either semi-flush (requires optional  
FPM‑1000‑SFMK Semi-flush Mounting Kit) or surface  
mounted.  
Depending on the configuration and the battery  
selection, the FPA‑1000 can be quite heavy. When  
attaching the enclosure to a surface, use mounting  
hardware (not supplied) capable of supporting this  
weight, and reinforce the wall as necessary.  
Power  
A transformer working with 120 VAC or 240 VAC is  
supplied standard with the control panel. Two backup  
batteries with 7 Ah to 18 Ah each fit inside the fire  
panel cabinet. A separate battery box can provide  
higher capacity. An automated battery calculator sheet  
is available online to aid in battery selection and  
submittal paperwork.  
Wiring Considerations  
The length of wire allowed between the control panel  
and the last device on a wiring run depends on the  
current drawn on that wiring run. Reducing the  
number of devices on a wiring run allows the  
individual runs to be longer.  
The FPA-1000 panels provide two auxiliary power  
supplies (one FWR and one DC) with 0.5 A at 24 V  
each, with switchable AUX/RST. This auxiliary power  
can run expansion boards or other low current  
auxiliary devices.  
If not otherwise specified, use wire gauge 12 AWG to  
18 AWG (3.3 mm2 to 0.8 mm2).  
Notice  
For installations requiring battery capacity higher than  
40 Ah, a regulated and UL1481 Listed external power  
supply can be used. The external power supply  
connects through the panel's battery terminals and is  
supervised for AC and battery fault by an input module  
on the SLC.  
The FPP-RNAC-8A-4C Remote NAC Booster adds four  
additional Notification Appliance Circuits (NFPA 72,  
Class A Style Z or Class B Style Y) to the fire panel or  
serves as a power supply for fire protective signaling  
systems. This regulated power supply provides up to  
8 A of power that is used to recharge batteries and  
operate continuous and intermittent alarm loads. This  
8 A of power can be distributed through the four NAC  
Power Supply circuits that are part of the FPP-  
RNAC-8A-4C. The FPP-RNAC-8A-4C is UL Listed for use  
in commercial fire alarm applications.  
Shared cable is not recommended for the Option  
Bus, addressable‑points bus, telephone, or NAC  
wiring. Do not run wiring for NAC, Option Bus,  
and SLC in the same conduit. Avoid shielded or  
twisted-pair wire except for network connections  
and special applications where a reduced length  
of wiring (roughly 50%) is acceptable for  
tolerating a harsh electrical environment.  
Point Capacity/Configuration  
Each FPA-1000-V2 panel supports up to 508  
addresses, 254 per loop. For addresses above 127 on  
each loop, only the FAA‑325‑B6S Sounder base,  
FAP‑325‑V2F Smoke Detector, FLM‑325-I4‑A,  
FLM‑325‑I4‑AI, and FLM-325-IM Contact Monitors,  
FLM‑325‑NA4 and FLM‑325‑NAI4 Supervised Output  
Modules, FLM-325-2R4-2A and FLM‑325‑2R4‑2AI 2 A  
Dual Relay Modules, and FLM‑325‑2R4‑8A and  
FLM‑325‑2R4‑8AI 8 A Dual Relay Modules can be used.  
For systems requiring more than 127 points per loop,  
 
4 | FPA‑1000 Analog Addressable Fire Panels  
Non‑switched, power‑limited, unfiltered,  
unsupervised  
use these devices on addresses above 127 and other  
devices below address 127. All compatible detectors  
and modules are addressed using the D5070  
Programmer.  
AUX/RST:  
0.5 A at 24 VDC  
Switched, power‑limited, filtered,  
unsupervised  
Parts Included  
Environmental  
Quant.  
Component  
Environment:  
Indoor, dry  
1
1
1
1
3
FPA‑1000‑V2 main board  
Enclosure with transformer  
Enclosure lock and two keys1 (replacement key: D102)  
Hardware pack  
Protection Class:  
IP 30  
Relative Humidity:  
Temperature (operating):  
Temperature (storage):  
Up to 95%, non-condensing  
+32°F to +120°F (0°C to +49°C)  
+14°F to +131°F (-10°C to +55°C)  
Wiring labels (one each in English, Spanish, and  
Portuguese)  
Mechanical  
2
2.21 kΩ EOL resistors (replacement resistors: EOL‑2.2K, 8  
per package)  
Operating Elements  
LCD:  
4‑line x 20‑character display, backlit  
Tabs with different language versions for LED and key text  
Literature (in English, Spanish, and Portuguese)  
LEDs:  
Six total: Fire, Gas Alarm, Power,  
Supervisory, Silenced, and Trouble  
Installation and Operation Guide  
Operating Instruction Sheet  
Release Notes  
Operation Keys:  
Drill, Reset, Silence, and Acknowledge  
1 Key code stamped on both lock and key  
Alphanumeric  
Keypad:  
12 alphanumeric keys, escape, enter,  
and navigation buttons (left, right, up,  
down)  
Technical Specifications  
Electrical  
Interfaces  
PSTN/DACT:  
2 lines, RJ45  
1 x RJ45  
Power supply (primary)  
Ethernet:  
Current:  
120 VAC: 2 A maximum  
240 VAC: 1 A maximum  
Peer-to-peer  
communication:  
Each interconnected panel requires one  
of the following:  
Voltage:  
120 VAC, 60 Hz or 240 VAC, 50 Hz  
FPE‑1000‑NE Networking Card  
3‑Ethermet  
FPE‑1000‑NF Networking Card  
1‑Ethernet 2‑Fiber Optic  
FPE‑1000‑NW Networking Card  
1‑Ethernet 2‑Wired  
Power supply (secondary)  
Current (alarm):  
Panel < 0.240 A  
SLC = 0.63 A maximum  
Current (load):  
Standby: < 1.25 A  
Network Connections  
Alarm: 4 A Shared maximum  
Ethernet:  
minimum of CAT 5 cable at a maximum  
length of 328 ft (100 m)  
NAC 1 = 2.5 A maximum  
NAC 2 = 2.5 A maximum  
AUX/FWR = 0.5 A maximum  
AUX/RST = 0.5 A maximum  
Option bus = 0.5 A maximum  
Fiber Optics:  
multi-mode fiber optic cable (62.5 μm/  
125 μm fiber size; 1270 nm to 1380 nm  
wavelength) with LC connectors at a  
maximum length of 6560 ft (2000 m or a  
10 db loss, whichever occurs first)  
Voltage:  
24 VDC  
Batteries  
Wired:  
12 AWG (2.05 mm) to 26 AWG  
(0.41 mm) twisted pair wire (shielded or  
unshielded) at a maximum length of  
2952 ft (900 m) or CAT 5 cable or better  
at a maximum length of 3280 ft  
(1000 m)  
Voltage:  
2 x 12 VDC in series  
maximum 40 Ah  
Capacities:  
in cabinet: 7 Ah to 18 Ah  
in additional battery box: 24 Ah  
to 40 Ah  
Wiring  
Fuses:  
15 A blade type  
Cable Entries:  
Triple knock-outs (3/4, 1/2, 1 in)  
Auxiliary power supply (AUX)  
AUX/FWR:  
0.5 A at 24 V FWR  
 
5 | FPA‑1000 Analog Addressable Fire Panels  
Connections:  
Wire Gauge:  
Pluggable terminal blocks for AUX,  
Option Bus, SLC, NAC, Main Board  
Relays  
D5070 Analog Device Programmer  
Programs address settings on EEPROM‑programmable  
analog devices  
Order number D5070  
12 AWG to 18 AWG (0.75 mm2 to  
3.25 mm2)  
D7030X LED Annunciator  
Eight zone LEDs indicate alarm conditions.  
Order number D7030X  
Enclosure  
Material:  
Color:  
Cold rolled steel, 19 gauge (1.2 mm)  
Red  
D7030X‑S2 LED Annunciator  
Two LEDs indicate supervisory conditions; six indicate  
alarm conditions.  
Dimensions  
Order number D7030X-S2  
Enclosure (W x H x  
14.5 in. x 4.3 in. x 22.7 in.  
(36.8 cm x 10.9 cm x 57.7 cm)  
D):  
D7030X‑S8 LED Annunciator  
All eight zone LEDs indicate supervisory conditions.  
Order number D7030X-S8  
with trim ring (W x  
D):  
17.5 in. x 25.6 in.(44.5 cm x 65.0 cm)  
3.25 in. / 1.05 in. (8.25 cm / 2.7 cm)  
D7032 Eight‑zone LED Annunciator Expander  
Use with D7030X Series LED Annunciators  
Order number D7032  
Semi-flush  
mounted (H  
recessed / H  
flush):  
D7035 Octal Relay Module  
Weight (enclosure):  
18.1 lb (8.32 kg)  
Provide eight Form C relay outputs (w/o enclosure) for  
the D7024, FPD-7024, or FPA‑1000 Fire Alarm Control  
Panels (FACP)  
Ordering Information  
Order number D7035  
FPA-1000-V2 Analog Addressable Fire Panel  
Order number FPA-1000-V2  
D7035B Octal Relay Module with Enclosure  
Provide eight Form C relay outputs (w/ enclosure) for  
the D7024, FPD-7024, or FPA‑1000 Fire Alarm Control  
Panels (FACP)  
FPA-1000-LC FPA-1000 Analog Addressable Fire Panel  
less enclosure  
Analog Addressable Fire Panel without enclosure  
Order number FPA-1000-LC  
Order number D7035B  
D7048 Octal Driver Module  
Module and hardware  
Order number D7048  
FPA-1000-LT Analog Addressable Fire Panel less trans-  
former  
Analog Addressable Fire Panel without transformer for  
Latin America only  
D7048B Octal Driver Module with Fire Enclosure  
Module, mounting plate, metal enclosure, and  
hardware  
Order number FPA-1000-LT  
Accessories  
Order number D7048B  
BATB-40 Battery Box  
The BATB-40 Battery Box holds two dry or wet cell  
batteries. The box can be used with fire alarm systems  
or intrusion systems. It measures 21 in. x 20.75 in. x  
7.25 in. (53.3 cm x 52.7 cm x 18.4 cm).  
Order number BATB-40  
FAA‑325‑2.5 Sampling Tube (2.5 ft)  
2.5 ft (762 mm) long sample tube for use with the  
FAD‑325 and FAD‑325‑R Analog Duct Detectors  
Order number FAA-325-2.5  
FAA‑325‑5 Sampling Tube (5 ft)  
BATB-80 Battery Box with Shelf  
5 ft (1.52 m) long sample tube for use with the  
FAD‑325 and FAD‑325‑R Analog Duct Detectors  
Order number FAA-325-5  
The BATB-80 Battery Box holds up to four dry or wet  
cell batteries. The box can be used with fire alarm  
systems or with intrusion systems. It measures  
12.25 in. x 20.75 in. x 7.25 in. (31.1 cm x 52.7 cm x  
18.4 cm) on the bottom and 9.2 in. x 20.75 in. x  
7.25 in. (23.2 cm x 52.7 cm x 7.25 cm) on the shelf.  
Order number BATB-80  
FAA‑325‑10 Sampling Tube (10 ft)  
10 ft (3.05 m) long sample tube for use with the  
FAD‑325 and FAD‑325‑R Analog Duct Detectors  
Order number FAA-325-10  
FAA‑325‑B4 4‑inch Analog Sensor Base  
Is combined with analog addressable detectors that  
use the advanced digital communication protocol to  
provide early fire warning for life safety and property  
protection  
BATB-SHELF Optional Battery Shelf  
An optional battery shelf for the BATB-40. It allows  
two additional batteries to be placed in the battery  
box.  
Order number BATB-SHELF  
Order number FAA-325-B4  
 
6 | FPA‑1000 Analog Addressable Fire Panels  
FAA‑325‑B6 6‑inch Analog Sensor Base  
6‑inch (152.4 mm) base for FAH‑325, FAI‑325, and  
FAP‑325 sensors. US sales only!  
FAP-325-V2F Analog Photoelectric Smoke Detector Flat  
Used to detect fast‑flaming fires and dense smoke  
typically given off by plastic, foam, paper, wood, and  
other materials that tend to smolder  
Order number FAA-325-B6  
Order number FAP-325-V2F  
FAA‑325‑B6S Analog Sounder Base  
Contains an addressable sounder which provides an  
audible alarm in the immediate vicinity and only works  
in combination with one of the FAH‑325, FAI-325, or  
FAP‑325 series analog sensors  
FAP-440 Analog Photoelectric Detector  
Order number FAP-440  
FAP-440-D Analog Dual-Photoelectric Detector  
Order number FAP-440-D  
Order number FAA-325-B6S  
FAP-440-DT Analog Multisensor Detector Dual-Photo/  
Heat  
Order number FAP-440-DT  
FAA-440-B4 Analog Standard Base 4-inch  
Order number FAA-440-B4  
FAA-440-B4-ISO Analog Isolator Base 4-inch  
Order number FAA-440-B4-ISO  
FAP-440-DTC Analog Multicriteria Detector Dual-Photo/  
Heat/CO  
Order number FAP-440-DTC  
FAA-440-B6 Analog Standard Base 6-inch  
Order number FAA-440-B6  
FAP-440-T Analog Multisensor Detector Photo/Heat  
Order number FAP-440-T  
FAA-440-B6-ISO Analog Isolator Base 6-inch  
Order number FAA-440-B6-ISO  
FAP-440-TC Analog Multicriteria Detector Photo/  
Heat/CO  
Order number FAP-440-TC  
FAD-325-DH Analog Duct Smoke Detector Replacement  
Head  
Replacement detector for the FAD-325 and the  
FAD‑325‑DH Analog Duct Smoke Detectors for use in  
heating, ventilation, and air conditioning systems  
Order number FAD-325-DH  
FCC‑380 Carbon Monoxide Detector (Macurco CM‑E1)  
Carbon monoxide detector  
Order number FCC-380  
FLM‑325‑2I4 Dual Input Monitor  
FAD‑325 Analog Duct Detector  
Provides two independent contact monitoring circuits  
to monitor Normally Open (NO) or Normally Closed  
(NC) dry contact types of fire alarm devices  
Order number FLM-325-2I4  
Housing for use in heating, ventilation and air  
conditioning systems (HVAC) that comes with an  
FAD‑325‑DH Analog Duct Smoke Detector  
Replacement  
Order number FAD-325  
FLM‑325‑N4 Supervised Output Module  
Provides a supervised pole reversal output used for  
acoustic and optical signaling devices or to trigger a  
remote NAC power expander; compatible with 127  
addresses  
FAD‑325‑R Analog Duct Detector with Relay  
Housing with two Form C alarm contacts for use in  
heating, ventilation and air conditioning systems  
(HVAC) that comes with an FAD‑325‑DH Analog Duct  
Smoke Detector Replacement. US sales only!  
Order number FAD-325-R  
Order number FLM-325-N4  
FLM-325-NA4 Supervised Output Module (Class A and  
B)  
Can be wired for Class A or Class B circuits;  
compatible with 254 addresses  
Order number FLM-325-NA4  
FAH‑325 Analog Heat Detector  
Used in indoor environments with high ambient  
temperatures such as kitchens, boiler rooms, or drying  
rooms; compatible with 127 addresses  
Order number FAH-325  
FLM-325-NAI4 Supervised Output Module (Class A and  
B, with isolator)  
Built-in short circuit isolator circuitry; can be wired for  
Class A or Class B circuits; compatible with 254  
addresses  
FAH-440 Analog Heat Detector  
Use with FAA‑440 Series bases and FAP-1000 Analog  
Addressable Fire Panels to provide general property  
protection  
Order number FLM-325-NAI4  
Order number FAH-440  
FLM‑325‑2R4 Dual Relay Module  
FAI‑325 Analog Ionization Smoke Detector  
For early warning of trouble from superheated or  
flaming combustibles where outside RFI and other  
electrical interference is expected. US sales only!  
Order number FAI-325  
Provides two independently-controlled Form C  
contacts for a variety of Normally Open and Normally  
Closed applications; compatible with 127 addresses  
Order number FLM-325-2R4  
 
7 | FPA‑1000 Analog Addressable Fire Panels  
FLM‑325‑2R4‑2A Dual Relay Module 2 A  
Provides 2 A current at two independently-controlled  
Form C contacts for a variety of Normally Open and  
Normally Closed applications; compatible with 254  
addresses  
FLM‑325‑ISO Short Circuit Isolator  
Isolates a shorted section on a specific polling circuit  
from the rest of the system to minimize the loss of  
communication  
Order number FLM-325-ISO  
Order number FLM-325-2R4-2A  
FMM‑325A Single‑action Manual Station  
FLM‑325‑2R4‑2AI Dual Relay Module 2 A with Isolator  
Provides 2 A current with built-in short circuit isolator  
circuitry at two independently-controlled Form C  
contacts for a variety of Normally Open and Normally  
Closed applications; compatible with 254 addresses  
Order number FLM-325-2R4-2AI  
Communicates with the FPA‑1000 Analog Addressable  
Fire Panels, D9024, D8024, and D10024A FACPs (both  
power and data) over a two‑wire polling circuit  
Order number FMM-325A  
FMM‑325A‑D Double‑action Manual Station  
Communicates with the FPA‑1000 Analog Addressable  
Fire Panels, D9024, D8024, and D10024A FACPs (both  
power and data) over a two‑wire polling circuit  
Order number FMM-325A-D  
FLM‑325‑2R4‑8A Dual Relay Module 8 A  
Provides 8 A current at two independently-controlled  
Form C contacts for a variety of Normally Open and  
Normally Closed applications; compatible with 254  
addresses  
FMR‑1000‑RA Remote Annunciator  
LCD annunciator without system control capability for  
use with the FPA‑1000 Analog Addressable Fire Panels  
Order number FMR-1000-RA  
Order number FLM-325-2R4-8A  
FLM‑325‑2R4‑8AI Dual Relay Module 8 A with Isolator  
Provides 8 A current with built-in short circuit isolator  
circuitry at two independently-controlled Form C  
contacts for a variety of Normally Open and Normally  
Closed applications; compatible with 254 addresses  
Order number FLM-325-2R4-8AI  
FMR‑1000‑RCMD Remote Command Center  
LCD annunciator with system control capability for use  
with FPA‑1000 Analog Addressable fire Panels  
Order number FMR-1000-RCMD  
FPE‑1000‑CITY City Tie Plug‑in Module  
Provides the FPA‑1000 Analog Addressable Fire Panels  
with two supervised City Tie Local Energy circuits or  
Reverse Polarity circuits  
FLM‑325‑CZM4 Conventional Zone Module  
Enables the FACP to interface and monitor up to 25  
conventional devices depending on the device type  
such as two‑wire smoke detectors or pull stations  
Order number FLM-325-CZM4  
Order number FPE-1000-CITY  
FPE‑1000‑NE Networking Card 3‑Ethermet  
Ethernet Networking Card for peer‑to‑peer  
communication in an FPA‑1000‑V2 networked system  
Order number FPE-1000-NE  
FLM‑325‑I4 Contact Monitor 4‑inch  
Mounted to a cover plate for a 4‑inch square or double  
gang electrical back box; a bi‑colored LED provides  
module status; compatible with 127 addresses  
Order number FLM-325-I4  
FPE‑1000‑NF Networking Card 1‑Ethernet 2‑Fiber Optic  
Fiber Optic Networking Card for peer‑to‑peer  
communication in an FPA‑1000 networked system  
Order number FPE-1000-NF  
FLM-325-I4-A Contact Monitor 4-inch Class A  
Can be wired for Class A or Class B circuits; mounted  
to a cover plate for a 4‑inch square or double gang  
electrical back box; bi‑colored LED provides module  
status; compatible with 254 addresses  
FPE‑1000‑NW Networking Card 1‑Ethernet 2‑Wired  
Wired Networking Card for peer‑to‑peer  
communication in an FPA‑1000 networked system  
Order number FPE-1000-NW  
Order number FLM-325-I4-A  
FLM-325-I4-AI Contact Monitor 4-inch Class A with Isola-  
tor  
FPE‑1000‑SLC Signaling Line Circuit Plug‑in Module  
Provides a Signaling Line Circuit (SLC) for connection  
of analog devices to the FPA‑1000 Analog Addressable  
Fire Panels  
Can be wired for Class A or Class B circuits; has  
built‑in short circuit isolator circuitry; mounted to a  
cover plate for a 4‑inch square or double gang  
electrical back box; bi‑colored LED provides module  
status; compatible with 254 addresses  
Order number FLM-325-I4-AI  
Order number FPE-1000-SLC  
FPM‑1000‑ENC Enclosure with Dead Front Door  
Enclosure with dead front door  
Order number FPM-1000-ENC  
FLM‑325‑IM Contact Module  
Allows compatible fire alarm control panels (FACP) to  
supervise Form A or B dry contact devices in a polling  
circuit  
FPM-1000-SFMK Semi-flush Mounting Kit  
The FPM-1000-SFMK Semi-flush Mounting Kit includes  
a trim ring and mounting hardware.  
Order number FLM-325-IM  
Order number FPM-1000-SFMK  
 
8 | FPA‑1000 Analog Addressable Fire Panels  
FPP‑RNAC‑8A‑4C Remote Notification Appliance Circuit  
(RNAC) Power Supply  
Adds four additional notification appliance circuits to a  
fire alarm control panel  
Order number FPP-RNAC-8A-4C  
Represented by:  
Americas:  
Europe, Middle East, Africa:  
Bosch Security Systems B.V.  
P.O. Box 80002  
5617 BA Eindhoven, The Netherlands  
Phone: + 31 40 2577 284  
Fax: +31 40 2577 330  
Asia-Pacific:  
Robert Bosch (SEA) Pte Ltd, Security  
Systems  
11 Bishan Street 21  
Singapore 573943  
Phone: +65 6571 2808  
Fax: +65 6571 2699  
China:  
Bosch (Shanghai) Security Systems Ltd. Robert Bosch Ltda Security Systems Division  
America Latina:  
Bosch Security Systems, Inc.  
130 Perinton Parkway  
Fairport, New York, 14450, USA  
Phone: +1 800 289 0096  
Fax: +1 585 223 9180  
201 Building, No. 333 Fuquan Road  
North IBP  
Via Anhanguera, Km 98  
CEP 13065-900  
Changning District, Shanghai  
200335 China  
Campinas, Sao Paulo, Brazil  
Phone: +55 19 2103 2860  
Fax: +55 19 2103 2862  
Phone +86 21 22181111  
Fax: +86 21 22182398  
© Bosch Security Systems 2012 | Data subject to change without notice  
2690096139 | en, V5, 03. Aug 2012  
 

Belkin Computer Accessories F1DC108B SR User Manual
Black Decker Saw 3009 User Manual
Blodgett Convection Oven MT2136 E User Manual
Bogen Air Compressor CMP1R User Manual
Brother All in One Printer 8060P MFC 9060 User Manual
Casio Camcorder EX ZR400 User Manual
Casio Digital Camera EX Z650 User Manual
CDA Cooktop HCG 731 User Manual
Chevrolet Automobile 2009 Colorado User Manual
Chief Manufacturing Indoor Furnishings FTR Series User Manual