PLEASE READ THIS MANUAL
BEFORE INSTALLING
AND USING APPLIANCE.
IMPORTANT: Read all instruc-
tions and warnings carefully
before starting installation. Fail-
ure to follow these instructions
may result in a possible fire
Vent-Free
Gas Room Heaters
hazard and will void the warranty.
WARNING: If the information in
this manual is not followed ex-
actly, a fire or explosion may
result causing property damage,
personal injury or loss of life.
UVHB10
FOR YOUR SAFETY
Installation and service must be
performed by a qualified installer,
service agency, or the gas sup-
plier. Do not store or use gasoline
or other flammable vapors and
liquids in the vicinity of this or
any other appliance.
FOR YOUR SAFETY
If you smell gas:
1. Open windows
2. Do not touch electrical
switches.
3. Do not try to light any appli-
ance.
4. Extinguish any open flame.
5. Do not use the phone in your
building.
6. Immediately call your gas
supplier from a neighbor's
phone.
Homeowner's Installation and
Operating Manual
S
G
N
E
D
7. Follow your gas supplier's
instructions.
8. If you cannot reach your gas
supplier, call the fire depart-
ment.
C
E
D
R
E
I
T
I
F
This is an unvented gas-fired
heater. It uses air (oxygen) from
the room in which it is installed.
Provisions for adequate combus-
tion and ventilation air must be
provided.
INSTALLER: DO NOT DISCARD THIS MANUAL
Leave in fireplace for homeowner.
20004232 10/02 Rev. 1
PYROMASTER® UVHB10 Vent-Free Heaters
UVHB10 Series Gas Appliance - Corner Cabinet
32
³⁄₈
"
³⁄₈
27
30"
26³⁄₄"
"
7¹⁄₈"
45³⁄₄"
10"
36¹⁄₂"
26⁵⁄₈"
26⁷⁄₈"
45⁵⁄₈"
7¹⁄₈"
12¹⁄₂"
4232c
Fig. 1 UVHB10 Series FPS1213N dimensions.
UVHB10 Series Gas Appliance
7"
39⁵⁄₈"
26¹⁄₂"
14⁵⁄₈"
26⁵⁄₈"
47³⁄₈"
15³⁄₈"
4232
Fig. 2 UVHB10 Series, FPS1212NC and FPS1214W specifications and dimensions.
3
20004232
PYROMASTER® UVHB10 Vent-Free Heaters
Description
High Elevations
The UVHB10 vent-free heater is designed to be in-
stalled into an FPS1212NC, FPS1214W or FPS1213N
(corner) mantel cabinet only. It may not be installed in
any other manner.
Input ratings are shown in BTU per hour and are
certified without deration from elevations up to 4,500
feet (1,370m) above sea level.
Nuisance outages may occur at altitudes above 4,500
feet (1,370m) if dirt, dust, lint and/or cobwebs are
allowed to accumulate on burner and/or ODS pilot.
Monthly inspection and cleaning is recommended for
altitudes above 4,500 feet (1,370m)
The UVHB10 is available in Natural or Propane gas,
equipped with an oxygen depletion sensor with a
standing pilot.
Minimum Clearances
For elevations above 4,500 feet (1,370m), installa-
tions must be in accordance with the current ANSI
Z223.1 and/or local codes having jurisdiction.
Minimum clearance to combustibles are maintained
when the UVHB10 is installed into the FPS1212NC,
FPS1214W or FPS1213N mantel cabinets. Top of unit
to ceiling minimum 42 inches.
Gas Specifications
Gas Supply Pressures
Max.
Input
BTU/hr BTU/hr
Min.
Input
This heater must be isolated from the gas supply piping
system by closing its individual manual shut-off valve
during any pressure equal to or less than 1/2 psig (3.45
kPa).
Model
Fuel
Gas Control
UVHB10TN
Natural
Millivolt HI/LO 25,000 17,500
UVHB10TP Propane Millivolt HI/LO 25,000 18,750
The heater and its individual shut-off valve must be
disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in
excess of 1/2 psig (3.45 kPa).
Fig. 3 Gas specifications.
UVHB10
Natural
5.5" w.c.
14.0" w.c.
7.0" w.c.
3.5" w.c.
LP
CERTIFIED TO
Inlet Minimum
11.0" w.c.
14.0" w.c.
11.0" w.c.
10.0" w.c.
ANSI Z21.11.2a-2001
Inlet Maximum
Input Adjustment
Manifold Pressure
Gas-Fired Room Heaters, Volume II Unvented
Table 1 Gas supply pressures.
Planning
Planning the installation is an important first step: it will
save time and money later in the actual installation. In
planning the installation, consider:
The State of California requires the following warning:
WARNING: Combustion by-products
produced contain crbon monoxide, a
chemical known to the State of Califor-
nia to cause cancer and birth defects (or
other reproductive harm).
1. Where the heater will be located.
2. All components needed to complete the
project.
4
20004232
PYROMASTER® UVHB10 Vent-Free Heaters
Installation
Preparing the UVHB10
The UVHB10 may only be used with the approved
mantel and hearth assembly.
Outer Top
1. After determining a location, open the mantel hearth
base carton and place into position on a solid
surface. NOTE: Be sure to level the base before
setting the UVHB10 heater in place.
2. Place the heater on the hearth base centering side
to side and 3/4" from the back edge of the hearth
base (Fig. 1)
FP1225
Fig. 4 Remove outer top.
3. Bend the lower mounting tabs down against the
hearth base and secure with two (2) wood screws
(Fig. 1)
Screws
Fan Bracket
Optional FK24 Fan Hook-Up
NOTE: The FK24 fan should be installed before the
mantel cabinet is complete. Later installation will be
more difficult.
Radiant Shield
Fan
1. Remove the front screen by lifting up on the screen,
Burner Tube
Shield
pulling out on the bottom and pulling down.
2. Remove the three (3) retaining screws that secure
the hood to the unit. (Fig. 3)
Thermo-disc
Hex Nut
Hood
Rheostat
To Receptacle
FP1226
Fig. 5 Attach fan to bracket.
Fan
Speed
Control
Temperature
Sensor
FP1224
Fig. 3 Remove hood.
3. Remove the 13 screws that secure the outer top to
the unit. (Fig. 4)
Wire Extension
FP394A
4. Remove the two (2) screws holding the bracket to
the fan.
Fig. 6 Wiring diagram.
5. Remove the two (2) wires attached to the fan and
assemble the fan to the bracket as shown in Figure 5.
8. Hook the wire extension to the wire leads from the
fan control box. NOTE: These leads were hooked to
the motor earlier.
6. Attach the electrical flag connectors to the fan motor
using the wire extension. (Fig. 6)
9. Mount the thermo-disc to the left log support tab and
secure with one (1) nut.
7. Feed the wire down the 1-inch diameter hole in the
left side of the radiant shield. Push the plastic
bushing in the hole.
5
20004232
PYROMASTER® UVHB10 Vent-Free Heaters
additional local codes, it is always best to consult your
local authority. Consult the current National Fuel Gas
Code, ANSI Z223.1
10. Mount the fan on-off control (Rheostat) to the base
with the studs provided and secure with two (2) nuts.
11. Feed the plug through the 4” x 5” hole on the left
side of the heater and plug into a wall receptacle.
Always check for gas leaks using a 50/50
soap and water solution. Apply water/soap
solution with a brush - do not over apply.
NEVER! test with an open flame.
12. Reassemble unit by following Steps 1- 3 in reverse
order.
Fan Operation
The gas control is equipped with a captured
screw type pressure test point, therefore it is not
necessary to provide a 1/8" test point up stream of the
control.
The FK24 fan has a heat sensor that will not allow the
fan to come on until heater reaches a preset tempera-
ture, approximately 100-120° F. Once the heater
reaches temperature use the speed control knob to turn
fan on and off to adjust fan speed.
1/2" Gas Supply
1/2" NPT x 1/2" Flare Shut-Off
Valve
Installing Brass Trim
3/8" Flex Line
(From Valve)
1. Remove brass trim (3 pieces) from carton. Remove
the protective coating from each piece.
2. Using the (2) screws provided, attach the side
pieces to the heater. (Fig. 7)
3. Mount the top trim to the heater. Be sure to overlap
top trim to the front side of the side trim pieces.
FP297A
Fig. 8 Typical gas supply installation.
Brass Trim (Top)
Final Assembly
Final assembly is accomplished by lifting the mantel
cabinet overtop of the heater behind the brass trim
pieces.
NOTE: The mantel is designed to fit flush to the wall as
a freestanding unit. If desired, it may be secured to the
wall with nails or screws (not provided).
When installed, the heater must be electri-
cally connected and grounded in accor-
dance with local codes or, in the absence of
local codes:
U.S. INSTALLATIONS: FOLLOW LOCAL CODES
AND THE NATIONAL ELECTRICAL CODE, ANSI/
NFPA NO. 70.
Brass Trim
(Sides)
FP1115
UVHB10 Logset
Fig. 7 Install brass trim.
The UVHB10 is
shipped with the
one piece log in
Run Gas Line from Its
Source to the Heater
position. However,
If gas piping from the source to the heater location has
not been accomplished, install the required pipe.
Consult local plumbing code to assure proper pipe size.
Logset
if the log needs to
be removed, let
the log cool, it
may be hot, lift it
straight up . (Fig. 9)
The gas pipeline can be brought in through the right
side of the heater.
NOTE: The gas line connection can be made with
properly tinned 3/8" copper tubing, 1/2" rigid pipe or an
approved flex connector, then reduced to 3/8" to the
heater. Because some municipalities have some
FP1213
Fig. 9 Remove logset by lifting up. Be
sure logset is cool before handling.
6
20004232
PYROMASTER® UVHB10 Vent-Free Heaters
Operation
First Firing
Upon completing the gas line connection, a small
amount of air will be trapped in the line. When first
lighting the unit with pilot light, it will take a few minutes
to purge the trapped air. Once purging is complete, the
pilot and burner will light and operate as indicated in the
instruction manual. Subsequent lightings of the appli-
ance will not require purging.
Yellow Tip
Blue
LG150
Fig. 12 Correct log flame appearance.
When lit for the first time, the appliance will emit a slight
odor for an hour or two. This is due to paint and lubri-
cants used in the manufacturing process. After each
lighting, vapor may condense and fog the glass; this
moisture disappears within a few minutes of burning.
When Used as a Heating Appliance
This appliance is equipped with a modulating valve
which controls the main burner by a thermostat. As the
room temperature increases, the flame will automati-
cally lower itself according to the control knob setting.
Flame Adjustment
The thermostatic bulb is located under the log set. If the
main burner flame modulates down to a lower level
while the control knob is at a higher setting, the bulb
may need to be located outside the fireplace.
Flame adjustment is accomplished by rotating the Hi/Lo
adjustment knob located near the center of the gas
control. (Fig. 10)
It is important to periodically perform a
visual check of the pilot and the burner
flames. (Figures 11 and 12)
The SIT 'T' series valve operates from the full clockwise
'LOW' position to the full counterclockwise
'HIGH' position. (Refer to Page 3 for BTU rates.)
Piezo Ignitor
When used as an unvented heater, maximum benefit
will result when the fireplace flue damper is fully closed.
NOTE: For your safety, the appliance is equipped with
an oxygen depletion sensor. This device senses the
level of oxygen in the atmosphere and switches off the
gas supply in case the level of oxygen falls below a
safe level.
LO
The appliance may be used as a heating appliance only
if unvented heating appliances are permitted by local,
state, and city codes. In locations that do not allow
unvented heaters, the chimney must have a permanent
chimney opening of not less than 29 square inches.
FP1036
Fig. 10 Flame adjustment on gas valve.
Thermocouple
P103
Fig. 11 Proper pilot flame appearance.
7
20004232
PYROMASTER® UVHB10 Vent-Free Heaters
Lighting And Operating Instructions
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING:If you do not follow these instructions exactly, a fire or explosion
may result causing property damage, personal injury or loss of life.
A. This heater has a pilot which must be lit manu-
ally. When lighting the pilot follow these instruc-
tions exactly.
instructions.
• If you cannot reach your gas supplier, call
the Fire Department
B. BEFORE LIGHTING smell all around the heater
area for gas. Be sure to smell next to the floor
because some gas is heavier than air and will
settle on the floor.
C. Use only your hand to push in or turn the gas
control knob. Never use tools. If the knob will not
push in or turn by hand, do not try to repair it, call a
qualified service technician. Applying force or any
attempted repair may result in a fire or explosion.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any fireplace
• Do not touch any electric switch
• Do not use any phone in your building
D. Do not use this fireplace if any part has been under
water. Immediately call a qualified service techni-
cian to inspect the heater and to replace any part of
the control system and any gas control which has
been under water.
• Immediately call your gas supplier from a
neighbor's phone. Follow the gas supplier's
Lighting Instructions
1. STOP! Read the safety information above.
2. Turn off all electrical power to the fireplace.
3. For MN/MP/TN/TP appliances ONLY, go on to
Step 4. For RN/RP appliances turn the On/Off
switch to “OFF” position or set thermostat to
lowest level.
10. Push the control knob all the way in and hold.
Immediately light the pilot by repeatedly depress-
ing the piezo spark ignitor until a flame appears.
Continue to hold the control knob in for about one
(1) minute after the pilot is lit. Release knob and it
will pop back up. Pilot should remain lit. If it goes
out, repeat steps 5 through 8.
4. Open control access panel.
5. Push in gas control knob slightly and turn
clockwise
to "OFF".
3/8" - 1/2"
OFF
PILOT
Honeywell
Euro SIT
SIT NOVA
•
If knob does not pop up when released, stop
and immediately call your service technician or
gas supplier.
6. Wait five (5) minutes to clear out any gas. Then
smell for gas, including near the floor. If you
smell gas, STOP! Follow "B" in the safety
information above. If you do not smell gas, go
to the next step.
7. Remove glass door before lighting pilot. (See
Glass Frame Removal section).
8. Visibly locate pilot by the main burner.
9. Turn knob on gas control counterclockwise
to "PILOT".
•
If after several tries, the pilot will not stay lit,
turn the gas control knob to "OFF" and call your
service technician or gas supplier.
11. Replace glass door.
12. Turn gas control knob to “ON” position.
13. For RN/RP appliances turn the On/Off switch to
“ON” position or set thermostat to desired setting.
14. Turn on all electrical power to the fireplace.
To Turn Off Gas To Heater
1. Turn the On/Off switch to Off position or set the
thermostat to lowest setting.
3. Open control access panel.
4. Push in gas control knob slightly and turn
2. Turn off all electric power to the fireplace if
service is to be performed.
clockwise
5. Close control access panel.
to "OFF". Do not force.
8
20004232
PYROMASTER® UVHB10 Vent-Free Heaters
Maintenance
Keep the control compartment, logs and burner area
surrounding the logs clean by vacuuming or brushing at
least twice a year. THE LOGS CAN GET VERY HOT
— HANDLE ONLY WHEN COOL.
Most of these components may require only an occa-
sional checkup and cleaning and some may require
adjustment. If repair is necessary, it should be per-
formed by a qualified technician.
Always turn off gas to the pilot before cleaning. For
relighting, refer to lighting instructions located on the
front cover plate.
In order to properly clean the burner and pilot assembly,
turn off the gas to the unit, remove the logs exposing
the burner and pilot assembly. Clean all foreign materi-
als from the top of the burner. Check to make sure that
burner parts are clean. Visually inspect pilot. Brush or
blow away any dust or lint accumulation If pilot orifice is
plugged, disassembly may be required to remove any
foreign material from the orifice or tubing.
Never obstruct the flow of combustion and ventilation
air. Keep the front of the heater clear of all obstacles
and materials.
Leave at least 36" clearance from front of heater to
combustibles.
To obtain proper operation, it is imperative that the pilot
and burner's flame characteristics are steady, not lifting
or floating.
Cleaning the Standing Pilot
Control System
Typically, the top 1/8" of the thermopile should be
engulfed in the pilot flame. (Fig. 10, Page 7)
The burner and control system consists of:
• main burner
• gas orifice
• pilot burner
• thermopile
The air shutter is set at the factory, no adjustment
should be necessary.
• combination millivolt gas valve
9
20004232
PYROMASTER® UVHB10 Vent-Free Heaters
Troubleshooting
With proper installation and maintenance, your new Gas Appliance should provide years of trouble-free service. If
you do experience a problem, this guide will help a CERTIFIED SERVICE PERSON in the diagnosis of problems
and the corrective action to take.
SYMPTOM
POSSIBLE CAUSES
CORRECTIVE ACTION
1. Pilot will not light with
piezo ignitor or match.
A. Main shutoff valve closed
1. Make sure that the shutoff valve located on the pipe
supplying gas to the fireplace is open.
B. Air in the gas line.
1. Light a match, turn gas valve knob to "PILOT"
position and depress. Keep match near pilot burner till
it lights.
C. Pilot orifice plugged, not
letting gas flow.
1. Replace the burner assembly.
D. No gas supply to the
fireplace.
1. Check plumbing to see if gas fireplace has been
hooked up to the gas supply line.
2. Propane tank is empty.
2. Pilot will not stay lit
after carefully following
the lighting instructions.
A. Defective thermocouple
1. Replace burner assembly.
1. Carefully tighten the fitting.
B. Thermocouple fitting not
tight in valve
C. Weak pilot flame.
1. The pilot flame must engulf the thermocouple.
Clean for maximum flame impingement on the
thermocouple.(Fig. 12)
D. Defective valve.
1. Replace the burner assembly.
E. Not enough oxygen in
1. Open the door and get fresh air at once!
the room (Danger!)
3. No gas to main burner
burner with pilot flame
burning and valve turned
to "High-Low" range.
A. Thermostat bulb too hot
1. Relocate thermostat bulb away from the heater in a
location more representative of room temperature.
B. Plugged main burner
orifice.
1. Replace burner assembly.
1. Replace burner assembly.
C. Defective valve.
10
20004232
PYROMASTER® UVHB10 Vent-Free Heaters
5
2
7a/b
1
4
3
3
8a/b
12
5
6
9
14
10a/b
15
13
16
17
11a/b
18
19
4232
CFM Harris Systems reserves the right to make changes in design, materials, specifications, prices and discontinue colors and products at any
time, without notice.
Replacement Parts List - UVHB10
Ref.
1.
Description
UVHB10
20004230
3187132
3187130
20003821
20003939
20004032
20004075
20004088
20001356
20001357
20000101
20005382
20000610
20004644
20004645
51851
Log
2.
Top Trim
3.
Right Side Trim
4.
Screen
5.
Top & Bottom Louvre
Pins
6.
7a.
7b.
8a.
8b.
9.
Burner Tube - Natural
Burner Tube - LP
NG Pilot - "OXYPROTECTORNG"
LP Pilot - "OXYPROTECTORLP"
Piezo Ignitor Cable 24"
Orifice - Natural
10a.
10b.
11a.
11b.
12.
13.
14.
15.
16.
17.
18.
19.
Orifice - LP
Valve - Eurosit 630 - Natural
Valve - Eurosit 630 - LP
Valve Cover (Includes Piezo & Screw)
Piezo Ignitor
52464
Hood
20003869
FK24
Fan
Electrical Cord (6ft.)
Fan Temperature Sesonr
Speed Control
51856
51740
51738
Speed Control Knob
51882
11
20004232
PYROMASTER ® UVHB10 Vent-Free Heaters
Accessories
The following accessories for these heaters are available from your local Pyromaster distributor. Each accessory
comes with a separate installation instruction for mounting to the particular heater. Be sure to read each
instruction thoroughly before installing.
Accessory
Description
Provides air flow
Used to connect fan
Part No.
FK24
Fan
Electrical Cord (6 ft.)
Fan Temperature Sensor
Speed Control
51865
51740
51738
51882
Allows speed adjustment for fan
Speed Control Knob
CAUTION: This heater is a highly engineered system, and, as such, must be operated only
with PYROMASTER approved components. If you use an unapproved component to make
any modifications, you may create a possible fire hazard and will void the PYROMASTER
warranty. In addition, such action may void the coverage provided by the owner’s insur-
ance.
Contact CFM Harris Systems for questions concerning
prices and policies covering replacement parts. Parts
may be ordered through your CFM Harris Systems
distributor or dealer.
Model and serial numbers are listed on the
rating plate (located on the instruction plate
behind the bottom louvre).
You will need the following information when ordering
replacement parts:
Record your model and serial numbers here for
future reference:
1. The heater model number.
2. The serial number.
3.A description of the part.
Model #
Serial #
____________________________
____________________________
Should you need additional information beyond what
your dealer can furnish, contact:
CFM Corporation
2695 Meadowvale Boulevard
Mississauga, Ontario L5N 8A3 Canada
(800) 668-5323
www.cfmcorp.com
12
20004232
LIMITED 2/20 YEAR WARRANTY
For CFM Harris Systems Decorative Gas Appliances
The CFM Harris Systems extends the warranties specified
CLUDING IMPLIED WARRANTIES OF MERCHANTABIL-
ITY OR FITNESS FOR A PARTICULAR PURPOSE), ALL
OF WHICH ARE HEREBY EXPRESSLY INCLUDED. IN
NO EVENT SHALL ANY IMPLIED WARRANTY PRE-
SCRIBED BY LAW (NOTWITHSTANDING THE FOREGO-
ING EXPRESS EXCLUSION) REMAIN IN EFFECT
AFTER EXPIRATIONS OF THE WARRANTIES SET
FORTH IN PARAGRAPHS A AND B.
A. Gas Appliances, electrical and manual compo-
nents, glass panels, all sealants or adhesives and
optional accessories (exclusive of CFM Harris Systems
supplies decorative logs which are covered by a separate
warranty under paragraph B below):
in paragraphs A and B below with respect to its Decorative
Gas Appliances (the “Gas Appliance”), including the CFM
Harris Systems supplied accessories and components
referred to in those paragraphs, subject to the following
conditions and limitations:
(1) These warranties are extended only to the Gas
Appliance installed in the continental United States,
including Alaska, and Canada; only if and so long as the
accordance with the installation and operating instructions
furnished therewith; and only if and so long as Gas
Appliance is not removed from its original installation.
(2). These warranties are limited to only the component
parts manufactured and supplied by CFM Harris Systems
The use of components manufactured by others with the
Gas Appliance (except for a listed Type B venting system
as defined in the installation instructions) could create
serious safety hazard, may result in the denial of certifica-
tion by recognized national safety agencies, and could be
in violation of local building codes.
(3). The Gas Appliance must be operated at all times in
accordance with the operating instruction furnished
therewith. The Gas Appliance is designed to burn either
natural or propane gas only. Burning conventional
fireplace fuels such as wood, coal, or any other solid fuel
will cause damage to the Gas Appliance, will produce
excessive temperatures and will result in a fire hazard.
(4). These warranties are limited to repair, replacement
or furnishing a replacement for sale, as specified in
Paragraphs A and B, for a part found to CFM Harris
Systems’ satisfaction, after examination, to be defective in
materials or workmanship under normal conditions, use
and service.
Within two years from the date of manufacture of the gas
appliance, CFM Harris Systems will repair, or replace (at
our option) a defective part without charge.
B. Cement or ceramic fiber log components:
Within two years from the date of manufacture of the gas
appliance, CFM Harris Systems will replace a defective
part without charge. Within years three through twenty
from the date of manufacture of the gas appliance, CFM
Harris Systems will provide a replacement for a defective
part to the homeowner, but assumes no liability for
incurred labor cost.
The foregoing warranties gives you specific legal rights
and you may also have other rights which vary from state
to state. Some states do not allow limitations on how long
an implied warranty may last, so the limitation specified
above on the duration of any implied warranty prescribed
by law may not apply to you. Similarly, some states do not
permit the exclusion or limitation of incidental or conse-
quential damages, so the above exclusion of such dam-
ages may not apply to you.
(5). All obligations with respect to these warranties may
be fully discharged by CFM Harris Systems refunding the
wholesale price of a defective part.
(6). Except as otherwise expressly specified in Para-
graphs A and B. NONE OF THESE WARRANTIES
COVER, AND CFM HARRIS SYSTEMS SHALL NOT BE
RESPONSIBLE FOR, ANY CONSTRUCTION, INSTALLA-
TION, LABOR, TRANSPORTATION OR OTHER COSTS
OR EXPENSES ARISING FROM A DEFECTIVE PART,
ITS REPAIR OR REPLACEMENT OR OTHERWISE, NOR
SHALL CFM HARRIS SYSTEMS, INC. IN ANY EVENT BE
RESPONSIBLE FOR ANY INDIRECT, INCIDENTAL OR
CONSEQUENTIAL DAMAGES. EXCEPT TO THE
EXTENT PROVIDED BY LAW, THERE ARE NO IMPLIED
WARRANTIES WITH RESPECT TO THE GAS APPLI-
ANCE, ITS COMPONENTS AND ACCESSORIES (IN-
Since local building requirements may vary greatly through-
out the country, users of CFM Harris Systems products
should determine in advance whether there are any building
code restrictions on the use of a specified product.
CFM HARRIS SYSTEMS MAKES NO REPRESENTA-
TION OR WARRANTY REGARDING, AND SHALL NOT
BE RESPONSIBLE FOR, ANY BUILDING CODE COM-
PLIANCE.
13
20004232
|