Chromalox
SERVICE REFERENCE
Installation, Operation
DIVISION
SALES
4
SECTION CAB
and
(Supersedes PF412-6)
161-048224-001
PF412-7
REFERENCE
RENEWAL PARTS INDENTIFICATION
Type CAB and CABB
Forced Air Duct Heaters
Sensitive Bulb of
Thermostat
2 Holes 5/16-18 Tapped,
Each Side For Mounting
4-1/4”
A
3/4”
B
C
21/32
1-9/16”
2-1/4”
2-1/4”
3-5/8”
Type CAB
Special Cover for Side
or Bottom Terminals
Type CABB
Specifications –
Model
Dimensions (In.)
Weight
(Lbs.)
No.
No.
Volts
Phase kW
1 or 3
(Note 1)
(Note 2)
Finstrips Ckts.
A
B
C
CAB-62
CAB-611
120, 208,
240 or 480
25
6
6
9
1
1
1
1
1
10-3/4 15-7/8 11-1/2
CABB-62
CAB-122
CABB-122
CAB-152
CABB-152
CAB-202
CABB-202
CAB-252
CABB-252
——
CAB-402
CABB-402
CAB-502
CABB-502
CAB-752
CABB-752
CAB-1002
CABB-611
CAB-1211
CABB-1211
CAB-1511
CABB-1511
CAB-2011
CABB-2011
CAB-2511
CABB-2511
CABB-3011
CAB-4011
CABB-4011
CAB-5011
CABB-5011
CAB-7511
CABB-7511
CAB-10021
35
208, 240 or 480
1 or 3 12
1 or 3 15
15-3/8 18-1/2 14-1/8
15-3/8 21-5/8 17-1/4
20-1/8 21-5/8 17-1/4
40
208, 240 or 480
9
208 or 240
480
208 or 240
480
480
208 or 240
480
208 or 240
480
208 or 240
480
208 or 240
480
3
55
20
12
12
1 or 3
3
65
25
20-1/8 26-1/8 21-3/4
29-1/2 21-5/8 17-1/4
1 or 3
75
90
3
3
30
40
18
18
2
2
29-1/2 27-3/8
23
1 or 3
3
1 or 3
3
1 or 3
3
1 or 3
110
200
220
50
75
18
27
27
2
3
3
29-1/2 33-1/8 28-3/4
44-7/16 42-1/8 37-3/4
44-7/16 47-1/2 43-1/8
100
CABB-1002 CABB-10021
1. Iron sheath strip heaters — for sheath temperatures to 750˚F.
2. Chrome steel sheath strip heaters — for sheath temperatures to 950˚F.
© 2010 Chromalox, Inc.
WIRING
wiring runs in heated zones. When ambient temperature in
heated zone exceeds that for which insulated wire is recom-
mended use bare nickel-plated copper with porcelain beads,
tubing or buss bar. Consult local Chromalox representative.
4. Users should install adequate back-up controls and safety
devices with their electric heating equipment. Selection of
controls, thermostat, SCR units, contactors and etc. depends
on the degree of accuracy required, reliability, electrical rating
of heater and economic considerations.
WARNING: Hazard of Electric Shock. Any installation
involving electric heaters must be effectively ground-
ed in accordance with the National Electrical Code to
eliminate shock hazard.
1. All wiring should be done in accordance with the National
Electrical Code and with local codes by a qualified person.
2. Connect air heaters to same line voltage, phase and frequency
as on heater nameplate.
3. Teflon insulated nickel plated copper wire or buss bar is rec-
5. Below is an example of standard CAB 122 480V 3P 12 kW
ommended for power connections to heater terminals and for
wired with recommended back-up controls (Figure 3).
Figure 3 - Wiring Diagram
Heater
Fan
Thermal Cutout
Motor
120/240
Control
Circuit
Contactor
Fused Switch
480V
Power
Supply
OPERATION
1. Do not operate heaters at voltages in excess of that stamped
WARNING: Users should install adequate back-up
controls and safety devices with their electric
heating equipment. Where the consequences of
failure may be severe, back-up controls are essen-
tial. Although the safety of the installation is the
responsibility of the user, Chromalox will be glad
to assist in making equipment recommendations.
on the heater since excess voltage will shorten heater life.
MAINTENANCE
2. Check for loose terminal connections.
WARNING: Hazard of Severe Shock. Disconnect all
power to heater before servicing or replacing heaters.
1. Periodically clean terminals and terminal covers of dust and
corrosion to maintain good electrical connections and to per-
mit rapid heat dissipation. Use airblast, and be careful to avoid
damage to mica insulation.
RENEWAL PARTS IDENTIFICATION
Heating Element
208 Volt 240 Volt
Model
CAB-62
CABB-62
CAB-611
CABB-611
CAB-122
kW
120 Volt
480 Volt
117-013851-001 (6) 117-013851-002 (6) 117-013851-003 (6) 117-013851-004 (6)
117-013852-001 (6) 117-013852-002 (6) 117-013852-003 (6) 117-013852-004 (6)
6
——
——
——
——
——
——
——
——
117-013851-006 (9) 117-013851-007 (9) 117-013851-008 (9)
117-013852-006 (9) 117-013852-007 (9) 117-013852-008 (9)
117-013851-010 (9) 117-013851-011 (9) 117-013851-012 (9)
117-013852-010 (9) 117-013852-011 (9) 117-013852-012 (9)
117-013851-010 (12) 117-013851-011 (12) 117-013851-012 (12)
117-013852-010 (12) 117-013852-011 (12) 117-013852-012 (12)
117-013851-014 (12) 117-013851-015 (12) 117-013851-016 (12)
117-013852-014 (12) 117-013852-015 (12) 117-013852-016 (12)
CABB-122
CAB-1211
CABB-1211
CAB-152
CABB-152
CAB-1511
CABB-1511
CAB-202
CABB-202
CAB-2011
CABB-2011
CAB-252
CABB-252
CAB-2511
CABB-2511
CABB-3011
CAB-402
CABB-402
CAB-4011
CABB-4011
CAB-502
CABB-502
CAB-5011
CABB-5011
CAB-752
CABB-752
CAB-7511
CABB-7511
CAB-1002
CABB-1002
CAB-10021
CABB-10021
12
15
20
25
30
40
——
——
——
——
117-013852-012 (18)
117-013851-018 (18) 117-013851-019 (18) 117-013851-020 (18)
117-013852-018 (18) 117-013852-019 (18) 117-013852-020 (18)
117-013851-022 (18) 117-013851-023 (18) 117-013851-024 (18)
117-013852-022 (18) 117-013852-023 (18) 117-013852-024 (18)
117-013851-026 (27) 117-013851-027 (27) 117-013851-028 (27)
117-013852-026 (27) 117-013852-027 (27) 117-013852-028 (27)
117-013851-030 (27) 117-013851-031 (27) 117-013851-032 (27)
117-013852-030 (27) 117-013852-031 (27) 117-013852-032 (27)
——
——
——
——
——
——
——
50
75
100
Number in parenthesis indicates total quantity in unit.
Terminal Cover — 306-021921-001
Bulb Mounting Strap — 283-033234-001
Limited Warranty:
Please refer to the Chromalox limited warranty applicable to this product at
2150 N. RULON WHITE BLVD., OGDEN, UT 84404
Phone: 1-800-368-2493
|