INSTALLATION INSTRUCTIONS AND RENEWAL PARTS IDENTIFICATION  
Power Disconnect Switch Kits  
Specifications – Table A  
Electrical Data (60Hz)  
Standard  
Contactor  
Rating (Qty.)  
Model  
Volts  
kW  
Phase Amps  
KUH-C-02-81  
KUH-C-02-21  
KUH-C-02-71  
KUH-C-04-81  
KUH-C-04-83  
KUH-C-04-21  
KUH-C-04-23  
KUH-C-04-71  
KUH-C-04-43  
KUH-C-05-81  
KUH-C-05-83  
KUH-C-05-21  
KUH-C-05-23  
KUH-C-05-71  
KUH-C-05-43  
KUH-C-07-81  
KUH-C-07-83  
KUH-C-07-21  
KUH-C-07-23  
KUH-C-07-71  
KUH-C-07-43  
KUH-C-10-81  
KUH-C-10-83  
KUH-C-10-21  
KUH-C-10-23  
KUH-C-10-43  
KUH-C-12-83  
KUH-C-12-23  
KUH-C-12-43  
KUH-C-15-83  
KUH-C-15-23  
KUH-C-15-43  
KUH-C-20-23  
KUH-C-20-43  
KUH-C-25-43  
KUH-C-30-83  
KUH-C-30-23  
KUH-C-30-43  
KUH-C-35-23  
KUH-C-35-43  
KUH-C-40-23  
KUH-C-40-43  
KUH-C-45-43  
208  
208/240  
277  
2.667  
2/2.667  
2.667  
1
1
1
1
3
1
3
1
3
1
3
1
3
1
3
1
3
1
3
1
3
1
3
1
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
12.8  
11.1*  
9.6  
19.2  
11.2  
16.7*  
9.6*  
14.5  
4.8  
24.0  
13.8  
20.8*  
12.1*  
18.2  
6.0  
36.1  
20.9  
31.1*  
18.1*  
27.2  
9.0  
48.0  
27.8  
41.7*  
24.0*  
12.0  
34.8  
30.1*  
15.1  
41.8  
36.2*  
18.1  
48.0*  
24.0  
30.0  
83.4  
72.2*  
36.1  
84.3*  
42.1  
96.0*  
48.0  
54.1  
208  
4
30A (1)  
30A (1)  
30A (1)  
30A (1)  
30A (1)  
208/240  
3/4  
277  
480  
4
4
208  
5
208/240  
3.75/5  
277  
480  
5
5
30A (1)  
50A (1)  
30A (1)  
30A (1)  
30A (1)  
30A (1)  
30A (1)  
50A (1)  
30A (1)  
30A (1)  
30A (1)  
30A (1)  
50A (1)  
50A (1)  
30A (1)  
50A (1)  
50A (1)  
30A (1)  
50A (1)  
30A (1)  
50A (1)  
50A (2)  
50A (2)  
30A (2)  
50A (2)  
30A (2)  
50A (2)  
30A (2)  
30A (2)  
3 Pole  
208  
7.5  
Model  
Rating  
PCN  
208/240  
5.625/7.5  
KDS-1 50 Amp for units rated 480V and less 304434  
40 Amp for units rated 500V to 600V  
277  
480  
7.5  
7.5  
208  
10  
208/240  
7.5/10  
480  
208  
208/240  
480  
208  
208/240  
480  
208/240  
480  
480  
208  
208/240  
480  
208/240  
480  
208/240  
480  
480  
10  
12.5  
9.375/12.5  
12.5  
15  
11.25/15  
15  
15/20  
20  
25  
30  
22.5/30  
30  
26.25/35  
35  
30/40  
40  
45  
Power Disconnect Switch  
for Field Installation  
3 Pole 600 V Rating  
Model  
KDS-2  
KDS-3  
Rating  
80 Amp  
100 Amp  
PCN  
304442  
304450  
*208V amperage is 86% of 240V value.  
GENERAL  
The following procedure contains instructions for installing  
Power Disconnect Switches.  
ELECTRIC SHOCK HAZARD. Disconnect all power  
before installing disconnect switch. Failure to do  
so could result in personal injury or property dam-  
age. Disconnect switch must be installed by a  
qualified person in accordance with the National  
Electrical Code, NFPA 70.  
© 2010 Chromalox®, Inc.  
 
INSTALLATION (Cont’d)  
KDS–2 and KDS – 3  
Rear Case  
8. The cover plate should be placed over the rectangular opening  
with its four mounting holes lined up with the four holes in the  
cabinet and the four holes in the mounting bracket (see Figure 7).  
9. Insert the four self tapping screws into the four holes until they  
engage the holes in the mounting bracket and tighten until they  
are secure (see Figure 8).  
10. Place plastic bezel over the installed switch and push towards the  
switch until the tabs snap into place (see Figure 9).  
Switch Assembly Mounted to Rear Case  
Figure 8  
Snap Plastic Housing  
Into Place  
(4) 8-32 Screws  
Cover Plate  
Rear Case  
Rear Case  
Mount Switch Assembly  
Onto Rear Case of Heater  
Figure 9  
Figure 7  
WIRING  
POWER DISCONNECT SWITCH (Available as a kit or  
factory installed option.) (KDS-1)This switch disconnects the  
power to power leads when the handle is rotated to the “0” posi-  
tion (left). The power is on when the switch handle is rotated to  
the “1” position (top) position. (KDS-2 and KDS-3) This switch  
disconnects power to the power leads when the handle is placed  
in its full lower position. The power is on when the switch handle  
is in its full upper position.  
ELECTRIC SHOCK HAZARD. Disconnect all power  
before installing disconnect switch. Failure to do  
so could result in personal injury or property dam-  
age. Disconnect switch must be installed by a  
qualified person and must be effectively grounded  
in accordance with the National Electrical Code,  
NFPA 70.  
1. Use the three pigtail leads supplied with kit (40 & 80 Amp) when  
connecting to the power line.  
For future replacement parts, the model number should be modi-  
fied on the nameplate to show that a disconnect kit has been field  
installed on the heater. A label kit (see Figure 14) (P/N 170-  
302788-002) has been included in the plastic envelope located in  
the disconnect kit. Cut off the appropriate number for the size dis-  
connect being installed (40 Amp = 1; 80 Amp = 2; 100 Amp = 3).  
The label has a pressure sensitive adhesive back so that the num-  
ber can be placed over the “0” as shown in Figure 14.  
a. Use No. 4GA Copper conductor wire only for 100 Amp dis-  
connect when wiring to the power line.  
2. The power disconnect wiring to the heater is to be made using the  
pigtail leads supplied on the heaters up to and including 25 kW.  
On larger heaters, the installer should supply 105˚C type AWM  
600V wire.  
Pigtail  
Power  
Power  
Leads  
Disconnect  
Switch  
Disconnect  
Contactor  
Switch  
Contactor (1)  
L1  
L2  
L3  
AL1  
AL2  
AL3  
L1  
L2  
L3  
AL1  
AL2  
AL3  
To  
To  
Power  
Supply  
Power  
Supply  
See Notes  
See  
Note 2  
Notes:  
1. This illustration shows wiring hook up for three phase  
service. Remove lead wires marked L2 and AL2 when  
using one phase power service.  
Contactor (2)  
2. For units without contactors, disconnect switch is to  
be wired to lead wires on heater power.  
KUH-30 through KUH-45 units with 2 contactors  
where the total load does not exceed 48 Amps.  
3. Use copper supply wire only with this switch.  
Figure 10  
KUH-02 through KUH-25  
Power Disconnect Switch  
Figure 11  
 
3
WIRING (Cont’d)  
Fuse Block (1)  
Contactor (1)  
Power  
Disconnect  
Switch  
L1  
L2  
L3  
AL1  
To  
Power  
Supply  
AL2  
AL3  
Fuse Block (2)  
Contactor (2)  
KUH-30 through KUH-45 units with 2 contactors  
where the total load exceeds 48 Amp and sub-  
circuit fuse blocks are provided.  
Figure 12  
®
Place Number at  
the end of the  
Catalog Number  
-42 -43 -44 -45 -1 -2 -3  
CATALOG NO.  
KUH-C- 07 - 43 - 32 - 00 - 0  
004 - 303375 - 265  
DATE  
CODE  
MFG. PART NO.  
MIN. CIRC. CAP.  
RATING  
AMPS MAX. CIRC. FUSE  
AMPS  
KW  
7.5  
V.A.C. ONLY  
480V  
PH  
3
AMPS  
9.0  
HZ  
60  
60  
60  
Number 1, 2 or 3 designates the Disconnect Code for Kit.  
1 = 40 Amp; 2 = 80 Amp; 3 = 100 Amp  
HEATER  
MOTOR  
CONT. CKT.  
SERIAL NO
480V  
120V  
1
1
.28  
10  
V.A.  
MAX.  
P/N 196-057744-002  
Figure 14 — Nameplate  
Figure 13 — Pressure Sensitive Label  
REPLACEMENT PARTS LIST  
Disconnect  
Size  
Kit Model #  
Disconnect  
Cover Plate  
Mounting Bracket  
50 Amp  
80 Amp  
100 Amp  
KDS-1  
KDS-2  
KDS-3  
292-303472-001  
292-303472-002  
292-303472-008  
220-303485-010  
220-303485-003  
220-303485-003  
220-303484-003  
220-303484-003  
Limited Warranty:  
Please refer to the Chromalox limited warranty applicable to this product at  
 

Black Box Computer Hardware ACS20001A R3 User Manual
Black Decker Electric Shaver RB 3612 User Manual
Brother All in One Printer 8060P MFC 9060 User Manual
Cabletron Systems Switch 9032848 02 User Manual
Canon Camera Lens KH21EX57 User Manual
Canon Projector LV 7260 User Manual
Carrier Air Compressor 06D User Manual
CFM Fan ADD 0911 User Manual
Chief Manufacturing Indoor Furnishings LCD2TS User Manual
Chrysler Automobile 2005 PT Cruiser Convertible User Manual