Delta Electronics Power Supply PMC 24V050W1AA User Manual

Instruction Manual  
PMC-24V050W1AA  
1. Safety Instructions  
3. Installation of the Device  
Refer to Fig. 2:  
To ensure sufficient convection cooling, always maintain a safety  
distance of >20mm from all ventilated surfaces while the device is in  
operation.  
The device is not recommended to be placed on low thermal  
conductive surface, for example, plastics.  
A
Mounting holes for power supply assembly onto the mounting surface. Power  
supply shall be mounted on minimum 2 mounting holes using M3 screw,  
minimum 5mm length.  
B
C
This surface belongs to customer’s end system or panel where the power  
supply is mounted.  
Note that the enclosure of the device can become very hot  
depending on the ambient temperature and load of the power supply.  
Do not touch the device while it is in operation or immediately after  
power is turned OFF. Risk of burning!  
Connector  
Do not touch the terminals while power is being supplied. Risk of  
electric shock.  
Base Mounting (Vertical) Side Mounting (Horizontal)  
Side Mounting (Vertical)  
Prevent any foreign metal, particles or conductors to enter the  
device through the openings during installation. It can cause:  
- Electric shock; Safety Hazard; Fire; Product failure  
Warning: When connecting the device, secure Earth connection  
before connecting L and N. When disconnecting the device, remove  
L and N connections before removing the Earth connection.  
2. Device Descriptions  
Refer to Fig. 1:  
Fig. 2 Mounting  
1
2
3
Input & Output terminal block connector  
Use flexible cable (stranded or solid), AWG no. 22-12. The torque at the  
Connector shall not exceed 13Kgf.cm The insulation stripping length should  
not exceed 0.275” or 7mm  
DC voltage adjustment potentiometer  
DC OK control LED (green)  
Side surface  
Ventilated surface  
Fig. 3 Wire Type  
Lug  
Stripped wire  
Top  
4. Installation of Mounting Accessories  
Only use M3 screw < 6mm through the base mounting holes. This is to keep  
a safety distance between the screw and internal components.  
Refer to Fig. 4:  
Recommended mounting tightening torque: 4 ~ 8Kgf.cm  
3
2
Base surface  
1
Fig. 1 Device Descriptions  
Fig. 4 Mounting Screw  
 

Cooper Lighting Work Light ADH061623 User Manual
Dell All in One Printer 3333dn User Manual
Dynacord Stereo Receiver DDL 204 User Manual
Eagle Electronics GPS Receiver Eagle View User Manual
Earthquake Sound Stereo Amplifier XJ 300R User Manual
GE Air Conditioner AVX08 User Manual
GE Air Conditioner Cool Only User Manual
Generac Power Systems Portable Generator 05176 0 User Manual
GE Oven JKP35BM User Manual
Gitzo Camcorder Accessories G1177M User Manual