Eaton Electrical Power Supply 164201420B User Manual

®
Powerware 9170+ Rail Kit  
9- and 12-Slot Cabinets  
Installation Guide  
 
Rack-Mount Installation  
To install a 9- or 12-slot uninterruptible power system (UPS) cabinet into  
a rack, you must order a cabinet specifically designed for rack-mounting.  
Nine- and 12-slot battery cabinets ASY-0749 and ASY-0750 are also  
available for rack-mounting. These models can be installed in an  
EIA-standard 48.3 cm (19) equipment rack and include a rack-mounting  
kit with the brackets and required hardware.  
To install the UPS or battery cabinet in the equipment rack:  
NOTE The 9- and 12-slot cabinets are heavy [9-slot: 72 kg (158 lb); 12-slot: 89 kg (196 lb)].  
This procedure requires two people to lift and position the cabinet into the equipment rack.  
Install the cabinet in the rack before installing power and battery modules and before making  
connections to the intended power source.  
1. Remove the four screws (two on either side) securing the top cover  
of the cabinet. Carefully lift the cover straight up and off to avoid  
stressing the front panel display. Set the cover aside.  
2. Remove the cabinet side covers by lifting the top edge. No other  
hardware must be detached. Store or discard the side covers.  
3. Carefully replace the cabinet top cover and secure with the four  
screws removed in Step 1. Position the cover lip to fit behind the  
front panel display.  
+
EATON Powerware® 9170 Rail Kit (9- and 12-Slot Cabinets) Installation Guide S 164201420 Rev B  
1
 
RACK-MOUNT INSTALLATION  
4. Install six metal clip nuts (nine clip nuts for 12-slot cabinets) onto  
each side flange along the front of the cabinet (see Figure 1).  
NOTE DO NOT install metal clip nuts in the bottom cabinet section.  
Metal Clip Nuts  
Tab Slots  
Tab Slots  
Metal Clip Nuts  
Tab Slots  
Metal Clip Nuts  
Figure 1. Metal Clip Nut and Tab Slot Locations  
+
EATON Powerware® 9170 Rail Kit (9- and 12-Slot Cabinets) Installation Guide S 164201420 Rev B  
2
 
RACK-MOUNT INSTALLATION  
5. Install two rack-mount ears (three for 12-slot cabinets) on each side  
of the cabinet (see Figure 2).  
Insert the two offset tabs on the rear edge of the ear into the  
matching tab slots on the cabinet side frame (see Figure 1). Pivot  
the ear forward until it is flush against the cabinet side frame.  
Secure each ear with three 1/4-20×1/2Phillips-head bolts; screw  
the bolts into the metal clip nuts installed in Step 4.  
NOTE DO NOT install rack-mount ears in the bottom cabinet section.  
Rack-Mount Ear  
Rack-Mount Ear  
Rack-Mount Ear  
Figure 2. Rack-Mount Ears Installed  
+
EATON Powerware® 9170 Rail Kit (9- and 12-Slot Cabinets) Installation Guide S 164201420 Rev B  
3
 
RACK-MOUNT INSTALLATION  
6. Select the proper holes in the rail that position the cabinet at the  
desired location in the rack.  
7. Install one equipment rail on each side of the rack using four  
10-32×1/2flat-head screws per rail.  
8. With one person lifting each side of the cabinet, position the cabinet  
onto the two equipment rails (see Figure 3).  
Carefully slide the cabinet into the equipment rack until the  
rack-mount ears of the cabinet are flush with the front vertical rails  
of the rack. Verify that the holes in the ears align with the holes in  
the rack.  
Equipment Rail  
Figure 3. Rails Holding UPS Cabinet  
+
EATON Powerware® 9170 Rail Kit (9- and 12-Slot Cabinets) Installation Guide S 164201420 Rev B  
4
 
RACK-MOUNT INSTALLATION  
®
9. Secure the cabinet in the rack using 10-32×1/2Torx screws or  
other appropriate customer-specified screws.  
10. Follow the instructions in the UPS user’s guide to install the power  
and battery modules.  
Service and Support  
If you have any questions or problems with the UPS, call your Local  
Distributor or the Help Desk at one of the following telephone numbers  
and ask for a UPS technical representative.  
United States:  
Canada:  
All other countries:  
1-800-356-5737 or 1-919-870-3149  
1-800-461-9166 ext 260  
Call your local service representative  
Please have the following information ready when you call the Help  
Desk:  
S Model number  
S Serial number  
S Version number (if available)  
S Date of failure or problem  
S Symptoms of failure or problem  
S Customer return address and contact information  
If repair is required, you will be given a Returned Material Authorization  
(RMA) Number. This number must appear on the outside of the package  
and on the Bill Of Lading (if applicable). Use the original packaging or  
request packaging from the Help Desk or distributor. Units damaged in  
shipment as a result of improper packaging are not covered under  
warranty. A replacement or repair unit will be shipped, freight prepaid for  
all warrantied units.  
NOTE For critical applications, immediate replacement may be available. Call the Help  
Desk for the dealer or distributor nearest you.  
+
EATON Powerware® 9170 Rail Kit (9- and 12-Slot Cabinets) Installation Guide S 164201420 Rev B  
5
 
*164201420B*  
164201420 B  
 

Compaq Personal Computer 408525 001 User Manual
Cornelius Ice Maker P N 630000085 User Manual
Cornelius Ice Maker Series 200 User Manual
Cuisinart Frozen Dessert Maker ICE 20 User Manual
Delta Electronics Power Supply Series E36SR User Manual
Edelbrock Automobile Parts TRX300EX User Manual
Electro Voice Portable Speaker E V TWO User Manual
Frigidaire Cooktop 318200603 User Manual
GBC Paper Shredder 5160X User Manual
GE Washer G1579 User Manual