Generac Power Systems Automobile Parts QT02516 User Manual

Standby Power Rating  
25 kW 60 Hz  
Liquid Cooled  
Gas Engine  
Generator Sets  
WHISPER-TEST  
Low Speed Exercise  
62 dB(A) at 23 feet  
GENERAC 1.6L ENGINE  
Naturally Aspirated  
Gaseous Fueled  
UL 2200 Listed  
Transfer Switch is sold separately  
STANDARD EQUIPMENT  
Watertight state of the art electrical connectors  
All input connections in one single area  
High coolant temperature shutdown  
Low oil pressure shutdown  
Low coolant level automatic shutdown  
Overspeed automatic shutdown  
Crank timer  
Mainline circuit breaker  
Radiator drain extension  
Battery charge alternator  
2 Amp static battery charger  
Battery rack and battery cables  
Fan and belt guards  
Isochronous governor  
UV/Ozone resistant hoses  
Flex fuel line pigtail  
Exercise timer  
Oil drain extension  
Cool flow radiator  
Closed coolant recovery system  
FEATURES  
State of the art control system with R-Series digital control panel  
Watertight electrical connectors  
Rodent proof construction  
High efficiency, low distortion Generac designed alternator  
Vibration isolated from mounting base  
Matching Generac transfer switches engineered and tested to work  
as a system  
Innovative design and fully prototype tested  
UL 2200 Listed  
Solid state frequency compensated  
voltage regulator  
Dynamic and static battery charger  
Sound attenuated acoustically designed enclosure  
Whisper-Test™ for low noise level exercise  
Acoustically designed engine cooling system  
High flow low noise factory engineered exhaust system  
All components easily accessible for maintenance  
Electrostatically applied powder paint  
COMMERCIAL SERIES  
 
COMMERCIAL 25 kW  
COMMERCIAL SERIES  
OPERATING DATA  
COMMERCIAL 25 kW  
KW RATING  
25  
ENGINE SIZE  
1.6 Liter 4 cyl. inline  
GENERATOR OUTPUT VOLTAGE/KW - 60Hz  
120/208V, 3-phase, 0.8 pf  
KW LP  
25  
KW NG  
AMP LP AMP NG CB Size  
24  
86.8  
83.3  
100  
120/240V, 3-phase, 0.8 pf  
25  
24  
75.2  
72.2  
90  
GENERATOR LOCKED ROTOR KVA  
AVAILABLE @ VOLTAGE DIP OF 35%  
208 or 240V 3-phase  
34  
ENGINE FUEL CONSUMPTION (Natural Gas) (Propane)  
Natural Gas  
(ft3/hr.)  
60  
Propane  
(gal/hr.)  
cu ft/hr  
24  
64  
101  
138  
175  
Exercise cycle  
0.65  
1.76  
2.77  
3.79  
4.81  
25% of rated load  
50% of rated load  
75% of rated load  
100% of rated load  
161  
253  
345  
437  
ENGINE COOLING  
Air flow (inlet air including alternator and combustion air) ft3/min.  
1,528  
2.0  
110,000  
60 (150)  
50 (140)  
System coolant capacity  
US gal.  
BTU/hr.  
°C (°F)  
°C (°F)  
Heat rejection to coolant  
Max. operating air temp. on radiator  
Max. ambient temperature  
COMBUSTION AIR REQUIREMENTS  
Flow at rated power 60 Hz  
cfm  
90  
SOUND EMISSIONS IN DBA  
db(A) @ 23 feet in exercise mode  
db(A) @ 23 feet at normal operating load  
62  
74  
EXHAUST  
Exhaust flow at rated output 60 Hz  
Exhaust temp. at muffler outlet  
cfm  
°F  
249  
1015  
ENGINE PARAMETERS  
Rated synchronous RPM  
HP at rated KW  
60 Hz  
60 Hz  
3600  
45  
POWER ADJUSTMENT FOR AMBIENT CONDITIONS  
Temperature Deration  
3% for every 10 °C above - °C  
1.65% for every 10 °F above - °F  
Altitude Deration  
25  
77  
1% for every 100 m above - m  
3% for every 1000 ft. above - ft.  
183  
600  
RATING: All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to  
varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change  
without notice. Maximum wattage and current are subject to and limited by such factors as fuelBtu content, ambient temperature, altitude, engine power and condition, etc.  
 
INTERCONNECTIONS  
COMMERCIAL 25 kW  
18-30  
R-SERIES  
CONTROL PANEL  
CIRCUIT BREAKER SIZE  
KW  
VOLTS / AMPS  
LUG SIZE  
25  
25  
208 3ø  
240 3ø  
100  
90  
#6 - 300 MCM  
#4 - 1/0  
INSTALLATION LAYOUT  
COMMERCIAL SERIES  
VISE ACTION LATCH,  
ONE PER DOOR, ONE LIFT-OFF  
CONTROL PANEL R TYPE  
BATTERY CHARGER IS  
ENCLOSED WITHIN  
DOOR PER SIDE OF GENERATOR  
62.2  
46  
DOOR TYP  
EXHAUST AND AIR DISCHARGE  
LOUVERS - FRONT AND SIDES  
29  
AUTO  
OFF  
OFF  
ON  
MANUAL  
SET  
EXERCISE  
TIME  
OVER CRANK  
OVER SPEED  
LOW COOLANT LEVEL  
HI COOLANT TEMPERATURE  
LOW OIL PRESSURE  
LOW BATTERY  
LOW FUEL PRESSURE  
SYSTEM READY  
27.4  
DANGER  
High voltage.  
FUSES  
LOCATED  
INSIDE  
Contact with terminals  
may result in personal  
injury or death.  
0F3215  
DOOR  
TYP  
33.5  
6
MIN.  
RIGHT SIDE VIEW  
CONCRETE BASE  
NOT INCLUDED  
FRONT VIEW  
30.7  
FUEL LINE CONNECTION  
3/4" NPT FEMALE COUPLING  
EXHAUST MUFFLERS  
ENCLOSED WITHIN,  
UNIT WEIGHT: Steel 875 lbs.  
®
GENERAC POWER SYSTEMS, INC. • P.O. BOX 297 • WHITEWATER, WI 53190  
Bulletin 0174350SBY / Printed in USA 05.07  
© 2007 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice.  
 

Echo Chainsaw CS 370 User Manual
Eicon Networks Network Card C2x Family User Manual
Fisher Paykel Refrigerator RF540 User Manual
Frigidaire Dishwasher FGHD2455LB User Manual
Fujitsu Printer FTP 627 Series User Manual
Fujitsu Server T5440 User Manual
Fujitsu Stud Sensor SK TSC 1125S User Manual
GBC Laminate Trimmer F 160 CE User Manual
Gemini Turntable XL DD50 IV E User Manual
GE Monogram Refrigerator ZIS480NR User Manual