Honeywell Burner RM7800E User Manual

RM7800E,G,L,M; RM7840E,G,L,M  
7800 SERIES Relay Modules  
INSTALLATION INSTRUCTIONS  
Maximum Total Connected Load: 2000 VA.  
APPLICATION  
Fusing: 15A maximum, Type SC or equivalent Fast Blow.  
The Honeywell RM7800/RM7840 Relay Modules are  
microprocessor-based integrated burner controls for  
automatically fired gas, oil, or combination fuel single burner  
applications. The RM7800/RM7840 Relay Modules are used  
for UL/CSA On/Off, UL/CSA Modulating, and FM/IRI  
Modulating burner applications. The RM7800/RM7840 system  
consists of a Relay Module. Keyboard Display Modules  
(standard with RM7800), Dust Cover (standard with RM7840),  
Subbase, Amplifier, and Purge Card. Options include DATA  
CONTROLBUS MODULE™, Remote Display Mounting, First-  
Out Expanded Annunciator and Communications through  
Modbus™.  
Environmental Ratings:  
Ambient Temperature:  
Operating: -40°F to +140°F (-40°C to +60°C).  
Storage: -40°F to +150°F (-40°C to +66°C).  
Humidity: 85% relative humidity continuous, noncondensing.  
Vibration: 0.5G environment.  
SIL 3 Capable:  
SIL 3 Capable in a properly designed Safety Instrumented  
System. See form number 65-0312 for Certificate Agree-  
ment.  
Functions provided by the RM7800/RM7840 include  
automatic burner sequencing, flame supervision, system  
status indication, system or self-diagnostics and  
troubleshooting. The RM7800/RM7840 is a solid state  
replacement for the electromechanical R4140 Automatic  
Programming Control.  
Approvals:  
Underwriters Laboratories Inc. Listed: File No. MP268,  
Guide No. MCCZ.  
Canadian Standards Association Certified: LR9S329-3.  
Factory Mutual Approved: Report No. J.I.1V9A0.AF.  
Swiss Re (formerly IRI): Acceptable.  
Federal Communications Commission, Part 15,  
Class B—Emissions.  
This document provides installation and static checkout  
instructions. Other applicable publications are:  
65-0084:Q7800A,B 22-Terminal Wiring Subbase Product  
Data.  
65-0089:ST7800A Plug-In Purge Timer Installation  
Instructions.  
INSTALLATION  
65-0090:S7800A Keyboard Display Module Product Data.  
65-0091:S7810A Data ControlBus Module™ Product Data.  
65-0095:S7820 Remote Reset Module Product Data.  
65-0097:221729C Dust Cover Packing Sheet.  
65-0101:S7830 Expanded Annunciator Product Data.  
65-0109:R7824, R7847, R7848, R7849, R7851, R7852,  
R7861, R7886 Flame Amplifiers for the 7800 SERIES  
Product Data.  
When Installing this Product...  
1. Read these instructions carefully. Failure to follow  
them could damage the product or cause a hazardous  
condition.  
2. Check the ratings given in the instructions and marked  
on the product to make sure the product is suitable for  
the application.  
3. Installer must be a trained, experienced, flame  
safeguard service technician.  
65-0131:221818A Extension Cable Assembly Product  
Data.  
4. After installation is complete, check out the product  
65-0229:7800 SERIES RELAY MODULES Checkout and  
Troubleshooting Product Data.  
operation as provided in these instructions.  
65-0249:S7810M ModBus™ Module Product Data.  
WARNING  
Can cause property damage, severe injury,  
or death.  
To prevent possible hazardous burner operation, verify  
safety requirements each time a control is installed on  
a burner.  
Fire or Explosion Hazard.  
SPECIFICATIONS  
Electrical Ratings, see Table 3:  
Voltage and Frequency: 120 Vac (+10/-15%), 50 or 60 Hz  
(±10%).  
Power Dissipation: RM7800/RM7840: 10W maximum.  
SIL3  
Capable  
66-1085-04  
 
RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES  
a. Do not run high voltage ignition transformer wires in  
the same conduit with the flame detector, Data  
Controlbus Module™, or Remote Reset Module  
wiring.  
b. Do not route flame detector, Data Controlbus  
Module™, or Remote Reset Module leadwires in  
conduit with line voltage circuits.  
c. Remote Reset leadwires—The maximum length of  
wire is 1000 feet to a Remote Reset pushbutton.  
d. Data Controlbus Module™—The maximum Data  
Controlbus Module™ cable length depends on the  
number of system modules connected, the noise  
conditions and the cable used. The maximum length  
of all Data Controlbus Module™ interconnecting  
wire is 1000 feet.  
c. Enclose flame detector leadwires without armor  
cable in metal cable or conduit.  
10. Make sure loads do not exceed the terminal ratings.  
Refer to the label on the RM7800/RM7840 or to the  
ratings in Tables 3, 4 and 5.  
d. Follow directions in flame detector, Data Controlbus  
Module™, or Remote Reset Module Instructions.  
8. Keyboard Display Module (KDM): Because the KDM is  
powered from a low voltage, energy limited source, it  
can be mounted outside of a control panel if it is  
protected from mechanical damage.  
Final Wiring Check  
1. Check the power supply circuit. The voltage and  
frequency tolerance must match those of the  
RM7800/RM7840. A separate power supply circuit may  
be required for the RM7800/RM7840. Add the required  
disconnect means and overload protection.  
2. Check all wiring circuits and complete the Static  
Checkout, see Table 8, before installing the  
RM7800/RM7840 on the subbase.  
NOTE: A 13 Vdc power supply must be used any time more  
than one Keyboard Display Module is used.  
9. Maximum wire lengths follow:  
a. RM7800/RM7840 leadwires—The maximum length  
of leadwire is 300 feet to terminal inputs (Control,  
Preignition Interlock, Running/Lockout Interlock,  
High Fire Switch and Low Fire Switch).  
b. Flame Detector leadwires—The maximum flame  
sensor leadwire length is limited by the flame signal  
strength.  
3. Install all electrical connectors.  
4. Restore power to the panel.  
Table 1. Recommended Wire Sizes and Part Numbers.  
Application  
Line voltage terminals  
Recommended Wire Size  
Recommended Part Number(s)  
14, 16 or 18 AWG copper conductor, 600 TTW60C, THW75C, THHN90C.  
volt insulation, moisture-resistant wire.  
Keyboard Display Module (KDM)  
Data ControlBus Module™  
Remote Reset Module  
22 AWG two-wire twisted pair with  
ground, or five wire.  
Belden 8723 shielded cable or equivalent.  
22 AWG two-wire twisted pair with  
ground, or five wire.  
Belden 8723 shielded cable or equivalent.  
22 AWG two-wire twisted pair, insulated  
for low voltage.  
13 Vdc full-wave rectified transformer  
power input.  
18 AWG wire insulated for voltages and TTW60C, THW75C, THHN90C.  
temperatures for given application.  
3
66-1085—04  
 
RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES  
L1  
(HOT) L2  
1
4
L2  
120 Vac,  
50/60 Hz  
PLUG-IN PURGE  
TIMER CARD  
CONFIGURATION  
JUMPERS  
TEST  
JACK  
FLAME SIGNAL  
RUN/TEST  
SWITCH  
F
PLUG-IN  
FLAME  
G
MICROCOMPUTER  
AMPLIFIER  
TEST  
RESET  
PUSHBUTTON  
22  
2K  
3K  
4K  
RELAY  
DRIVE  
5K  
RELAY  
6K  
7K  
8K  
CIRCUIT  
STATUS  
FEEDBACK  
AND LINE  
VOLTAGE  
INPUTS  
9K  
SAFETY RELAY  
CIRCUIT  
1K  
STATUS LEDs  
CONTROL  
POWER  
POWER SUPPLY  
20  
PRE-IGNITION  
INTERLOCK  
RUNNING/  
LOCKOUT  
LIMITS CONTROLLER  
INTERLOCK  
1K1  
2K1 5K1  
7
6
10  
8
IGNITION  
4K1  
7K1  
2K2  
LOW FIRE SWITCH  
18  
PILOT  
21  
9
PILOT/V2  
HIGH FIRE SWITCH  
19  
MAIN VALVE  
6K1  
3K1  
5
3
BLOWER  
ALARM  
HIGH FIRE  
12  
KEYBOARD  
DISPLAY MODULE  
8K1  
8K2  
9K2  
DDL  
COMMON  
INDICATES FEEDBACK SENSING  
OF RELAY CONTACT STATUS  
AND LINE VOLT INPUTS  
13  
15  
14  
RS485  
MODULATE  
1
2
9K1  
DDL  
FIELD WIRING  
INTERNAL WIRING  
REMOTE  
RESET  
3
LOW FIRE  
COMMUNICATIONS  
1
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.  
M12258  
Fig. 1. Internal block diagram of the RM7800L/RM7840L (See Fig. 2, 3, 4 or 5  
for individual detailed wiring instructions).  
66-1085—04  
4
 
RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES  
Table 2. Recommended Grounding Practices.  
Ground Type  
Recommended Practice  
Earth ground (subbase and relay module).  
1. Use to provide a connection between the subbase and  
the control panel of the equipment. Earth ground must be  
capable of conducting enough current to blow the 20A fuse  
(or breaker) in the event of an internal short circuit.  
2. Use wide straps or brackets to provide minimum length,  
maximum surface area ground conductors. If a leadwire  
must be used, use 14 AWG copper wire.  
3. Make sure that mechanically tightened joints along the  
ground path are free of nonconductive coatings and pro-  
tected against corrosion on mating surfaces.  
Signal ground (KDM, Data ControlBus Module™  
Use the shield of the signal wire to ground the device to the  
signal ground terminals [3(c)] of each device. Connect the  
shield at both ends of the chain to earth ground.  
Table 3. Terminal Ratings.  
Description  
Terminal No.  
Ratings  
a
G
Flame Sensor Ground  
a
Earth G  
Earth Ground  
L2(N)  
Line Voltage Common  
Alarm  
3
4
120 Vac, 1A pilot duty.  
b
Line Voltage Supply (L1)  
120 Vac (+10%/-15%), 50 or 60 Hz (±10%)  
120 Vac, 9.8 AFL, 58.8 ALR (inrush).  
120 Vac, 1 mA.  
5
6
7
8
Burner Motor  
Burner Controller and Limits  
Lockout/Running Interlock  
Pilot Valve/Ignition  
120 Vac, 8A run, 43A inrush.  
c
120 Vac .  
c
9
Main Fuel Valve  
Ignition  
120 Vac .  
c
10  
120 Vac .  
F(11)  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
Flame Sensor  
60 to 220 Vac, current limited.  
120 Vac, 75 VA pilot duty.  
120 Vac, 75 VA pilot duty.  
120 Vac, 75 VA pilot duty.  
120 Vac, 75 VA pilot duty.  
Firing Rate High Fire  
Firing Rate Common  
Firing Rate Low Fire  
Firing Rate Modulate  
Unused  
Unused  
Low Fire Switch Input  
High Fire Switch Input  
Preignition Interlock Input  
Interrupted/Intermittent Pilot Valve/First Stage Oil Valve  
120 Vac, 1 mA.  
120 Vac, 1 mA.  
120 Vac, 1 mA.  
c
120 Vac .  
22  
a
Shutter  
120 Vac, 0.5A.  
.
The relay module must have an earth ground providing a connection between the subbase and the control panel or the  
equipment. The earth ground wire must be capable of conducting the current to blow the 15A fuse (or breaker) in event of an  
internal short circuit. The relay module requires a low impedance ground connection to the equipment frame, which, in turn,  
requires a low impedance connection to earth ground.  
b
c
2000 VA maximum connected load to relay module assembly.  
See tables 4 and 5.  
5
66-1085—04  
 
RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES  
Table 4. Combinations for Terminals 8, 9, 10 and 21.  
Main 9 Ignition 10  
Pilot Fuel 8  
Intermittent Pilot Valve 21  
No Load  
C
B
F
F
F
F
F
F
D
D
D
No Load  
No Load  
No Load  
No Load  
F
No Load  
B
A
A
A
A
A
A
No Load  
No Load  
D
F
No Load  
No Load  
D
D
No Load  
D
No Load  
Table 5. Explanation of Each Combination.  
C
A
B
D
F
4.5A ignition.  
50 VA Pilot Duty plus  
4.5A ignition.  
180 VA ignition plus  
motor valve with:  
2A Pilot Duty.  
64 VA Pilot Duty plus motor  
valves with:  
660 VA inrush, 360 VA  
open, 260 VA hold.  
3850 VA inrush, 700 VA  
open, 250 VA hold.  
3. Make sure no subbase wiring is projecting beyond the  
terminal blocks. Tuck in wiring against the back of the  
subbase so it does not interfere with the knife blade  
terminals or bifurcated contacts.  
Mounting RM7800/RM7840  
Relay Module (Fig. 5)  
1. Mount the RM7800/RM7840 vertically on the Q7800  
Subbase, or mount horizontally with the knife blade  
terminals pointing downward. When mounted on the  
Q7800A, the RM7800/RM7840 must be in an electrical  
enclosure.  
IMPORTANT  
The RM7800/RM7840 must be installed with a  
plug-in motion rather than a hinge action.  
2. When mounting in an electrical enclosure, provide  
adequate clearance for servicing, installation and  
removal of the RM7800/RM7840, Keyboard Display  
Module, flame amplifier, flame amplifier signal voltage  
probes, electrical signal voltage probes, and electrical  
connections.  
4. Mount the RM7800/RM7840 by aligning the four  
L-shaped corner guides and knife blade terminals with  
the bifurcated contacts on the wiring subbase and  
securely tighten the two screws without deforming the  
plastic.  
a. Allow an additional two inches below the  
RM7800/RM7840 for the flame amplifier mounting.  
b. Allow an optional three-inch minimum to both sides  
of the RM7800/RM7840 for electrical signal voltage  
probes.  
66-1085—04  
6
 
RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES  
SERIES 90  
FIRING RATE  
MOTOR  
SERIES 90  
CONTROLLER  
Q7800  
HIGH FIRE  
COMMON  
LOW FIRE  
MODULATE  
12  
13  
14  
G
B
R
B
R
FOR DIRECT SPARK IGNITION (OIL  
OR GAS)  
L2  
IGNITION  
TRANSFORMER  
10  
W
3
4
5
W
120V ALARM  
8
9
L2  
15  
16  
(L1)  
2ND STAGE  
FUEL VALVE  
(OPTIONAL)  
BURNER MOTOR  
(BLOWER)  
BURNER  
CONTROLLER/LIMITS  
17  
6
4
LOCKOUT INTERLOCKS  
(INC. AIR FLOW SWITCH)  
LOW FIRE  
7
8
18  
19  
20  
21  
22  
START SWITCH  
1
2
120V, 50/60 Hz POWER SUPPLY. PROVIDE DISCONNECT  
MEANS AND OVERLOAD PROTECTION AS REQUIRED.  
10 SEC. INTERRUPTED  
PILOT/IGNITION  
HIGH FIRE  
PURGE SWITCH  
RM7800/7840E ONLY: HIGH FIRE PURGE SWITCH  
2
5
CONNECTED TO  
(L1), NOT  
.
4
5
MAIN FUEL VALVE(S)  
9
10  
F
PREIGNITION  
INTERLOCK  
3
SEE FLAME DETECTOR INSTALLATION INSTRUCTIONS  
FOR CORRECT WIRING.  
5 SECOND IGNITION  
(EARLY SPARK  
TERMINATION)  
15 SEC.  
INTERRUPTED  
PILOT VALVE  
4
5
DO NOT WIRE TO ANY UNUSED TERMINALS.  
RM7840L1026, RM7800L1053 HAVE INTERMITTENT  
PILOT VALVE FUNCTIONS.  
FLAME DETECTOR  
3
L1  
(HOT)  
1
L2  
M12261C  
MASTER  
SWITCH  
RM7800/RM7840E,L  
INITIATE  
(INITIAL  
POWERUP  
PREPURGE  
HOLD  
DRIVE TO  
HIGH FIRE  
PREPURGE PFEP  
HOLD  
DRIVE TO  
10 SEC.  
00  
(4 SEC. IF  
00  
00  
00  
10  
20 25  
MFEP  
00  
POSTPURGE STANDBY  
POWER POWER  
15  
TIMED  
PREPURGE  
ONLY)  
LOW FIRE JR1 CLIPPED  
STANDBY  
POWER  
RUN  
POWER  
POWER  
POWER  
POWER  
POWER  
POWER  
PILOT  
POWER  
PILOT  
LED  
DISPLAY  
PILOT  
FLAME  
MAIN  
PILOT  
FLAME  
MAIN  
PILOT  
FLAME  
MAIN  
FLAME  
MAIN  
FLAME  
MAIN  
ALARM  
ALARM  
ALARM  
ALARM  
ALARM  
BURNER/BLOWER MOTOR  
10 IGN.  
5
BURNER  
1
5 SEC.  
10 SEC. IGN./PILOT  
15 SEC. PILOT  
8
21  
2
9
MAIN VALVE  
OPERATING  
CONTROLS  
AND  
TO  
TO  
LIMITS AND BURNER CONTROLLER CLOSED  
LOCKOUT INTERLOCKS CLOSED  
L1  
6
6
7
INTERLOCK. CHECK  
IC  
INTERLOCKS  
PREIGNITION INTERLOCK CLOSED  
TO 19 HIGH FIRE SW.  
4
TO 20  
PII  
18  
5
5
LOW FIRE SW.  
TO  
FLAME PROVING  
13  
1
FLAME  
SIGNAL  
SSC  
SAFE START CHECK  
SWITCHING  
15  
TO  
TO  
14  
13  
14  
13  
TO  
13  
12  
TO  
FIRING  
RATE  
MOTOR ACTION  
MOTOR  
1
2
FOR THE R7800/R7840E: THE HIGH FIRE SWITCH MUST BE WIRED CORRECTLY TO PERFORM ENERGY SAVING PURGE  
FUNCTIONS. THE BURNER/BLOWER MOTOR DOES NOT START UNTIL THE HIGH FIRE SWITCH MAKES.  
RM7800L1053, RM7840L1026: TERMINAL 21 PROVIDES INTERMITTENT PILOT FUNCTION.  
M12263D  
Fig. 2. Wiring subbase and sequence for RM7800E,L/RM7840E,L.  
7
66-1085—04  
 
RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES  
SERIES 90  
FIRING RATE  
MOTOR  
SERIES 90  
CONTROLLER  
Q7800  
HIGH FIRE  
COMMON  
LOW FIRE  
G
12  
13  
14  
B
B
R
L2  
R
W
3
4
5
W
120V ALARM  
MODULATE  
(L1)  
15  
16  
FOR DIRECT SPARK IGNITION  
(OIL OR GAS)  
BURNER MOTOR  
(BLOWER)  
3
IGNITION  
TRANSFORMER  
10  
BURNER  
CONTROLLER/LIMITS  
17  
6
4
1ST STAGE  
FUEL VALVE  
21  
L2  
RUNNING INTERLOCKS  
(INC. AIR FLOW SWITCH)  
LOW FIRE  
START SWITCH  
7
8
18  
19  
20  
21  
22  
2ND STAGE  
9
FUEL VALVE  
(OPTIONAL)  
10 SEC. INTERRUPTED  
PILOT/IGNITION  
2
JUMPER WIRE FOR 30s MFEP  
MAIN FUEL VALVE(S)  
9
10  
F
PREIGNITION  
INTERLOCK  
1
2
120V, 50/60 Hz POWER SUPPLY. PROVIDE DISCONNECT  
MEANS AND OVERLOAD PROTECTION AS REQUIRED.  
5 SECOND IGNITION  
(EARLY SPARK  
TERMINATION)  
15 OR 30 SEC.  
INTERRUPTED/  
INTERMITTENT  
PILOT VALVE  
ADD JUMPER FOR 30 SECOND MAIN FLAME  
ESTABLISHING PERIOD (MFEP).  
FLAME DETECTOR  
4
3
4
DO NOT WIRE TO ANY UNUSED TERMINALS.  
L1  
(HOT)  
SEE FLAME DETECTOR INSTALLATION INSTRUCTIONS  
FOR CORRECT WIRING.  
L2  
MASTER  
SWITCH  
M12260B  
1
RM7800G/RM7840G  
INITIATE  
(INITIAL  
POWERUP  
ONLY)  
PREPURGE PFEP  
10 SEC.  
00  
HOLD  
DRIVE TO  
00  
00  
10  
20 25  
MFEP  
00  
POSTPURGE STANDBY  
POWER POWER  
15  
TIMED  
PREPURGE  
(4 SEC. IF  
LOW FIRE JR1 CLIPPED  
STANDBY  
POWER  
RUN  
POWER  
POWER  
POWER  
POWER  
POWER  
PILOT  
POWER  
PILOT  
LED  
DISPLAY  
PILOT  
FLAME  
MAIN  
PILOT  
FLAME  
MAIN  
PILOT  
FLAME  
MAIN  
FLAME  
MAIN  
FLAME  
MAIN  
ALARM  
ALARM  
ALARM  
ALARM  
ALARM  
BURNER/BLOWER MOTOR  
10 IGN.  
10 SEC. IGN./PILOT  
15/30 SEC. INTERRUPTED/INTERMITTENT PILOT VALVE 21  
MAIN VALVE  
5
BURNER  
5 SEC.  
8
9
OPERATING  
CONTROLS  
AND  
TO  
TO  
LIMITS AND BURNER CONTROLLER CLOSED L1  
6
7
6
INTERLOCK. CHECK  
PREIGNITION INTERLOCK CLOSED  
LOW FIRE SW.  
RUNNING INTERLOCKS CLOSED  
IC  
INTERLOCKS  
4
TO 20  
PII  
18  
5
TO  
FLAME PROVING  
13  
FLAME  
SIGNAL  
SSC  
SAFE START CHECK  
15  
TO  
RM7800/7840G SWITCHING  
13  
TO  
14  
14  
13  
TO  
13  
12  
TO  
FIRING  
RATE  
MOTOR ACTION  
MOTOR  
M12264A  
Fig. 3. Wiring subbase and sequence for RM7800G/RM7840G.  
66-1085—04  
8
 
RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES  
Q7800  
G
12  
13  
14  
COMMON  
L2  
FOR DIRECT SPARK IGNITION  
(OIL OR GAS)  
3
4
5
120V ALARM  
IGNITION  
TRANSFORMER  
10  
2
MODULATE  
DAMPER  
MOTOR  
(L1)  
15  
16  
1ST STAGE  
FUEL VALVE  
21  
L2  
BURNER MOTOR  
(BLOWER)  
2ND STAGE  
9
FUEL VALVE  
(OPTIONAL)  
BURNER  
CONTROLLER/LIMITS  
17  
6
2
2
LOW FIRE  
START SWITCH  
RUNNING INTERLOCKS  
(INC. AIR FLOW SWITCH)  
7
8
18  
19  
20  
21  
22  
10 SEC. INTERRUPTED  
PILOT/IGNITION  
3
1
2
120V, 50/60 Hz POWER SUPPLY. PROVIDE  
DISCONNECT MEANS AND OVERLOAD  
PROTECTION AS REQUIRED.  
MAIN FUEL VALVE(S)  
9
10  
F
PREIGNITION  
INTERLOCK  
WHEN NO DAMPER MOTOR OR LOWFIRE  
SWITCH IS USED, JUMPER TERMINAL 14  
TO TERMINAL 18. DO NOT WIRE TERMINAL 15.  
5 SECOND IGNITION  
(EARLY SPARK  
TERMINATION)  
INTERMITTENT  
PILOT  
3
4
DO NOT WIRE TO ANY UNUSED TERMINALS.  
SEE FLAME DETECTOR INSTALLATION  
INSTRUCTIONS FOR CORRECT WIRING.  
FLAME DETECTOR  
4
L1  
(HOT)  
1
L2  
M12262A  
MASTER  
SWITCH  
RM7800M/RM7840M  
INITIATE  
(INITIAL  
POWERUP  
ONLY)  
PREPURGE PFEP  
HOLD  
10 SEC.  
00  
00  
00  
10  
20 25  
00  
POSTPURGE STANDBY  
POWER POWER  
15  
TIMED  
PREPURGE  
DRIVE TO  
LOW FIRE  
(4 SEC. IF  
JR1 CLIPPED  
POWER  
STANDBY  
MFEP  
RUN  
POWER  
POWER  
POWER  
POWER  
POWER  
PILOT  
POWER  
PILOT  
LED  
DISPLAY  
PILOT  
FLAME  
MAIN  
PILOT  
FLAME  
MAIN  
PILOT  
FLAME  
MAIN  
FLAME  
MAIN  
FLAME  
MAIN  
ALARM  
ALARM  
ALARM  
ALARM  
ALARM  
BURNER/BLOWER MOTOR  
10 IGN.  
10 SEC. IGN./PILOT  
5
BURNER  
5 SEC.  
8
INTERMITTENT PILOT VALVE 21  
MAIN VALVE  
9
OPERATING  
CONTROLS  
AND  
TO  
TO  
LIMITS AND BURNER CONTROLLER CLOSED L1  
6
7
6
INTERLOCK. CHECK  
RUNNING INTERLOCKS CLOSED  
TO 20  
LOW FIRE SW.  
IC  
INTERLOCKS  
PREIGNITION INTERLOCK CLOSED  
4
PII  
18  
5
TO  
FLAME PROVING  
13  
FLAME  
SIGNAL  
SSC  
SAFE START CHECK  
RM7800M/7840M SWITCHING  
13 15  
15  
TO  
TO  
MOTOR ACTION  
DAMPER  
MOTOR  
M12265A  
Fig. 4. Wiring subbase and sequence for RM7800M/RM7840M.  
9
66-1085—04  
 
RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES  
WIRING  
SUBBASE  
RUN/TEST  
SWITCH  
HONEYWELL  
RELAY  
MODULE  
CONFIGURATION  
JUMPERS  
PURGE  
TIMER  
SEQUENCE  
STATUS  
LED PANEL  
POWER  
RESET  
BUTTON  
PILOT  
FLAM  
E
MAIN  
ALARM  
RE  
KEYBOARD  
DISPLAY  
MODULE  
CAPTIVE  
MOUNTING  
SCREW  
SET  
(STANDARD ON  
RM7800E,G,L,M)  
BUR  
NE  
R
CONTROL  
FLAME  
AMPLIFIER  
S
CROLL  
MODE  
- S  
A
V
E
-
M16353  
Fig. 5. RM7800/RM7840 Relay Module exploded view.  
d. Ignition/pilot valve/intermittent pilot valve terminal is  
energized.  
e. Main valve terminal is energized.  
f. Internal system fault occurred.  
g. Purge card is not installed or is removed.  
h. Purge card is bad.  
SAFETY SHUTDOWN  
Safety Shutdown (Lockout) occurs if  
any of the following occur during the  
indicated period:  
3. PREPURGE Period:  
a. Preignition Interlock opens anytime during  
1. INITIATE Period:  
PREPURGE period (RM7840E,L).  
a. Purge card is not installed or is removed.  
b. Purge card is bad.  
c. Configuration jumpers are changed (after 200 hours  
of operation).  
d. Ac line power errors occurred, see Operation  
section.  
b. Flame signal is detected after first ten seconds  
during PREPURGE (RM7840E,L).  
c. High Fire Switch fails to close within four minutes  
and fifteen seconds after the firing rate motor is  
commanded to drive to the high fire position at the  
start of PREPURGE (RM7840E,L).  
e. Four minute INITIATE period has been exceeded.  
2. STANDBY Period:  
d. Low Fire Switch fails to close within four minutes  
and fifteen seconds after the firing rate motor is  
commanded to drive to the low fire position at the  
end of PREPURGE.  
e. Running Interlock does not close within 30 seconds  
(RM7840G,M).  
a. Flame signal is present after 240 seconds.  
b. Preignition Interlock is open an accumulative time  
of 30 seconds.  
c. Interlock check feature is enabled and the  
Interlock String (including airflow switch) is closed  
for 120 seconds with controller closed.  
f. Lockout Interlock does not close within 10 seconds  
(RM7840E,L).  
66-1085—04  
10  
 
RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES  
g. Lockout Interlock opens during PREPURGE  
(RM7840E,L).  
h. Ignition/pilot valve/intermittent pilot valve terminal is  
energized.  
i. Main valve terminal is energized.  
j. Internal system fault occurred.  
k. Purge card is removed.  
unless the voltage or frequency tolerances are not met. When  
the tolerances are not met, a hold condition is initiated and  
displayed on the VFD for at least five seconds. When the  
tolerances are met, the INITIATE sequence restarts. If the  
condition is not corrected and the hold condition exists for four  
minutes, the RM7800/RM7840 locks out. Causes for hold  
conditions in the INITIATE sequence:  
l. Purge card is bad.  
4. PILOT FLAME ESTABLISHING Period (PFEP):  
a. Low Fire Switch opens.  
a. AC line dropout is detected.  
b. AC line noise prevents a sufficient reading of the  
line voltage inputs.  
c. Low line voltage brownouts occur.  
b. Lockout Interlock opens (RM7840E,L).  
c. Ignition/pilot valve/intermittent pilot valve terminal is  
not energized.  
The INITIATE sequence also delays the burner motor starter  
from being energized and de-energized from an intermittent  
AC line input or control input.  
d. Early spark termination terminal is energized after  
five seconds.  
e. No flame is present at the end of PFEP.  
f. Main valve terminal is energized (RM7800G,M).  
g. Internal system fault occurred.  
h. Purge card is removed.  
Standby  
The RM7800/RM7840 remains in standby, ready to start. The  
operating control determines a call for heat is present and  
provides input to terminal 6. The burner switch, limits,  
operating control and all microcomputer monitored circuits  
must be in the correct state for the RM7800/RM7840 to  
advance into the PREPURGE sequence.  
i. Purge card is bad.  
5. MAIN FLAME ESTABLISHING Period (MFEP):  
a. Low Fire Switch Opens.  
b. Lockout Interlock opens (RM7840E,L).  
c. Ignition/pilot valve/intermittent pilot valve terminal is  
not energized.  
d. Main valve terminal is not energized.  
e. No flame is present at the end of MFEP.  
f. Internal system fault occurred.  
g. Purge card is removed.  
Prepurge  
The RM7800/RM7840 provides a prepurge timing selectable  
from two seconds to 30 minutes with power applied and the  
RM7800 operating control indicating a call for heat:  
h. Purge card is bad.  
6. RUN Period:  
a. Running Interlocks, Preignition Interlocks, Burner  
Switch, Run/Test Switch, Lockout Interlocks and all  
microcomputer monitored circuits must be in the  
correct operating state.  
b. The blower motor output, terminal 5, is powered to  
start the PREPURGE sequence, except for the  
RM7800E/RM7840E. The firing rate motor is driven  
to the high fire position. The PREPURGE timing for  
the RM7800/RM7840E,L does not begin until the  
Lockout Interlock String and High Fire Switch are  
both closed. The blower motor output for the  
RM7800E is not energized until the High Fire Switch  
is closed.  
a. No flame is present.  
b. Lockout Interlock opens (RM7840E,L).  
c. Interrupted pilot valve terminal is energized  
(RM7840G,M).  
d. Main valve terminal is not energized.  
e. Internal system fault occurred.  
f. Purge card is removed.  
g. Purge card is bad.  
7. POSTPURGE Period:  
a. Preignition Interlock does not close in five seconds  
and opens after five-second time period.  
b. Ignition/pilot valve/intermittent pilot valve terminal is  
energized.  
c. Main valve terminal is energized.  
d. Internal system fault occurred.  
e. Purge card is removed.  
c. The Preignition Interlock input must remain closed  
throughout PREPURGE; otherwise, control returns  
to the STANDBY state and holds (30 seconds) for  
the RM7800/RM7840G,M or safety shutdown for the  
RM7800/RM7840E,L occurs.  
f. Purge card is bad.  
d. The Lockout Interlock or Running Interlock inputs  
(interlock circuit including Airflow Switch) must close  
by ten seconds into PREPURGE; otherwise, a  
recycle to the beginning of PREPURGE for the  
RM7800/RM7840G,M will happen or a safety  
shutdown for the RM7800/RM7840E,L occurs.  
e. When PREPURGE timing is complete, the firing rate  
motor drives to the low fire position,  
OPERATION  
Sequence of Operation  
The RM7800/RM7840 has the following operating sequences,  
see Fig. 2, 3, 4, and Table 6. The RM7800/RM7840 LED  
provide positive visual indication of the program sequence:  
POWER, PILOT, FLAME, MAIN and ALARM.  
RM7800/RM7840E,G,L.  
f. When the firing rate motor reaches low fire position,  
the Low Fire Switch, terminal 18, input must be  
energized before entering the Ignition Trial state.  
Initiate  
The RM7800/RM7840 enters the INITIATE sequence when  
the Relay Module is powered. The RM7800/RM7840 can also  
enter the INITIATE sequence if the Relay Module verifies  
voltage fluctuations of +10/-15 percent or frequency  
Ignition Trials  
1. Pilot Flame Establishing Period (PFEP):  
a. With the firing rate motor at the low fire position:  
(1) The pilot valve and ignition transformer,  
terminals 8, 10 and 21, are energized. The  
RM7800M has an intermittent pilot valve,  
fluctuations of +/-10 percent during any part of the operating  
sequence. The INITIATE sequence lasts for ten seconds  
11  
66-1085—04  
 
RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES  
terminal 21. The RM7800/RM7840G has an  
interrupted or intermittent pilot valve, terminal  
21, depending on the selection of configuration  
jumper 2. The RM7800/RM7840E,L has a  
fifteen-second interrupted pilot valve, terminal  
21. All of the RM7800/RM7840s have a  
ten-second interrupted pilot valve/ignition,  
terminal 8.  
(a) Not turned off, or  
(b)15 seconds after Terminal 9 is energized and  
JR2 is clipped, or  
(c)30 seconds after Terminal 9 is energized and  
Terminals 5 and 19 are jumpered and jumper  
JR2 is clipped.  
(3) RM7800L1053, RM7840L1026,  
RM7800M/RM7840M: Remain energized as  
long as call for heat is present.  
(2) During PFEP, the Low Fire Switch must remain  
closed. If it opens, a safety shutdown occurs.  
(3) The Preignition Interlock input is ignored  
Run  
throughout the Ignition Trial state.  
b. Flame must be proven by the end of the ten-second  
PFEP (four if JR1 is clipped) to allow the sequence  
to continue. If flame is not proven by the end of  
PFEP, a safety shutdown occurs.  
1. A ten-second stabilization period occurs at the  
beginning of the RUN period.  
2. The firing rate motor releases to modulation  
(RM7800/RM7840E,G,L). Damper motor is energized  
(RM7800/RM7840M).  
3. The RM7800/RM7840 is now in RUN and remains in  
RUN until the controller input, terminal 6, opens,  
indicating that the demand is satisfied or a limit opened.  
c. After five seconds, the ignition, terminal 10, is  
de-energized for early spark termination.  
2. Main Flame Establishing Period (MFEP):  
a. Terminal 9 is energized when the presence of flame  
is verified at the end of a 10-second Pilot Flame  
Establishing Period (PFEP) (four seconds if JR1 is  
clipped).  
Postpurge  
The RM7800/RM7840 provides a fifteen-second  
POSTPURGE following the completion of the RUN period.  
The blower motor output is powered to drive all products of  
combustion and any unburned fuel from the combustion  
chamber. It also supplies combustion air to burn fuel being  
purged from the fuel line downstream of the fuel shutoff valve.  
b. Terminal 8 is turned off 10 seconds after Terminal 9  
is energized.  
c. Terminal 21 action:  
(1) RM7800E,L/RM7840E,L: De-energized  
15 seconds after Terminal 9 is energized.  
(2) RM7840G:  
Table 6. Sequence Timing for Normal Operation.  
Flame Establishing  
Period  
Post-  
Firing  
Rate  
Energy Approval  
Saving Code  
Purge Interlock  
Run Timing Circuits  
a
Device  
Initiate Standby Purge Pilot  
Main  
Circuit Prepurge Bodies  
RM7800E/ 10 sec.. *  
RM7840E  
**  
4 or 10 10 or 15  
*
15 sec. Preignition, 4-wire  
Yes  
FM/IRI  
Modulating  
sec.  
sec.  
Lockout,  
High and  
Low Fire  
modulating  
RM7800G/  
RM7840G  
10, 15 sec.  
or  
intermittent  
Preignition,  
Running,  
Low Fire  
No  
UL/CSA  
Modulating  
RM7800L/  
RM7840L  
10 or 15  
Preignition,  
Lockout,  
High and  
Low Fire  
FM/IRI  
Modulating  
b
sec.  
RM7800M/  
RM7840M  
10 sec. or  
intermittent  
Preignition, 2-wire  
Running, isolated  
UL/CSA  
On-Off  
Low Fire  
On-Off-On  
contacts  
*
STANDBY and RUN can be an infinite time period.  
** PURGE determined by which ST7800A purge card is selected.  
a
The MFEP is determined by which terminal is used, configuration jumper selected or jumper wire added.  
See Fig. 2, 3, 4, 5 and 6.  
b
RM7800L1053, RM7840L1026: 10 second or intermittent.  
Keyboard Display Module (VFD)  
The Keyboard Display Module (see Fig. 5) is provided with the  
RM7800 Relay Module (but is not required for operation) and  
is an option for the RM7840 Relay Module. The first line of the  
Vacuum Fluorescent Display (VFD) provides:  
Current status of the burner sequence (STANDBY,  
PURGE, PILOT IGN, MAIN IGN, RUN and POSTPURGE).  
Timing information (PURGE, PILOT IGN, MAIN IGN and  
POSTPURGE) in minutes and seconds.  
Hold information (PURGE HOLD: T19).  
66-1085—04  
12  
 
RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES  
Lockout information (Lockout, Fault Code, Message and  
Sequence).  
allowing pilot-turn-down test and other burner  
adjustments to be made. This activates a fifteen second  
flameout timer that permits pilot flame adjustment  
without nuisance safety shutdowns. The Run/Test  
Switch is ignored during PFEP for the RM7800/  
RM7840E,L if Terminals 8 and 9 or 9 and 21 are  
jumpered.  
The extreme right side of the first line is either blank or shows  
a small arrow pointing to the second line followed by a  
two-letter code (DI-Diagnostic Information, Hn-Fault History  
Information, and EA-Expanded Annunciator). When the arrow  
and two-letter code are displayed, it indicates the second line  
is showing a selectable message submenu. The second line  
displays selectable or preemptive messages.  
5. During Run, the Run/Test Switch, when placed in the  
TEST position, drives the firing rate motor to the Low  
Fire position.  
A selectable message supplies information for flame strength,  
system status indication, system or self-diagnostics and  
troubleshooting.  
NOTE: When RM7800/RM7840 is switched to the Test  
mode, it stops and holds at the next Run/Test Switch  
point in the operating sequence. Make sure that the  
Run/Test Switch is in the RUN position before  
leaving the installation.  
A preemptive message has parentheses around the message  
and supplies a detailed message to support the sequence  
status information. A preemptive message can also be a  
lockout message. A preemptive message replaces a  
selectable message to support the sequence status  
information. It also replaces a selectable message after 60  
seconds if it or a lockout message is available.  
SETTINGS AND ADJUSTMENTS  
Selectable Site-Configurable  
Jumpers  
Run/Test Switch  
The RM7800/RM7840 has three site-configurable jumper  
options, see Fig. 6 and Table 7. If necessary, clip the  
site-configurable jumpers with side cutters and remove the  
resistors from the Relay Module.  
WARNING  
Explosion Hazard.  
Can cause serious injury or death.  
Do not use the Run/Test switch during the Pilot Flame  
Establishing Period for the RM7800/RM7840G,M  
when using Direct Spark Function, because it turns on  
the main gas valve, causing an accumulation of fuel in  
the burner.  
SELECTABLE CONFIGURATION JUMPERS  
RUN/TEST SWITCH  
The Run/Test Switch is located on the top side of the  
RM7800/RM7840, see Fig. 6. The Run/Test Switch allows the  
burner sequence to be altered as follows:  
1. In Prepurge Drive To High Fire Position, the Run/Test  
Switch, when placed in the TEST position, holds in  
PREPURGE with the firing rate motor in the High Fire  
position.  
2. In the measured PREPURGE sequence, the Run/Test  
Switch, when placed in the TEST position, causes the  
PREPURGE timing to stop. The firing rate motor is in  
the High Fire position.  
3. In Prepurge Drive to Low Fire position, the Run/Test  
Switch, when placed in the TEST position, holds the  
burner sequence in PREPURGE with the firing rate  
motor in the Low Fire position.  
4. In PFEP, the Run/Test Switch, when placed in the TEST  
position, stops the timer during the first eight seconds  
when a ten second PFEP is selected or during the first  
three seconds when a four second PFEP is selected,  
NOTE: CONFIGURATION JUMPERS SHOWN FOR RM7800G/RM7840G.  
M12301  
Fig. 6. Selectable site-configurable jumpers.  
13  
66-1085—04  
 
RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES  
Table 7. Site Configurable Jumper Options.  
Description Intact Clipped  
10 seconds  
Jumper Number  
JR1  
RM7800/RM7840 Type  
Pilot Flame Establishing  
Period (PFEP)  
4 seconds  
All  
a
b
JR2  
10 seconds  
Intermittent  
RM7800G/RM7840G  
All  
Pilot Valve /Main Flame  
15 or 30 seconds Interrupted  
Establishing Period (MFEP)  
JR3  
Start-up Interlock Check  
Disabled  
Enabled  
a
b
Pilot Valve /First Stage Oil Valve (Valve/Start) Terminal 21.  
A 30 second MFEP can be accomplished by adding a jumper wire between Terminals 19 and 5.  
SERVICE NOTE:Clipping and removing a site-configurable jumper enhances the level of safety. Removal after 200 hours of  
main valve operation will result in a hard lockout, Code 110.  
Equipment Recommended  
STATIC CHECKOUT  
1. Voltmeter (1M ohm/volt minimum sensitivity) set on the  
0-300 Vac scale.  
After checking all wiring, perform this checkout before  
installing the RM7800/RM7840 on the subbase. These tests  
verify the Q7800 Wiring Subbase is wired correctly, and the  
external controllers, limits, interlocks, actuators, valves,  
transformers, motors and other devices are operating  
properly.  
2. Two jumper wires; no. 14 wire, insulated, 12 inches  
(304.8 mm) long with insulated alligator clips at both  
ends. An ammeter may be used in place of a jumper  
wire to check the amp usage when testing the blower  
motor, ignition, pilot and main valve operation.  
General Instructions  
WARNING  
1. Perform all applicable tests listed in Static Checkout,  
Table 8, in the order listed.  
Explosion and Electrical Shock Hazard.  
Can cause serious injury, death or equipment  
damage.  
2. Make sure all manual fuel shutoff valve(s) are closed.  
3. Perform only those tests designated for the specific  
RM7800/RM7840 model being tested.  
4. Raise the setpoint of the operating controller to simulate  
a call for heat.  
5. For each test, open the master switch and install the  
jumper wire(s) between the subbase wiring terminals  
listed in the Test Jumpers column.  
6. Close the master switch before observing operation.  
7. Read the voltage between the subbase wiring terminals  
listed in the Voltmeter column.  
1. Close all manual fuel shutoff valve(s) before starting  
these tests.  
2. Use extreme care while testing the system. Line  
voltage is present on most terminal connections  
when power is on.  
3. Open the master switch before installing or  
removing a jumper on the subbase.  
4. Before continuing to the next test, be sure to  
remove test jumper(s) used in the previous test.  
5. Replace all limits and interlocks that are not  
operating properly. Do not bypass limits and  
interlocks.  
8. If there is no voltage or the operation is abnormal, check  
the circuits and external devices as described in the last  
column.  
9. Check all wiring for correct connections, tight terminal  
screws, correct wire, and proper wiring techniques.  
Replace all damaged or incorrectly sized wires.  
10. Replace faulty controllers, limits, interlocks, actuators,  
valves, transformers, motors and other devices as  
required.  
11. Make sure normal operation is obtained for each  
required test before continuing the checkout.  
12. After completing each test, be sure to remove the test  
jumper(s).  
CAUTION  
Equipment Damage Hazard.  
Improper testing can damage equipment.  
Internal surge protectors can break down and conduct  
a current, causing the RM7800/RM7840 to fail the  
dielectric test or possibly destroy the internal lightning  
and high current protection. Do not perform a dielectric  
test with the RM7800/RM7840 installed.  
WARNING  
Explosion Hazard.  
Can cause serious injury or death.  
Make sure all manual fuel shutoff valves are closed  
before performing static checkout.  
66-1085—04  
14  
 
RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES  
Table 8. Static Checkout.  
RM7800/  
RM7840  
Models  
Test  
No.  
Test  
If Operation is Abnormal,  
Check the Items Listed Below  
Jumpers Voltmeter  
Normal Operation  
1
2
All  
None  
4-L2  
Line voltage at Terminal 4.  
1. Master Switch.  
2. Power connected to the Master Switch.  
3. Overload protection (fuse, circuit breaker,  
etc.) has not opened the power line.  
6-L2  
Line voltage at Terminal 6.  
Line voltage at Terminal 20.  
1. Limits.  
2. Burner Controller.  
3
4
20-L2  
7-L2  
1. Preignition interlocks.  
4-5  
1. Burner motor (fan or  
blower) starts.  
2. Line voltage at Terminal  
7 within 10 seconds.  
1. Burner motor circuit.  
a. Manual switch of burner motor.  
b. Burner motor power supply, overload  
protection, and starter.  
c. Burner motor.  
2. Running or Lockout Interlocks (including  
Airflow Switch).  
5
6
4-10  
4-8  
Ignition spark (if ignition  
transformer is connected to  
Terminal 10)  
1. Watch for spark or listen for buzz.  
a. Ignition electrodes are clean.  
b. Ignition transformer is okay.  
All  
1. Ignition spark (if ignition  
transformer is connected to  
Terminal 8).  
2. Automatic pilot valve opens (if  
connected to Terminal 8).  
1. Watch for spark or listen for buzz.  
a. Ignition electrodes are clean.  
b. Ignition transformer is okay.  
2. Listen for click or feel head of valve for  
activation.  
a. Actuator if used.  
b. Pilot valve.  
NOTE: Refer to wiring diagram of  
system being tested.  
7
8
4-21  
4-9  
Same as test no. 6 for connections Same as test no. 6. If using direct spark  
to Terminal 8. If using direct spark ignition, check the first stage fuel valve(s)  
ignition, check the first stage fuel  
valve(s) instead of the pilot valve.  
instead of the pilot valve.  
Automatic main fuel valve(s) open. 1. Listen for and observe operation of the  
If using direct spark ignition on a  
model with intermittent pilot on  
Terminal 21, check the optional  
second stage fuel valve, if used.  
main  
fuel valve(s) and actuator(s).  
2. Valve(s) and actuator(s).  
1. Alarm.  
9
4-3  
Alarm (if used) turns on.  
10  
11  
12  
13  
14  
RM7800E,G,L; 4-5  
RM7840E,G,L and  
18-L2  
Firing rate motor drives open; zero 1. Low Fire Start Switch.  
volts at Terminal 18 after motor  
starts driving open.  
2. Firing rate motor and transformer.  
12-13  
RM7800E,G,L; 4-5  
RM7840E,G,L and  
18-L2  
19-L2  
19-L2  
Firing rate motor drives closed; line 1. Low Fire Start Switch.  
voltage at Terminal 18 after motor 2. Firing rate motor and transformer.  
is in Low Fire position.  
14-13  
RM7800E,L;  
RM7840E,L  
4-5  
and  
12-13  
Firing rate motor drives open; line 1. High Fire Purge Switch.  
voltage at Terminal 19 after motor 2. Firing rate motor and transformer.  
is in High Fire position.  
RM7800E,L;  
RM7840E,L  
4-5  
and  
14-13  
Firing rate motor drives closed;  
zero volts at Terminal 19 after  
motor starts driving closed.  
1. Low Fire Start Switch.  
2. Firing rate motor and transformer.  
RM7800E,G,L; 15-13  
RM7840E,G,L  
1. Raise setpoint of Series 90  
controller—firing rate motor  
should drive toward open.  
2. Lower setpoint of Series 90  
controller—firing rate motor  
should drive toward closed.  
1. Series 90 Controller.  
2. Firing rate motor and transformer.  
15  
66-1085—04  
 
RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES  
Table 8. Static Checkout. (Continued)  
RM7800/  
RM7840  
Models  
Test  
No.  
Test  
If Operation is Abnormal,  
Check the Items Listed Below  
Jumpers Voltmeter  
Normal Operation  
15  
RM7800M;  
14-13  
If damper motor is used, motor  
drives damper open.  
Damper motor.  
RM7840M with  
open damper  
contacts..  
16  
17  
RM7800M;  
4-5  
18-L2  
18-L2  
If damper motor is used, motor  
drives open; line voltage at  
Terminal 18 after motor is in Low  
Fire position.  
1. Low Fire Start Switch.  
2. Damper motor.  
RM7840M with  
open damper  
contacts..  
RM7800M;  
4-5  
If damper motor is used, motor  
drives open; zero volts at  
Terminal 18.  
1. Low Fire Start Switch.  
2. Damper motor.  
RM7840M with and  
open damper 4-13  
contacts..  
Final All  
CAUTION  
Equipment Damage Hazard.  
Improper wiring can damage equipment.  
On completing these tests, open the master switch and remove all test jumpers from the  
subbase terminal. Also remove bypass jumpers from the low fuel pressure limits (if used) to  
prevent equipment damage.  
Automation and Control Solutions  
Honeywell International Inc.  
1985 Douglas Drive North  
Golden Valley, MN 55422  
Honeywell Limited-Honeywell Limitée  
35 Dynamic Drive  
® U.S. Registered Trademark  
© 2010 Honeywell International Inc.  
66-1085—04 M.S. Rev. 09-10  
Printed in U.S.A.  
Toronto, Ontario M1V 4Z9  
customer.honeywell.com  
 

Graco High Chair 3645 User Manual
Grizzly Impact Driver H8000 User Manual
Grundig Flat Panel Television 40 VLE 555 BG User Manual
Hamilton Watch Watch Khaki Navy Frogman User Manual
Harbor Freight Tools Automobile Parts 98480 User Manual
Honeywell Humidifier HE365A User Manual
Hotpoint Freezer FZ175X User Manual
HP Hewlett Packard Digital Camera M730 Series User Manual
Humminbird Marine GPS System 409380 1 User Manual
iLive Bluetooth Headset IAB13B User Manual