574D- -A AND 577C- -A
LEGACYt AND PREFERREDt 13 AND 14 SEER
SINGLE-PACKAGED AIR CONDITIONER AND GAS FURNACE SYSTEM
WITH PURON (R-410A) REFRIGERANT SINGLE AND THREE PHASE
2-5 NOMINAL TONS (SIZES 24-60)
Owner’s Information Manual
A09033
A09034
577C--A Without Economizer
574D----A Without Economizer
A10078
A10077
577C--A With Economizer
Fig. 2 -- Unit 577C--A
574D----A With Economizer
Fig. 1 -- Unit 574D--A
1
SAFETY CONSIDERATIONS
!
WARNING
Improper installation, adjustment, alteration, service maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory--authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
FIRE AND EXPLOSION HAZARD
What to do if you smell gas:
1. Do not try to light any appliance.
2. Do not touch any electrical switch; do not use any phone
in your building.
3. Leave the building immediately.
4. Immediately call your gas supplier from a nearby phone.
Follow the gas supplier’s instructions.
5. If you cannot reach your gas supplier, call the fire
department.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Have a fire extinguisher available. Read these
instructions thoroughly and follow all warnings or cautions
included in literature and attached to the unit. consult local
building codes, the current editions of the National Fuel Gas Code
(NFGC) NFPA 54/ANSI Z223.1, and the National Electrical Code
(NEC) NFPA 70.
!
WARNING
In Canada refer to the current editions of the National Standards of
Canada CAN/CSA--B149.1 and .2 Natural Gas and Propane
Installation codes, and Canadian Electrical Code CSA C22.1
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury and/or death.
Recognize safety information. This is the safety--alert symbol
.
Before performing recommended maintenance, be sure the
main power switch to unit is turned off and lock--out tag is
installed.
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury. Understand
these signal words: DANGER, WARNING, and CAUTION. These
words are used with the safety--alert symbol. DANGER identifies
the most serious hazards which will result in severe personal injury
or death. WARNING signifies hazards which could result in
personal injury or death. CAUTION is used to identify unsafe
practices which may result in minor personal injury or product and
property damage. NOTE is used to highlight suggestions which
will result in enhanced installation, reliability, or operation.
!
WARNING
FIRE,
EXPLOSION,
HAZARD
ELECTRICAL
SHOCK
Failure to follow this warning could result in personal
injury, death and/or property damage.
NOTE: Installer: This manual should be left with the equipment
user.
1. Do not turn off the electrical power to unit without first
turning off the gas supply.
2. Before attempting to start the gas heating section,
familiarize yourself with all the procedures that must be
followed.
!
WARNING
FIRE,
EXPLOSION,
ELECTRICAL
SHOCK
HAZARD
Failure to follow this warning could result in personal
injury, death or property damage.
WARNING
FIRE, EXPLOSION HAZARD
!
Installation and servicing of this equipment can be
hazardous due to mechanical and electrical components.
Only trained and qualified personnel should install, repair,
or service this equipment.
Failure to follow this warning could result in personal
injury, death, and/or property damage.
Do not attempt to light by hand.
WARNING
FIRE, EXPLOSION HAZARD
!
!
CAUTION
Failure to follow this warning could result in personal
injury, death, and/or property damage.
CUT HAZARD
Failure to follow this caution may result in personal injury.
Do not store or use combustible materials, gasoline, or other
flammable vapors and liquids in the vicinity of this or any
other appliance.
When removing access panels or performing maintenance
functions inside your unit, be aware of sharp sheet metal
parts and screws. Although special care is taken to reduce
sharp edges to a minimum, be extremely careful when
handling parts or reaching into the unit.
!
WARNING
FIRE,
EXPLOSION,
ELECTRICAL
SHOCK
HAZARD
Failure to follow this warning could result in personal
injury, death or property damage.
Do not use this unit if any part has been under water.
Immediately call a qualified service technician to inspect the
unit and to replace any part of the control system which has
been under water.
3
UNIT INTRODUCTION
WARNING
!
These units are small packaged gas heat/electric cooling system
that can utilize the comfort of gas heating packaged along with
efficient electric air conditioning. This unit uses Puronr, the
ozone friendly refrigerant for cooling.
FIRE AND EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death, and/or property damage.
Starting or Shutting Off Unit
NOTE: Your combination heating/cooling unit is equipped with
an automatic direct spark ignition and power combustion blower.
1. If the main burners fail to light, or the blower fails to
start, shut down gas heating section and call your dealer for
service.
2. Never attempt to manually light the main burners on unit
with a match, lighter, or any other flame. If the electric
sparking device fails to light the main burners, refer to the
following shutdown procedures, then call your dealer as
soon as possible.
To start unit gas heat:
Refer to Fig. 3 for location of unit front access panel. Refer to Fig.
4 for location of gas valve. Refer to Fig. 5 while proceeding with
the following steps.
1. Set the temperature selector on room thermostat to the low-
est temperature setting and set system switch to HEAT.
To shut off unit gas heat:
2. Close the external manual gas shutoff valve.
3. Turn off the electrical supply to the unit.
4. Remove the control access panel with a 5/16--in. nut driver.
(See Fig. 3.)
WARNING
!
FIRE,
HAZARD
EXPLOSION,
ELECTRICAL
SHOCK
5. Move the selector switch on the internal gas valve to the
OFF position and wait 5 minutes.
Failure to follow this warning could result in personal
injury, death, and/or property damage.
6. Move the selector switch on the internal gas valve to the ON
position.
Do not turn off the electrical power to unit without first
turning off the gas supply.
7. Replace the control access panel.
8. Turn on the electrical supply to unit.
9. Open the external manual gas shutoff valve.
NOTE: If the unit is being shut down because of a malfunction,
call your dealer as soon as possible.
10. Set the temperature selector on room thermostat slightly
above room temperature to start unit. The induced--draft
combustion air fan will start. Main gas valve will open and
main burners should ignite within 5 seconds. If the burner
does not light within 5 seconds, the ignition module will go
into a Retry Mode after a period of approximately 22
seconds (following the 5--second ignition period). If the
burners do not light within 15 minutes of the initial call for
heat, there is a lockout.
Should overheating occur or the gas supply fail to shut off, shut
off the external manual gas valve to the unit before shutting off
the electrical supply. Do not use this unit if any part has been under
water. Immediately call a qualified service technician to inspect the
unit and to replace any part of the control system and any gas
control which has been under water.
Refer to Fig. 6 while proceeding with the following steps.
11. Set the temperature selector on room thermostat to desired
setting.
1. Set the temperature selector on room thermostat to lowest
temperature setting and set system SWITCH to OFF.
2. Close the external manual shutoff valve.
3. Turn off the electrical power supply to the unit.
4. Remove the control access panel. (See Fig. 3.)
5. Move the selector switch on the internal gas valve to the
OFF position.
6. Replace the control access panel.
To start unit electric cooling:
Refer to Fig. 7 while proceeding with the following steps.
1. Set the temperature selector on room thermostat to highest
temperature setting and set system SWITCH to OFF.
2. Close the external manual shutoff valve, if not already
closed.
3. Turn ON the electrical power supply to the unit.
4. Set system switch to COOL.
Control
Access
Panel
Blower
Access
Panel
Filter Access Panel
For Accessory Filter Rack
Compressor
Access
Panel
5. Set the temperature selector on room thermostat slightly
below the room temperature to start unit.
A09213
To shut off unit electric cooling:
Fig. 3 -- Accessory Filter Rack Access Panel
Refer to Fig. 8 while proceeding with the following steps.
1. Set the temperature selector on room thermostat to highest
temperature setting and set system SWITCH to OFF.
2. Close the external manual shutoff valve. if not already
closed.
3. Turn off the electrical power supply to the unit.
4
Air Filters
OPERATING YOUR UNIT
The air filter(s) should be checked every 3 or 4 weeks and
changed or cleaned whenever it becomes dirty. Dirty filters
produce excessive stress on the blower motor and can cause the
motor to overheat and shut down.
This unit must have air filters in place before it can be operated.
These filters can be located in one of at least two places. In many
applications, the installer will provide return air filter grilles
mounted on the wall or ceiling of the conditioned structure. In the
instance of filter grilles, the filters can simply be removed from the
grille and replaced.
The operation of your unit is controlled by the indoor temperature
control (thermostat). You simply adjust the thermostat and it
maintains the indoor temperature at the level you select. Most
thermostats of heating and cooling systems have 3 controls: a
temperature control selector, a FAN control, and a SYSTEM or
MODE control. Refer to your thermostat owner’s manual for more
information.
To better protect your investment and to eliminate unnecessary
service calls, familiarize yourself with the following facts:
Cooling Mode
The other typical application is an accessory filter rack installed
inside the unit itself. The following information is given to assist in
changing filters used in these internal filter racks.
Table 1 indicates the correct indoor filter size for your unit. Refer
to Fig. 3 to access filters installed in the accessory filter rack. If
using an Accessory Filter Rack, refer to the Installation Instructions
provided with it for correct filter sizes and quantities.
Table 1 – Indoor Air Filter Data
With the SYSTEM control set to COOL, your unit will run in
cooling mode until the indoor temperature is lowered to the level
you have selected. On extremely hot days, your unit will run for
longer periods at a time and have shorter “off” periods than on
moderate days.
Gas Heat Mode
With the SYSTEM or MODE control of your indoor thermostat set
to HEAT, your unit will run in heating mode until room
temperature is raised to the level you have selected. On cold days
and nights, your system will typically run for longer periods of
time and have shorter “off” periods than on moderate days.
Unit Size
A24040
Filter Size
20x20x1 (508x508x25 mm)
20x24x1 (508x610x25 mm)
24x30x1 (610x762x25 mm)
24x36x1 (610x914x25 mm)
A24060, 30
A36 --- A42
A48 --- A60
MAINTENANCE AND SERVICE
This section discusses maintenance that should be performed on
your system. Most maintenance should be performed by your
dealer. You, as the owner, may wish to handle some minor
maintenance for your new unit.
Routine Maintenance
All routine maintenance should be handled by skilled, experienced
personnel. Your dealer can help you establish a standard procedure.
For your safety, keep the unit area clear and free of combustible
materials, gasoline, and other flammable liquids and vapors.
To assure proper functioning of the unit, flow of condenser air
must not be obstructed from reaching the unit. Clearance from the
top of the unit is 48 in. (1219 mm). Clearance of at least 36 in.
(914 mm) is required on sides except the power entry side (42 in.
(1067 mm) clearance) and the duct side (12 in. (305 mm)
minimum clearance). Also, ensure that the return--air duct
connection (s) is physically sound, is sealed to the furnace casing,
and terminates outside the space containing the furnace.
Flue Hood
Burners
Gas Valve
A09043
Maintenance and Care for the Equipment Owner
Fig. 4 -- Gas Heating/Electric Cooling Unit with Access Panel
Removed
Before performing equipment maintenance
carefully consider the following:
yourself, please
To replace or inspect filters in accessory filter rack (See Fig. 3):
1. Remove the filter access panel using a 5/16--in. nut driver.
2. Remove the filter(s) by pulling it out of the unit. If the
filter(s) is dirty, clean or replace with a new one.
When installing the new filter(s), note the direction of the airflow
arrows on the filter frame.
If you have difficulty locating your air filter(s) or have questions
concerning proper filter maintenance, contact your dealer for
instructions. When replacing filters, always use the same size and
type of filter that was supplied originally by the installer.
!
WARNING
FIRE, EXPLOSION, ELECTRICAL SHOCK AND
CUT HAZARD
Failure to follow this warning could result in personal
injury, death or property damage.
1. Turn off gas supply first, then all electrical power to your
unit and install lock--out tag before servicing or per-
forming maintenance.
2. When removing access panels or performing
maintenance functions inside your unit, be aware of
sharp sheet metal parts and screws. Although special care
is taken to reduce sharp edges to a minimum, be
extremely careful when handling parts or reaching into
the unit. Wear safety glasses, gloves, and appropriate
protective clothing.
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in property
damage.
Never operate your unit without filters in place. An
accumulation of dust and lint on internal parts of your unit
can cause loss of efficiency and blower motor and/or
compressor damage.
5
Replacing or inspecting filters in units with econom-
izers
Small Chassis (See Fig. 5)
!
CAUTION
UNIT OPERATION HAZARD
1. Remove return air duct cover at rear of unit using a 5/16--in.
nut driver.
Failure to follow this caution may result in property
damage.
2. Remove the filter(s) by pulling it out and through the unit
duct opening. If filter is dirty, replace both filters with new
ones.
Never operate your unit without filters in place. An
accumulation of dust and lint on internal parts of your unit
can cause loss of efficiency and blower motor and/or
compressor damage.
When installing the new filters, note the direction of the airflow
arrows on the filter frame, which should be pointing at the indoor
coil.
3. Reinstall duct cover ensuring opening is air and watertight.
Table 2 – Indoor Air Filter Data with Economizer
Unit Size
Filter Size
2 each 20 x 12 x 1
30-040/060
(508 x 305 x 25 mm)
2 each 20 x 12 x 1
36-060/090
42-060/090
(508 x 305 x 25 mm)
1 each 24 x 14 x 1 (610 x 356 x 25 mm),
24 x 16 x 1 (610 x 406 x 25 mm)
1 each 24 x 14 x 1 (610 x 356 x 25 mm),
24 x 16 x 1 (610 x 406 x 25 mm)
1 each 24 x 16 x 1 (610 x 406 x 25 mm),
24 x 18 x 1 (610 x 457 x 25 mm)
48-090/115/130
60-090/115/130*
FILTER
ACCESS
PANEL
*Units with bent indoor coil.
LARGE CHASSIS
A10062
Fig. 6 -- Large Chassis Filter Access
Fans and Fan Motors
Periodically check the condition of fan wheels and housings and
fan motor shaft bearings. Contact your dealer for the required
annual maintenance.
Heat Exchanger
To ensure dependable and efficient heating operation, the heat
exchanger should be checked by a qualified maintenance person
before each heating season, and cleaned when necessary. This
checkout should not be attempted by anyone not having the
required expertise and equipment to properly do the job. Contact
your dealer for the required periodic maintenance.
RETURN
DUCT COVER
(Remove for
filter access)
Indoor and Outdoor Coils
SMALL CHASSIS
Cleaning of the coils should only be done by qualified service
personnel. Contact your dealer for the required annual
maintenance.
A10063
Fig. 5 -- Small Chassis Filter Access
Large Chassis (See Fig. 6)
Condensate Drain
1. Remove filter access door using a 5/16--in. nut driver.
The drain pan and condensate drain line should be checked and
cleaned at the same time the cooling coils are checked by your
dealer.
2. Remove the filter(s) by pulling it out and through the unit
filter access door. If filter is dirty, replace both filters with
new ones.
Compressor
Units with bent indoor coils, install 24 x 18 x 1 (610 x 457 x 25
mm) filter first and then install 24 x 16 x 1 (610 x 406 x 25) filter.
All compressors are factory shipped with a normal charge of the
correct type of refrigeration grade oil. A compressor should rarely
require additional oil.
When installing the new filters, note the direction of the airflow
arrows on the filter frame, which should be pointing at the indoor
coil.
3. Reinstall filter access door ensuring opening is air and water
tight.
6
Condenser (Outdoor) Fan
Combustion Area and Vent System
For proper and safe operation, the furnace needs air for combustion
and ventilation. The air openings, on the furnace, the air openings
to the area in which the furnace is installed, and the spacing around
the furnace must not be blocked or obstructed.
WARNING
!
PERSONAL INJURY AND UNIT DAMAGE
HAZARD
The combustion area and vent system should be inspected visually
before each heating season. The normal accumulation of dirt, soot,
rust, and scale can result in loss of efficiency and improper
performance if allowed to build up. This inspection should be done
by a trained service person.
Failure to follow this warning could result in personal
injury, death or property damage.
Do not insert sticks, screwdrivers, or any other objects into
revolving fan blades.
!
WARNING
The fan must be kept free of all obstructions to ensure proper
cooling. Contact your dealer for any required service.
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
Electrical Controls and Wiring
Electrical controls are difficult to check without proper
instrumentation. If there are any discrepancies in the operating
cycle, contact your local dealer and request service.
If your unit makes an especially loud noise when the main
burners are ignited, shut down the heating section and call
your dealer.
Refrigerant Circuit
The refrigerant circuit is difficult to check for leaks without the
proper equipment. If inadequate cooling is suspected, contact your
local dealer for service.
!
CAUTION
BURN HAZARD
!
WARNING
Failure to follow this caution may result in personal injury.
Components in heating section may be hot after unit has
been started up. When observing flame, be careful not to get
close to or touch heating components.
EXPLOSION AND ENVIRONMENTAL HAZARD
Failure to follow this warning could result in personal
injury, death or property damage.
System under pressure. Relieve pressure and recover all
refrigerant before system repair or final unit disposal. Use
all service ports and open all flow--control devices,
including solenoid valves.
Regular Dealer Maintenance
In addition to the type of routine maintenance you might be willing
to perform, your unit should be inspected regularly by a properly
trained service technician. An inspection (preferably each year, but
at least every other year) should include the following:
Unit Panels
1. Inspection of all flue product passages--including the burn-
ers, heat exchanger, and flue collector box, Mare sure the
burner flames are blue in color and in proper adjustment.
Refer to Fig. 9 for burner flame.
After performing any maintenance or service on the unit, be sure
all panels are fastened securely in place to prevent rain from
entering unit cabinet and to prevent disruption of the correct unit
airflow pattern.
2. Inspection of all combustion--and ventilation--air passages
and openings.
3. Close inspection of all gas pipes leading to and inside of
your unit.
4. Inspection and, if required, cleaning of the outdoor and
indoor coils.
5. Inspection and, if required, cleaning of the indoor coil con-
densate drain pan.
7
MAIN
ON
55
OFF
STEP 1
STEP 2
STEP 3
STEP 5
STEP 4
STEP 6
STEP 7
MAIN
ON
72
OFF
STEP 8
STEP 9
STEP 10
A07662
Fig. 7 -- To Start Unit Gas Heat
8
MAIN
ON
55
OFF
STEP 1
STEP 2
STEP 3
STEP 4
STEP 5
STEP 6
A07663
Fig. 8 -- To Shut--off Unit Gas Heat
MAIN
ON
72
90
OFF
STEP 4 & 5
STEP 2
STEP 1
STEP 3
A09194
Fig. 9 -- To Start Unit Electric Cooling
9
MAIN
ON
90
OFF
STEP 1
STEP 2
STEP 3
A07797
Fig. 10 -- To Shut--off Unit Electric Cooling
BURNER FLAME
Warranty Certificate
Your unit has a limited warranty. Be sure to read the warranty
carefully to determine the coverage for your unit.
BURNER
Before you call for service...
...check for several easily--solved problems.
If insufficient heating or cooling is suspected:
(
) Check for sufficient airflow. Check the air filter for dirt. Check
for blocked return--air or supply--air grilles. Be sure they are open
and unobstructed. If these checks do not reveal the cause, call your
servicing dealer.
MANIFOLD
If your unit is not operating at all, check the following list for
easy solutions:
(
) Check to be sure that your thermostat temperature selector is
C99021
set below the indoor temperature during the cooling season or
above the indoor temperature during heating season. Be sure the
SYSTEM switch or MODE control is in the COOL or HEAT
position and not in the OFF position.
Fig. 11 -- Monoport Burner
6. Inspection and cleaning of blower wheel housing and
motor.
(
) If your unit still fails to operate, call your servicing dealer for
7. Inspection of all supply--air and return--air ducts for leaks,
obstructions, and insulation integrity. Any problems found
should be resolved at this time.
8. Inspection of the unit base to ensure that no cracks, gaps,
etc., exist which may cause a hazardous condition.
troubleshooting and repairs. Specify the model and serial numbers
of your unit. (Record them in this manual in the space provided.) If
the dealer knows exactly which unit you have, he may be able to
offer suggestions over the phone, or save valuable time through
knowledgeable preparation for the service call.
In Case of Trouble
9. Inspection of the unit casing for signs of deterioration.
If you perform the steps above and unit performance is still
unsatisfactory, shut off the unit and call your dealer.
10. Inspection of all electrical wiring and components to assure
proper connection.
11. Inspection for leaks in the refrigerant circuit. Pressure
check to determine appropriate refrigerant charge.
12. Operational check of the unit to determine working
conditions. Repair or adjustment should be made at this
time.
Your servicing dealer may offer an economical service contract that
covers seasonal inspections. Ask for further details.
Complete service instructions can be found in the unit Installation,
Start--up and Service Instructions.
Heating & Cooling Systems
TO OBTAIN INFORMATION ON PARTS: Consult your installing dealer or classified section of your local telephone directory under the
“Heating Equipment” or “Air Conditioning Contractors & Systems” heading for dealer listing by brand name.
Have available the Model No., Series Letter, & Serial No. of your equipment to ensure correct replacement part.
Edition Date: 04/10
Catalog No: OM574D---577C---03
Copyright 2010 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indianapolis, IN 46231
Replaces: OM574D---577C---02
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
10
|