ROOMTOP®
50AH024-096
Horizontal Indoor Single-Package Cooling Units
with PURON® Refrigerant (R-410A)
Installation, Start-Up, and
Service Instructions
system. If unit is split, the condensing section must be mounted
horizontally.
All units are designed to be ducted on both the condenser
and evaporator sides. Centrifugal blowers are used to ensure
quiet air delivery to the conditioned space. Sound level
requirements should be determined before final unit installa-
tion site is chosen.
Unit servicing is relatively simple since access to the con-
denser and evaporator motors, blowers, belt, and pulley is
gained through access panels located on the sides of the unit.
These panels may also be used for cleaning of condenser coils.
Unit side panels also provide access to control box and pres-
sure switches.
Refrigeration cycle components (e.g., compressor, filter
drier, etc.) can be serviced upon removal of the base unit from
the space.
CONTENTS
SAFETY CONSIDERATIONS. . . . . . . . . . . . . . . . . . . . . . 1
GENERAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-17
Step 1 — Receive and Inspect Unit. . . . . . . . . . . . . . . 1
Step 2 — Protect Unit from Damage. . . . . . . . . . . . . . 1
Step 3 — Provide Unit Support. . . . . . . . . . . . . . . . . . . 1
Step 4 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . 8
Step 5 — Make Condensate Piping
Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Step 6 — Install Ductwork. . . . . . . . . . . . . . . . . . . . . . . . 8
Step 7 — Split Systems (Factory Option,
if Required). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Step 8 — Make Electrical Connections . . . . . . . . . . 10
• FIELD CONTROL WIRING
• THERMOSTAT WIRE
Step 9 — Adjust Fan Speed . . . . . . . . . . . . . . . . . . . . . 10
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17,18
INSTALLATION
WARNING
Determine building alterations required to run piping, wir-
ing, and ductwork. Follow dimensional drawings carefully
for ductwork, piping locations, electrical wiring, and over-
all unit dimensions. Read all installation instructions before
starting installation.
SAFETY CONSIDERATIONS
Installing and servicing air-conditioning equipment can be
hazardous due to system pressure and electrical components.
Only trained and qualified service personnel should install,
repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func-
tions such as cleaning coils and filters and replacing filters. All
other operations should be performed by trained service per-
sonnel. When working on air-conditioning equipment, observe
precautions in the literature and on tags and labels attached to
unit.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguisher available.
The 50AH units are intended for indoor installation only.
Step 1 — Receive and Inspect Unit — Unpack and
check unit against shipping order. See Fig. 1 for model number
nomenclature. Inspect carefully for concealed shipping dam-
age. If unit is damaged or incomplete, file claim with transpor-
tation company and advise Carrier immediately.
Step 2 — Protect Unit from Damage — To main-
tain warranty, unit must be protected against theft and vandal-
ism and stored indoors at all times.
WARNING
Step 3 — Provide Unit Support — Refer to Fig. 2-5
for unit dimensions. Refer to Table 1 for unit sizes and weights.
Disconnect all power to the unit before performing mainte-
nance or service. Electrical shock and personal injury could
result.
Each unit requires the following field-supplied items:
8 — threaded suspension rods (3/8-in.-16 SAE Grade 1
minimum), 4 additional rods are needed if the unit
has a factory-installed air-side economizer
8 — washers
NOTE: Ensure voltage on unit agrees with voltage listed on
the unit rating plate.
8 — locknuts
GENERAL
Install the 8 field-supplied rods by suspending them from a
suitable ceiling support. Locate rods to mate with 8 outside cor-
ner rigging holes shown in Fig. 2-5. Unit center of gravity is
shown in Fig. 6.
The ceiling and ceiling supports of existing buildings may
require reinforcements; follow all applicable codes.
The 50AH024-096 units are single-package, indoor, hori-
zontally mounted air conditioners of 2 to 8 tons capacity. The
50AH units are ASHRAE (American Society of Heating, Re-
frigerating and Air Conditioning Engineers) 90.1 compliant.
These units can be mounted as factory-shipped single-
package units or can be separated and mounted as a split
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500057-01 Printed in U.S.A. Form 50AH-14SI Pg 1 5-10 Replaces: 50AH-12SI
a50-8547
3
a50-8548
4
a50-8549
5
a50-8550
6
CENTER OF GRAVITY
DIMENSIONS (in.)
UNIT 50AH
A
B
024
036
048
060
072
096
29.0
28.8
29.0
28.8
59.3
60.0
25.6
26.0
27.0
26.8
31.2
31.5
NOTE: Fasten threaded rods through holes in end frames as shown.
Use 4 rods on each side of unit for a total of 8.
CAUTION
All panels must be in place when rigging.
Fig. 6 — Rigging Details
Table 1 — Physical Data
UNIT 50AH
024
036
048
OPERATING WEIGHT (lb)
Base Unit
Evaporator/Condenser Sections
903
399/484
910
401/489
952
417/515
SHIPPING WEIGHT (lb)*
REFRIGERANT TYPE
Operating Charge (lb-oz)†
1036
4-5
1043
R-410A
4-5
1085
8-8
COMPRESSOR — TYPE
Quantity...Model
Oil (oz)
Scroll
1...ZP31K5E
25
1...ZP20K5E
25
1...ZP38K5E
42
HPS Setting (psig)
Cutout
650
7
Reset
Manual Reset
LPS Setting (psig)
Cutout
75
100
7
7
Reset
CONDENSATE DRAIN CONNECTION
Size (in.)...Type
7/8...OD
CONDENSER COIL
Size (L x H) (in.)
Number of Rows...Fins/in.
Copper Tubes — Aluminum Fins
40 x 30
4...14
40 x 30
4...14
90 x 30
2...12
CONDENSER FAN
Nominal Cfm
Blower Size (in.)
Motor Hp (Rpm)
Standard Motor
Upgrade 1 Motor
Upgrade 2 Motor
Centrifugal — Belt Drive
1700
2000
2500
15 x15
15 x 15
15 x 15
0.33 (1725)
0.33 (1725)
0.33 (1725)
0.50 (1725)
0.75 (1725)
—
—
—
—
EVAPORATOR COIL
Size (L x H) (in.)
Number of Rows...Fins/in.
Copper Tubes — Aluminum Fins
32 x 16
3...12
32 x 16
3...12
32 x 26
3...14
EVAPORATOR AIR FAN
Nominal Cfm
Centrifugal — Belt Drive
800
1200
1600
Blower Size (in.)
Motor Hp (Rpm)
Standard Motor
Upgrade 1 Motor
Upgrade 2 Motor
Upgrade 3 Motor
12 x 9
12 x 9
12 x 9
0.25 (1725)
0.33 (1725)
0.50 (1725)
—
0.33 (1725)
0.50 (1725)
0.75 (1725)
1.00 (1725)
0.33 (1725)
0.50 (1725)
0.75 (1725)
1.00 (1725)
INDOOR-AIR FILTERS
Number...Size (in.)
Factory-Supplied Disposable Type
2...18 x 24 x 1
2...18 x 24 x 1
2...18 x 24 x 1
INTERCONNECTING TUBING SIZE
Suction (Qty...in.)
Liquid (Qty...in.)
1...5/8
1...3/8
1...5/8
1...3/8
1...7/8
1...3/8
LEGEND
HPS — High-Pressure Switch
LPS — Low-Pressure Switch
NOTE: If components are to be split, the maximum length of refrigerant
tubing to be used is 50 equivalent ft, assuming components will be
installed in same horizontal plane. If components are not to be installed
in same horizontal plane, contact your Carrier representative for more
information. For additional piping information, refer to Carrier System
Design Manual, Part 3.
*Shipping weights include base unit plus packaging.
†If components are to be split, additional refrigerant will be needed.
7
Table 1 — Physical Data (cont)
UNIT 50AH
060
072
096
OPERATING WEIGHT (lb)
Base Unit
Evaporator/Condenser Sections
960
421/519
1214
554/634
1283
556/701
SHIPPING WEIGHT (lb)*
1093
1647
1716
REFRIGERANT TYPE
Operating Charge (lb-oz)†
R-410A
6-6
8-8
6-6
COMPRESSOR — TYPE
Quantity...Model
Oil (oz)
Scroll
2...ZP31K5E
25
1...ZPKP51K5E
42
2...ZP38K5E
42
HPS Setting (psig)
Cutout
650
7
Reset
Manual Reset
LPS Setting (psig)
Cutout
75
100
7
7
Reset
CONDENSATE DRAIN CONNECTION
Size (in.)...Type
7/8...OD
CONDENSER COIL
Size (L x H) (in.)
Number of Rows...Fins/in.
Copper Tubes — Aluminum Fins
40 x 30 (2 coils)
90 x 30
2...12
40 x 30 (2 coils)
2...20
2...20
CONDENSER FAN
Nominal Cfm
Blower Size (in.)
Motor Hp (Rpm)
Standard Motor
Upgrade 1 Motor
Upgrade 2 Motor
Centrifugal — Belt Drive
3000
5200
6400
15 x 15
18 x 18
18 x 18
0.33 (1725)
0.50 (1725)
0.75 (1725)
1.00 (1725)
1.50 (1725)
—
1.50 (1725)
2.00 (1725)
3.00 (1725)
EVAPORATOR COIL
Size (L x H) (in.)
Number of Rows...Fins/in.
Copper Tubes — Aluminum Fins
32 x 26
3...14
46 x 28
46 x 28
3...14
3...14
EVAPORATOR AIR FAN
Nominal Cfm
Centrifugal — Belt Drive
2000
2400
3200
Blower Size (in.)
Motor Hp (Rpm)
Standard Motor
Upgrade 1 Motor
Upgrade 2 Motor
Upgrade 3 Motor
12 x 9
15 x 15
15 x 15
0.33 (1725)
0.50 (1725)
0.75 (1725)
1.00 (1725)
0.50 (1725)
0.75 (1725)
1.00 (1725)
1.50 (1725)
0.75 (1725)
1.00 (1725)
1.50 (1725)
2.00 (1725)
INDOOR-AIR FILTERS
Number...Size (in.)
Factory-Supplied Disposable Type
2...18 x 24 x 1
2...20 x 25 x 1
2...20 x 25 x 1
INTERCONNECTING TUBING SIZE
Suction (Qty...in.)
Liquid (Qty...in.)
1...7/8
1...3/8
1...5/8
1...3/8
1...7/8
1...7/8
LEGEND
HPS — High-Pressure Switch
LPS — Low-Pressure Switch
NOTE: If components are to be split, the maximum length of refrigerant
tubing to be used is 50 equivalent ft, assuming components will be
installed in same horizontal plane. If components are not to be installed
in same horizontal plane, contact your Carrier representative for more
information. For additional piping information, refer to Carrier System
Design Manual, Part 3.
*Shipping weights include base unit plus packaging.
†If components are to be split, additional refrigerant will be needed.
Step 4 — Rig and Place Unit — Move and store unit
in horizontal position. Provide space around unit for service,
filter access, ductwork, and overhead clearance as indicated in
Fig. 2-5.
Step 6 — Install Ductwork — Use flexible ductwork
to attach duct to unit and to help control transmission of vibra-
tions to building structures. Attach ductwork to the return and
supply ends of both coils.
Using suitable hydraulic lift source, raise unit up to meet
bottom of the 8 threaded rods suspended from ceiling (12 rods
for units with air-side economizer). Center unit so that the 8 or
12 threaded rods can be easily inserted into the factory-drilled
holes at each end. Refer to Fig. 6 for rigging details.
Apply washers and locknuts on ends of each of the 8 or 12
rods.
If unit is located with condenser close to outside of building,
install a field-supplied rainhood. Hood intake dimensions
should be same as condenser return-air dimensions. In addi-
tion, install a triple-layer bird screen over rainhood intake to
eliminate possibility of insects, birds, water, or debris from
entering unit. Ensure hood and/or louvers are installed correct-
ly to avoid condenser air recirculation.
Tighten locknuts sufficiently so that unit weight is support-
ed entirely by the 8 or 12 rods. Level unit within the space by
adjusting locknuts.
Step 7 — Split Systems (Factory Option, if
Required) — The Roomtop® 50AH units may be split into
2 sections, if desired, with condensing section mounted
remotely horizontally. The unit must be ordered with the
“Splittable” cabinet type as shown in the unit model number
nomenclature. See Fig. 1. All splittable units come with the
interconnecting tubing kit.
Sections installed in the same horizontal plane may be sepa-
rated by up to 50 equivalent ft of tubing. Use type L copper or
better.
IMPORTANT: Unit must be level to operate properly.
NOTE: For split systems, 8 (or 12) suspension rods are
required (4 for each section and 4 for economizer if required).
Refer to Splitting Systems section below.
Step 5 — Make Condensate Piping Connec-
7
tions — One /8-in. OD pipe thread condensate drain con-
nection is provided for the evaporator section.
8
Condensing section must be located in same plane as, or
above, evaporator section to maintain the liquid refrigerant seal
at the expansion device. This permits expansion device to feed
liquid refrigerant to evaporator coil properly. To split sections
(some of the following steps may be eliminated depending on
particular application):
Perform the following procedure:
1. For condensing section, hand thread the female halves of
the self-sealing couplings (supplied with the interconnect
tubing kit) onto the male couplings (factory supplied and
installed on the condensing section). Turn union nut ap-
proximately 1 to 11/2 turns. This is to make sure that the
interconnecting tubing will be routed and brazed with the
self-sealing couplings in their final proper location, so
that there will be no difficulty when the final coupling as-
sembly is made.
2. For evaporator section, hand thread the male halves of the
self-sealing couplings (supplied with the interconnect
tubing kit) onto the female couplings (factory supplied
and installed on the evaporating section). Turn union nut
approximately 1 to 11/2 turns. This is to make sure that the
interconnecting tubing will be routed and brazed with the
self-sealing couplings in their final proper location, so
that there will be no difficulty when the final coupling as-
sembly is made.
1. Disconnect all electrical power to unit.
2. Remove the 10 size 10 drive screws that hold on the top
tie strap.
3
3. Remove the 8 size /8-in. drive bolts that hold on each
side angle.
4. Control panel access panels are held on with 2 size 10
drive screws for each panel. A standard 50AH024-060
unit has one control panel located in the evaporator sec-
tion. A standard 50AH072 or 096 unit has a control panel
in both the evaporator and condenser sections.
5. Units have resealable fittings. Do not cut refrigerant pip-
ing. See Interconnecting Refrigerant Tubing section be-
low for procedure on installing tubing.
6. Install evaporator and condensing sections in desired
locations.
7. Use sufficient length of refrigerant piping to reconnect
piping cut in previous step. Refer to Carrier System
Design Manual, Part 3, for additional piping data.
3. Run the interconnecting tubing required.
NOTE: Installations may be made with up to 50 ft equiv-
alent line lengths by installing the recommended tube siz-
es and adding the necessary refrigerant. For equivalent
line lengths greater than 50 ft, contact Carrier for line siz-
ing and additional accesories required.
8. Recharge unit with R-410A. See Refrigerant Charge sec-
tion on page 18 for more information.
IMPORTANT: On units with more than one refrig-
erant circuit, be careful not to intermix lines of the
various circuits. If the connections were labeled
before disconnecting the couplings, this should not
be a problem. Half couplings may be removed to
make brazing to the interconnecting tubing more
convenient.
After splitting sections, additional refrigerant must be added
to system to ensure proper refrigerant charge. The amount of
refrigerant to be added depends on length of tubing added to
system and operating temperatures of system. Refer to Carrier
System Design Manual, Chapter 3. Allow unit to operate at
least 10 minutes before adjusting refrigerant charge.
Since standard roomtop unit has negligible line losses, split-
ting the system can increase line loss and decrease system
capacity. Capacity reduction can be determined by referring to
Carrier System Design Manual.
INTERCONNECTING REFRIGERANT TUBING — The
interconnecting tubing kit comes with all factory-optional split-
table units. After the separated sections have been installed, the
interconnecting tubing can be run, using the self-sealing cou-
plings supplied in the interconnect tubing kit (see Fig. 7 and 8).
D
D
A
C
A
B
B
C
C
EVAPORATOR
CONDENSING
SECTION
SECTION
D
D
A
A
C
SELF-SEALING
COUPLING
(FEMALE HALF)
SELF-SEALING
COUPLING
(MALE HALF)
A — Male self-sealing fittings
B — Refrigerant piping between sections
C — Female self-sealing fittings
D — Schrader fittings
a50-8552
SCREWS
Fig. 8 — Tubing Installation
CAUTION
When brazing tubing to the self-sealing couplings, be sure
to use a wet rag, running water bath or chill blocks on the
quick-connects to prevent overheating the valves and dam-
aging the seals.
SELF-SEALING
4. The interconnect tubing kit contains a sufficient number
of Schrader access valves to permit installation of one in
each end of both the liquid and suction lines of the field-
supplied tubing. Each interconnecting line (suction, liq-
uid, hot gas) must have one of the supplied Schrader ac-
cess fittings installed into the field-supplied tubing, how-
ever, for short lengths of tubing, only one Schrader in
each line is necessary. Install the Schrader valve fittings
into the tubing before brazing the couplings onto the ends
a50-8551
FLANGE
Fig. 7 — Self Sealing Coupling
For dual circuits, 2 kits are supplied. It is recommended that
some refrigerant oil be placed on the coupling threads to facili-
tate threading.
9
of the tubing. Use a 1/4-in. hole to mount the valve. Clean
and debur the tubing before doing any brazing to ensure
that no chips or debris are left in the refrigerant circuit.
Remove the Schrader valve cap and core before doing
any brazing.
section is more than 50 ft above the evaporator, consult
Carrier for specific refrigeration components.
Step 8 — Make Electrical Connections — Con-
nect power wiring to junction box located on unit side near
control box access panel. All wiring must comply
with National Electrical Code (NEC) and all local code
requirements.
Operating voltage to compressor must be within voltage
range as indicated on unit nameplate. On 3-phase units, volt-
ages between phases must be balanced within 2% and current
must be balanced within 10%. Contact local power company
for correction of improper voltage or phase imbalance. Unit
failure as a result of operation on improper line voltage or ex-
cessive phase imbalance constitutes abuse and may cause dam-
age to electrical components. Such operation would invalidate
any applicable Carrier warranty.
Install a fused disconnect per NEC. Refer to unit nameplate
and Tables 2A-2L for fuse sizes and wire amperages for all
units.
FIELD CONTROL WIRING — Install a Carrier-approved
accessory thermostat assembly according to installation
instructions provided by thermostat manufacturer. Locate
thermostat assembly on a solid wall in the conditioned space
away from drafts to sense average room temperature.
5. After brazing the tubing to the self-sealing coupling
halves, evacuate each line to 500 microns. Check to make
sure that each line holds a vacuum after removal of the
vacuum pump (indicating no leaks). Add the appropriate
charge of R-410A refrigerant using the Schrader valves.
Refasten male halves to outer back panel of evaporator
section with flanges and screws (if they were removed for
brazing to tubing). Wipe off coupling seals and threaded
surfaces with a clean cloth to prevent the inclusion of dirt
or foreign material into the system. Lubricate rubber seal
and metal seal in the male halves with refrigeration oil.
Thread coupling halves together by hand to ensure proper
mating of threads. Continue to handthread each half-cou-
pling to its mating half until resistance is felt (approxi-
mately 11/2 to 13/4 turns). Complete the connection of the
mating half-couplings with a wrench. The suction line
couplings (size 12) will be totally engaged after an addi-
tional 51/2 to 53/4 turns. The liquid line couplings (size 8)
will be totally engaged after an additional 41/2 to 43/4
turns. Use a backup wrench to prevent the couplings from
twisting.
Using thermostat cable or equivalent single leads of no. 18
AWG (American Wire Gage) colored wire, route cable or wire
from the subbase terminals, up and through connector on unit
side (below power lead junction box) and connect to low-volt-
age terminal block inside the control box.
THERMOSTAT WIRE — Use 18 gage for 0 to 50-ft long
wires and 16 gage for 51 to 75-ft wire lengths.
6. Refrigerant piping must be insulated in accordance with
local codes and/or applicable ASHRAE standards. Insu-
lation exposed to weather must be suitable for outdoor
use. Provide protection from water and shielding from so-
lar radiation as necessary.
7. Add refrigerant to the system to compensate for the addi-
tional interconnecting tubing. The suction line should be
pitched downward to the compressor, sloping approxi-
Step 9 — Adjust Fan Speed — Adjust fan speed to
meet jobsite conditions. Refer to Tables 3 and 4 to determine
fan speed settings. See Service section of this document for
instructions to adjust fan speed.
The evaporator and condenser fan motors on all units are
belt drive.
1
mately /4-in. every 10 ft to facilitate oil return. P-traps
(field supplied) are required for all suction line risers ev-
ery 15 ft. When the evaporator is above the condensing
section, an inverted P-trap should be incorporated as
close as possible to the evaporator (this minimizes flood-
back/oil slugging during the off cycle). If the condensing
Table 2A — Electrical Data — Standard Evaporator Motor with Standard Condenser Motor
FAN MOTORS
VOLTAGE
COMPRESSOR
POWER SUPPLY
Evaporator
(Standard)
Condenser
(Standard)
RANGE
UNIT
50AH
V-PH
(60 Hz)
Min Ckt
Amps
MOCP
Amps
Min
Max
QTY
RLA
LRA
Hp
FLA
Hp
FLA
1
1
024
036
208/230-1
187
254
1
13.5
58.0
/
1.25
/
1.7
19.8
35
4
3
1
1
1
1
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
187
187
414
187
187
414
187
187
414
187
187
414
254
254
508
254
254
508
254
254
508
254
254
508
16.7
10.4
5.8
19.9
13.6
6.1
26.4
16.0
7.8
16.7
10.4
5.8
79.0
73.0
38.0
109.0
83.1
41.0
134
110.0
52.0
79.0
73.0
38.0
/
/
/
/
/
/
/
/
/
/
/
/
1.7
1.3
0.7
1.7
1.3
0.7
1.7
1.3
0.7
2.5
1.8
0.9
/
1.7
1.3
0.7
1.7
1.3
0.7
1.7
1.3
0.7
4.2
3.2
1.6
24.3
15.6
8.6
40
25
15
3
3
3
3
1
1
1
1
2
2
/
3
1
/
3
1
1
1
1
/
28.3
19.6
8.9
50
35
15
3
3
3
3
1
048
060
/
3
1
/
3
1
1
1
1
/
36.4
22.6
11.1
65
40
20
3
3
3
3
1
/
3
1
/
3
1
1
1
1
1
1
1 1/2
1 1/2
1 1/2
44.3
28.4
15.6
60
40
20
2
2
2
072*
096*
3
3
3
208/230-1
208/230-3
460-3
187
187
414
254
254
508
19.9
13.6
6.1
109.0
83.1
41.0
/
/
/
3.2
2.4
1.2
6.5
4.8
2.4
54.5
37.8
17.3
75
50
25
4
4
4
LEGEND
HACR — Heating, Air Conditioning, and Refrigeration
Hp
— Horsepower
FLA
LRA
— Full Load Amps
— Locked Rotor Amps
MOCP — Maximum Overcurrent Protection (HACR breaker)
RLA
— Rated Load Amps
*Unit has two compressors.
10
Table 2B — Electrical Data — Upgrade 1 Evaporator Motor with Standard Condenser Motor
FAN MOTORS
VOLTAGE
COMPRESSOR
POWER SUPPLY
Evaporator
(Upgrade 1)
Condenser
(Standard)
RANGE
UNIT
50AH
V-PH
(60 Hz)
Min Ckt
Amps
MOCP
Amps
Min
Max
QTY
RLA
LRA
Hp
FLA
Hp
FLA
1
1
024
036
208/230-1
187
254
1
13.5
58.0
/
1.7
/
1.7
20.3
35
3
3
1
1
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
187
187
414
187
187
414
187
187
414
187
187
414
254
254
508
254
254
508
254
254
508
254
254
508
16.7
10.4
5.8
19.9
13.6
6.1
26.4
16.0
7.8
16.7
10.4
5.8
79.0
73.0
38.0
109.0
83.1
41.0
134.0
110.0
52.0
79.0
73.0
38.0
/
2.5
1.8
0.9
2.5
1.8
0.9
2.5
1.8
0.9
3.2
2.4
1.2
/
1.7
1.3
0.7
1.7
1.3
0.7
1.7
1.3
0.7
4.2
3.2
1.6
25.1
16.1
8.8
40
25
15
2
3
1
1
1
1
1
2
2
/
/
2
3
1
1
/
/
2
3
1
1
/
/
29.1
20.1
9.2
50
35
15
2
3
1
1
048
060
/
/
2
3
1
1
/
/
2
3
1
1
/
/
37.2
23.1
11.3
65
40
20
2
3
1
1
/
/
2
3
1
1
/
/
2
3
3
/
1
1
1
1 1/2
1 1/2
1 1/2
45.0
29.0
15.9
60
40
20
4
3
072*
096*
/
4
3
/
4
208/230-1
208/230-3
460-3
187
187
414
254
254
508
19.9
13.6
6.1
109.0
83.1
41.0
1
1
1
4.2
3.2
1.6
6.5
4.8
2.4
55.5
38.6
17.7
75
50
25
Table 2C — Electrical Data — Upgrade 2 Evaporator Motor with Standard Condenser Motor
FAN MOTORS
VOLTAGE
COMPRESSOR
POWER SUPPLY
Evaporator
(Upgrade 2)
Condenser
(Standard)
RANGE
UNIT
50AH
V-PH
(60 Hz)
Min Ckt
Amps
MOCP
Amps
Min
Max
QTY
RLA
LRA
Hp
FLA
Hp
FLA
1
1
024
036
208/230-1
187
254
1
13.5
58.0
/
2.5
/
1.7
21.1
35
2
3
3
1
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
187
187
414
187
187
414
187
187
414
187
187
414
254
254
508
254
254
508
254
254
508
254
254
508
16.7
10.4
5.8
19.9
13.6
6.1
26.4
16.0
7.8
16.7
10.4
5.8
79.0
73.0
38.0
109.0
83.1
41.0
134.0
110.0
52.0
79.0
73.0
38.0
/
3.2
2.4
1.2
3.2
2.4
1.2
3.2
2.4
1.2
4.2
3.2
1.6
/
1.7
1.3
0.7
1.7
1.3
0.7
1.7
1.3
0.7
4.2
3.2
1.6
25.8
16.7
9.1
40
25
15
4
3
3
1
1
1
1
2
2
/
/
4
3
3
1
/
/
4
3
3
1
/
/
29.8
20.7
9.5
50
35
15
4
3
3
1
048
060
/
/
4
3
3
1
/
/
4
3
3
1
/
/
37.9
23.7
11.6
65
40
20
4
3
3
1
/
/
4
3
3
1
/
/
4
3
1
1
1
11/2
11/2
11/2
1
1
1
1 1/2
1 1/2
1 1/2
46.0
29.8
16.3
60
40
20
072*
096*
208/230-1
208/230-3
460-3
187
187
414
254
254
508
19.9
13.6
6.1
109.0
83.1
41.0
6.5
4.8
2.4
6.5
4.8
2.4
57.8
40.2
18.5
80
55
25
LEGEND
HACR — Heating, Air Conditioning, and Refrigeration
Hp
— Horsepower
FLA
LRA
— Full Load Amps
— Locked Rotor Amps
MOCP — Maximum Overcurrent Protection (HACR breaker)
RLA
— Rated Load Amps
*Unit has two compressors.
11
Table 2D — Electrical Data — Upgrade 3 Evaporator Motor with Standard Condenser Motor
FAN MOTORS
VOLTAGE
COMPRESSOR
POWER SUPPLY
Evaporator
(Upgrade 3)
Condenser
(Standard)
RANGE
UNIT
50AH
V-PH
(60 Hz)
Min Ckt
Amps
MOCP
Amps
Min
Max
QTY
RLA
LRA
Hp
FLA
Hp
FLA
024
036
208/230-1
187
254
1
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
187
187
414
187
187
414
187
187
414
187
187
414
254
254
508
254
254
508
254
254
508
254
254
508
16.7
10.4
5.8
19.9
13.6
6.1
26.4
16.0
7.8
16.7
10.4
5.8
79.0
73.0
38.0
109.0
83.1
41.0
134.0
110.0
52.0
79.0
73.0
38.0
1
1
1
1
1
1
1
1
1
1 1/2
1 1/2
1 1/2
3.2
2.4
1.2
3.2
2.4
1.2
3.2
2.4
1.2
6.5
4.8
2.4
/
1.7
1.3
0.7
1.7
1.3
0.7
1.7
1.3
0.7
4.2
3.2
1.6
25.8
16.7
9.1
29.8
20.7
9.5
37.9
23.7
11.6
48.3
31.4
17.1
40
25
15
50
35
15
65
40
20
65
40
25
3
1
1
1
1
2
2
/
3
1
/
3
1
/
3
1
048
060
/
3
1
/
3
1
/
3
1
/
3
1
/
3
1
1
1
N/A
1 1/2
1 1/2
072*
096*
208/230-1
208/230-3
460-3
187
187
414
254
254
508
N/A
13.6
6.1
N/A
83.1
41.0
N/A
2
2
N/A
6.0
2.9
N/A
4.8
2.4
N/A
41.4
19.0
N/A
55
25
Table 2E — Electrical Data — Standard Evaporator Motor with Upgrade 1 Condenser Motor
FAN MOTORS
VOLTAGE
COMPRESSOR
POWER SUPPLY
Evaporator
(Standard)
Condenser
(Upgrade 1)
RANGE
UNIT
50AH
V-PH
(60 Hz)
Min Ckt
Amps
MOCP
Amps
Min
Max
QTY
RLA
LRA
Hp
FLA
Hp
FLA
024
036
208/230-1
187
254
1
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
187
187
414
187
187
414
187
187
414
187
187
414
254
254
508
254
254
508
254
254
508
254
254
508
N/A
N/A
N/A
19.9
13.6
6.1
26.4
16.0
7.8
16.7
10.4
5.8
N/A
N/A
N/A
109.0
83.1
41.0
134.0
110.0
52.0
79.0
73.0
38.0
N/A
N/A
N/A
1
N/A
N/A
N/A
1.7
1.3
0.7
1.7
1.3
0.7
2.5
1.8
0.9
N/A
N/A
N/A
1
N/A
N/A
N/A
2.5
1.8
0.9
2.5
1.8
0.9
6.5
4.8
2.4
N/A
N/A
N/A
29.1
20.1
9.2
37.2
23.1
11.3
46.6
30.0
16.4
N/A
N/A
N/A
50
35
15
65
40
20
65
40
20
1
1
1
2
2
/
/
3
2
1
1
048
060
/
/
3
2
1
1
/
/
3
2
1
1
/
/
3
2
1
1
/
/
3
2
1
1
/
/
3
2
1
/
1 1/2
1 1/2
1 1/2
N/A
2
2
2
1
072*
096*
/
2
1
/
2
208/230-1
208/230-3
460-3
187
187
414
254
254
508
N/A
13.6
6.1
N/A
83.1
41.0
N/A
N/A
2.4
1.2
N/A
6.0
2.9
N/A
39.0
17.8
N/A
55
25
3
/
/
4
3
4
LEGEND
HACR — Heating, Air Conditioning, and Refrigeration
Hp
— Horsepower
FLA
LRA
— Full Load Amps
— Locked Rotor Amps
MOCP — Maximum Overcurrent Protection (HACR breaker)
RLA
— Rated Load Amps
*Unit has two compressors.
12
Table 2F — Electrical Data — Upgrade 1 Evaporator Motor with Upgrade 1 Condenser Motor
FAN MOTORS
VOLTAGE
COMPRESSOR
POWER SUPPLY
Evaporator
(Upgrade 1)
Condenser
(Upgrade 1)
RANGE
UNIT
50AH
V-PH
(60 Hz)
Min Ckt
Amps
MOCP
Amps
Min
Max
QTY
RLA
LRA
Hp
FLA
Hp
FLA
024
036
208/230-1
187
254
1
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
187
187
414
187
187
414
187
187
414
187
187
414
254
254
508
254
254
508
254
254
508
254
254
508
N/A
N/A
N/A
19.9
13.6
6.1
26.4
16.0
7.8
16.7
10.4
5.8
N/A
N/A
N/A
109.0
83.1
41.0
134.0
110.0
52.0
79.0
73.0
38.0
N/A
N/A
N/A
1
N/A
N/A
N/A
2.5
1.8
0.9
2.5
1.8
0.9
3.2
2.4
1.2
N/A
N/A
N/A
1
N/A
N/A
N/A
2.5
1.8
0.9
2.5
1.8
0.9
6.5
4.8
2.4
N/A
N/A
N/A
29.9
20.6
9.4
38.0
23.6
11.6
47.3
30.6
16.7
N/A
N/A
N/A
50
35
15
65
40
20
65
40
20
1
1
1
2
2
/
/
2
2
1
1
048
060
/
/
2
2
1
1
/
/
2
2
1
1
/
/
2
2
1
1
/
/
2
2
1
1
/
/
2
2
3
/
1 1/2
1 1/2
1 1/2
N/A
2
2
4
3
072*
096*
/
4
3
/
4
208/230-1
208/230-3
460-3
187
187
414
254
254
508
N/A
13.6
6.1
N/A
83.1
41.0
N/A
1
1
N/A
3.2
1.6
N/A
6.0
2.9
N/A
39.8
18.2
N/A
55
25
Table 2G — Electrical Data — Upgrade 2 Evaporator Motor with Upgrade 1 Condenser Motor
FAN MOTORS
VOLTAGE
COMPRESSOR
POWER SUPPLY
Evaporator
(Upgrade 2)
Condenser
(Upgrade 1)
RANGE
UNIT
50AH
V-PH
(60 Hz)
Min Ckt
Amps
MOCP
Amps
Min
Max
QTY
RLA
LRA
Hp
FLA
Hp
FLA
024
036
208/230-1
187
254
1
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
187
187
414
187
187
414
187
187
414
187
187
414
254
254
508
254
254
508
254
254
508
254
254
508
N/A
N/A
N/A
19.9
13.6
6.1
26.4
16.0
7.8
16.7
10.4
5.8
N/A
N/A
N/A
109.0
83.1
41.0
134.0
110.0
52.0
79.0
73.0
38.0
N/A
N/A
N/A
3
N/A
N/A
N/A
3.2
2.4
1.2
3.2
2.4
1.2
4.2
3.2
1.6
N/A
N/A
N/A
1
N/A
N/A
N/A
2.5
1.8
0.9
2.5
1.8
0.9
6.5
4.8
2.4
N/A
N/A
N/A
30.6
21.2
9.7
38.7
24.2
11.9
48.3
31.4
17.1
N/A
N/A
N/A
50
35
15
65
40
20
65
40
25
1
1
1
2
2
/
/
4
2
3
1
048
060
/
/
4
2
3
1
/
/
4
2
3
1
/
/
4
2
3
1
/
/
4
2
3
1
/
/
4
2
1
1
1
N/A
1 1/2
1 1/2
1 1/2
1 1/2
1 1/2
N/A
2
2
072*
096*
208/230-1
208/230-3
460-3
187
187
414
254
254
508
N/A
13.6
6.1
N/A
83.1
41.0
N/A
4.8
2.4
N/A
6.0
2.9
N/A
41.4
19.0
N/A
55
25
LEGEND
HACR — Heating, Air Conditioning, and Refrigeration
Hp
— Horsepower
FLA
LRA
— Full Load Amps
— Locked Rotor Amps
MOCP — Maximum Overcurrent Protection (HACR breaker)
RLA
— Rated Load Amps
*Unit has two compressors.
13
Table 2H — Electrical Data — Upgrade 3 Evaporator Motor with Upgrade 1 Condenser Motor
FAN MOTORS
VOLTAGE
COMPRESSOR
POWER SUPPLY
Evaporator
(Upgrade 3)
Condenser
(Upgrade 1)
RANGE
UNIT
50AH
V-PH
(60 Hz)
Min Ckt
Amps
MOCP
Amps
Min
Max
QTY
RLA
LRA
Hp
FLA
Hp
FLA
024
036
208/230-1
187
254
1
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
187
187
414
187
187
414
187
187
414
187
187
414
254
254
508
254
254
508
254
254
508
254
254
508
N/A
N/A
N/A
19.9
13.6
6.1
26.4
16.0
7.8
16.7
10.4
5.8
N/A
N/A
N/A
109.0
83.1
41.0
134.0
110.0
52.0
79.0
73.0
38.0
N/A
N/A
N/A
1
1
1
1
1
1
1 1/2
1 1/2
1 1/2
N/A
N/A
N/A
3.2
2.4
1.2
3.2
2.4
1.2
6.5
4.8
2.4
N/A
N/A
N/A
1
N/A
N/A
N/A
2.5
1.8
0.9
2.5
1.8
0.9
6.5
4.8
2.4
N/A
N/A
N/A
30.6
21.2
9.7
38.7
24.2
11.9
50.6
33.0
17.9
N/A
N/A
N/A
50
35
15
65
40
20
65
45
25
1
1
1
2
2
/
2
1
048
060
/
2
1
/
2
1
/
2
1
/
2
1
/
2
1 1/2
1 1/2
1 1/2
N/A
2
2
072*
096*
208/230-1
208/230-3
460-3
187
187
414
254
254
508
N/A
13.6
6.1
N/A
83.1
41.0
N/A
2
2
N/A
6.0
2.9
N/A
6.0
2.9
N/A
42.6
19.5
N/A
55
25
Table 2I — Electrical Data — Standard Evaporator Motor with Upgrade 2 Condenser Motor
FAN MOTORS
VOLTAGE
COMPRESSOR
POWER SUPPLY
Evaporator
(Standard)
Condenser
(Upgrade 2)
RANGE
UNIT
50AH
V-PH
(60 Hz)
Min Ckt
Amps
MOCP
Amps
Min
Max
QTY
RLA
LRA
Hp
FLA
Hp
FLA
024
036
208/230-1
187
254
1
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
187
187
414
187
187
414
187
187
414
187
187
414
254
254
508
254
254
508
254
254
508
254
254
508
N/A
N/A
N/A
19.9
13.6
6.1
26.4
16.0
7.8
N/A
N/A
N/A
N/A
N/A
N/A
109.0
83.1
41.0
134.0
110.0
52.0
N/A
N/A
N/A
N/A
N/A
N/A
1
N/A
N/A
N/A
1.7
1.3
0.7
1.7
1.3
0.7
N/A
N/A
N/A
N/A
N/A
N/A
3
N/A
N/A
N/A
3.2
2.4
1.2
3.2
2.4
1.2
N/A
N/A
N/A
N/A
N/A
N/A
29.8
20.7
9.5
37.9
23.7
11.6
N/A
N/A
N/A
N/A
N/A
N/A
50
35
15
65
40
20
N/A
N/A
N/A
1
1
1
2
2
/
/
3
4
1
3
048
060
/
/
3
4
1
3
/
/
3
4
1
3
/
/
3
4
1
3
/
/
3
4
1
3
/
/
3
4
N/A
N/A
N/A
N/A
N/A
N/A
N/A
3
3
072*
096*
208/230-1
208/230-3
460-3
187
187
414
254
254
508
N/A
13.6
6.1
N/A
83.1
41.0
N/A
N/A
2.4
1.2
N/A
8.4
4.0
N/A
41.4
18.9
N/A
55
25
3
/
/
4
3
4
LEGEND
HACR — Heating, Air Conditioning, and Refrigeration
Hp
— Horsepower
FLA
LRA
— Full Load Amps
— Locked Rotor Amps
MOCP — Maximum Overcurrent Protection (HACR breaker)
RLA
— Rated Load Amps
*Unit has two compressors.
14
Table 2J — Electrical Data — Upgrade 1 Evaporator Motor with Upgrade 2 Condenser Motor
FAN MOTORS
VOLTAGE
COMPRESSOR
POWER SUPPLY
Evaporator
(Upgrade 1)
Condenser
(Upgrade 2)
RANGE
UNIT
50AH
V-PH
(60 Hz)
Min Ckt
Amps
MOCP
Amps
Min
Max
QTY
RLA
LRA
Hp
FLA
Hp
FLA
024
036
208/230-1
187
254
1
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
187
187
414
187
187
414
187
187
414
187
187
414
254
254
508
254
254
508
254
254
508
254
254
508
N/A
N/A
N/A
19.9
13.6
6.1
26.4
16.0
7.8
N/A
N/A
N/A
N/A
N/A
N/A
109.0
83.1
41.0
134.0
110.0
52.0
N/A
N/A
N/A
N/A
N/A
N/A
1
N/A
N/A
N/A
2.5
1.8
0.9
2.5
1.8
0.9
N/A
N/A
N/A
N/A
N/A
N/A
3
N/A
N/A
N/A
3.2
2.4
1.2
3.2
2.4
1.2
N/A
N/A
N/A
N/A
N/A
N/A
30.6
21.2
9.7
38.7
24.2
11.9
N/A
N/A
N/A
N/A
N/A
N/A
50
35
15
65
40
20
N/A
N/A
N/A
1
1
1
2
2
/
/
2
4
1
3
048
060
/
/
2
4
1
3
/
/
2
4
1
3
/
/
2
4
1
3
/
/
2
4
1
3
/
/
2
4
N/A
N/A
N/A
N/A
1
1
N/A
N/A
N/A
N/A
3
3
072*
096*
208/230-1
208/230-3
460-3
187
187
414
254
254
508
N/A
13.6
6.1
N/A
83.1
41.0
N/A
3.2
1.6
N/A
8.4
4.0
N/A
42.2
19.3
N/A
55
25
Table 2K — Electrical Data — Upgrade 2 Evaporator Motor with Upgrade 2 Condenser Motor
FAN MOTORS
VOLTAGE
COMPRESSOR
POWER SUPPLY
Evaporator
(Upgrade 2)
Condenser
(Upgrade 2)
RANGE
UNIT
50AH
V-PH
(60 Hz)
Min Ckt
Amps
MOCP
Amps
Min
Max
QTY
RLA
LRA
Hp
FLA
Hp
FLA
024
036
208/230-1
187
254
1
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
187
187
414
187
187
414
187
187
414
187
187
414
254
254
508
254
254
508
254
254
508
254
254
508
N/A
N/A
N/A
19.9
13.6
6.1
26.4
16.0
7.8
N/A
N/A
N/A
N/A
N/A
N/A
109.0
83.1
41.0
134.0
110.0
52.0
N/A
N/A
N/A
N/A
N/A
N/A
3
N/A
N/A
N/A
3.2
2.4
1.2
3.2
2.4
1.2
N/A
N/A
N/A
N/A
N/A
N/A
3
N/A
N/A
N/A
3.2
2.4
1.2
3.2
2.4
1.2
N/A
N/A
N/A
N/A
N/A
N/A
31.3
21.8
10.0
39.4
24.8
12.2
N/A
N/A
N/A
N/A
N/A
N/A
50
35
15
65
40
20
N/A
N/A
N/A
1
1
1
2
2
/
/
4
4
3
3
048
060
/
/
4
4
3
3
/
/
4
4
3
3
/
/
4
4
3
3
/
/
4
4
3
3
/
/
4
4
N/A
N/A
N/A
N/A
1 1/2
1 1/2
N/A
N/A
N/A
N/A
3
3
072*
096*
208/230-1
208/230-3
460-3
187
187
414
254
254
508
N/A
13.6
6.1
N/A
83.1
41.0
N/A
4.8
2.4
N/A
8.4
4.0
N/A
43.8
20.1
N/A
55
25
LEGEND
HACR — Heating, Air Conditioning, and Refrigeration
Hp
— Horsepower
FLA
LRA
— Full Load Amps
— Locked Rotor Amps
MOCP — Maximum Overcurrent Protection (HACR breaker)
RLA
— Rated Load Amps
*Unit has two compressors.
15
Table 2L — Electrical Data — Upgrade 3 Evaporator Motor with Upgrade 2 Condenser Motor
FAN MOTORS
VOLTAGE
COMPRESSOR
POWER SUPPLY
Evaporator
(Upgrade 3)
Condenser
(Upgrade 2)
RANGE
UNIT
50AH
V-PH
(60 Hz)
Min Ckt
Amps
MOCP
Amps
Min
Max
QTY
RLA
LRA
Hp
FLA
Hp
FLA
024
036
208/230-1
187
254
1
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
208/230-1
208/230-3
460-3
187
187
414
187
187
414
187
187
414
187
187
414
254
254
508
254
254
508
254
254
508
254
254
508
N/A
N/A
N/A
19.9
13.6
6.1
26.4
16.0
7.8
N/A
N/A
N/A
N/A
N/A
N/A
109.0
83.1
41.0
134.0
110.0
52.0
N/A
N/A
N/A
N/A
N/A
N/A
1
1
1
1
1
1
N/A
N/A
N/A
N/A
N/A
N/A
3.2
2.4
1.2
3.2
2.4
1.2
N/A
N/A
N/A
N/A
N/A
N/A
3
N/A
N/A
N/A
3.2
2.4
1.2
3.2
2.4
1.2
N/A
N/A
N/A
N/A
N/A
N/A
31.3
21.8
10.0
39.4
24.8
12.2
N/A
N/A
N/A
N/A
N/A
N/A
50
35
15
65
40
20
N/A
N/A
N/A
1
1
1
2
2
/
4
3
048
060
/
4
3
/
4
3
/
4
3
/
4
3
/
4
N/A
N/A
N/A
N/A
3
3
072*
096*
208/230-1
208/230-3
460-3
187
187
414
254
254
508
N/A
13.6
6.1
N/A
83.1
41.0
N/A
2
2
N/A
6.0
2.9
N/A
8.4
4.0
N/A
45.0
20.6
N/A
55
25
LEGEND
HACR — Heating, Air Conditioning, and Refrigeration
Hp
— Horsepower
FLA
LRA
— Full Load Amps
— Locked Rotor Amps
MOCP — Maximum Overcurrent Protection (HACR breaker)
RLA
— Rated Load Amps
*Unit has two compressors.
Table 3 — Evaporator-Fan Performance
EXTERNAL STATIC PRESSURE (in. wg)
UNIT
SIZE
CFM
0.2
0.4
0.6
0.8
1.0
1.2
50AH
Rpm
509
495
470
550
526
510
607
566
537
640
588
552
461
449
435
555
514
448
Bhp
0.11
0.07
0.06
0.17
0.14
0.11
0.29
0.22
0.17
0.44
0.32
0.24
0.36
0.29
0.24
0.74
0.66
0.37
Rpm
632
623
604
651
635
627
685
652
632
715
670
642
543
537
529
618
584
552
Bhp
0.14
0.12
0.10
0.23
0.19
0.16
0.36
0.28
0.23
0.52
0.40
0.31
0.47
0.40
0.34
0.87
0.80
0.51
Rpm
739
733
717
744
734
731
760
734
722
786
747
725
619
616
611
680
652
626
Bhp
0.19
0.17
0.14
0.29
0.25
0.21
0.43
0.35
0.29
0.61
0.48
0.38
0.60
0.53
0.47
1.01
0.81
0.64
Rpm
833
829
814
831
825
824
832
813
806
—
819
803
689
—
683
—
Bhp
0.24
0.22
0.19
0.36
0.31
0.27
0.50
0.42
0.35
—
0.56
0.46
0.75
—
0.61
—
Rpm
Bhp
0.30
0.28
0.25
0.43
0.38
0.33
0.58
0.49
0.42
—
Rpm
Bhp
0.37
0.34
0.31
—
0.45
0.40
—
900
800
700
919
915
901
912
908
910
902
888
886
—
997
993
979
—
986
988
—
960
962
—
024
036
048
060
072
096
1350
1200
1050
1800
1600
1400
2250
2000
1750
2700
2400
2100
3600
3200
2800
0.56
0.49
—
889
878
—
0.64
0.53
—
—
950
—
—
0.61
—
—
—
—
—
—
—
—
—
—
—
—
—
707
695
0.94
0.79
769
759
1.10
0.95
—
818
—
1.12
LEGEND
NOTES:
1. Refer to Table 1 for evaporator fan motor and drive information.
2. Upgrade 1 Static Motor is required for boldface values.
3. Upgrade 2 Static Motor is required for shaded values.
Bhp
—
Brake Horsepower
16
Table 4 — Condenser-Fan Performance
EXTERNAL STATIC PRESSURE (in. wg)
UNIT
SIZE
50AH
CFM
0.0
0.1
0.2
0.3
0.4
0.5
Rpm
247
276
251
287
367
448
Bhp
0.07
0.11
0.17
0.22
0.68
1.26
Rpm
255
282
305
334
438
524
Bhp
0.07
0.11
0.18
0.28
0.89
1.59
Rpm
262
289
357
378
464
546
Bhp
0.08
0.12
0.22
0.33
0.98
1.70
Rpm
269
295
408
421
490
568
Bhp
0.08
0.12
0.27
0.38
1.07
1.81
Rpm
277
301
456
464
516
—
Bhp
0.08
0.12
0.32
0.43
1.16
—
Rpm
284
307
501
505
542
—
Bhp
0.09
0.13
0.37
0.49
1.25
—
024
036
048
060
072
096
1700
2000
2500
3000
5200
6400
LEGEND
Brake Horsepower
NOTES:
1. Refer to Table 1 for condenser fan motor and drive information.
2. Upgrade 1 Static Motor is required for boldface values.
3. Upgrade 2 Static Motor is required for shaded values.
Bhp
—
START-UP
SERVICE
Unit Preparation — Make sure unit has been installed in
WARNING
accordance with installation instructions and applicable codes.
Disconnect all power to the unit before performing mainte-
nance or service. Electrical shock and personal injury could
result.
Compressor Mounting — Compressors are internally
mounted on rubber-in-shear (RIS) isolators. Do not loosen or
remove compressor holddown bolts.
Internal Wiring — Check all electrical connections in
unit control boxes and tighten as required.
IMPORTANT: If repairs to refrigerant cycle compo-
nents (e.g., compressor, filter drier, etc.) are required,
recover all refrigerant from the system by using both
high and low-pressure ports. Then remove base unit
from the space.
Refrigerant Service Valves — Each unit system has
2 Schrader-type service ports, one on the suction line and one
on the compressor discharge line. Be sure that caps on the ports
are tight.
Compressor Rotation — On 50AH036-096, 3-phase
units, it is important to be certain compressor is rotating in the
proper direction. To determine whether or not compressor is
rotating in the proper direction:
1. Connect service gages to suction and discharge pressure
fittings.
Filters — Filters are disposable and should be inspected and
replaced at regular intervals monthly or as conditions require.
They are located in front of the evaporator coil and may be re-
moved by sliding them horizontally out to edge of unit. See
Fig. 2-5. No tools are required for installation or removal of
filters.
2. Energize the compressor.
3. The suction pressure should drop and the discharge pres-
sure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge pres-
sure does not rise to normal levels:
1. Note that the condenser and evaporator fans may also be
rotating in the wrong direction.
2. Turn off power to the unit and tag disconnect.
3. Reverse any two of the unit power leads.
4. Reapply power to the unit; remove tag.
5. Verify correct refrigerant pressures.
The suction and discharge pressure levels should move to
their normal start-up levels.
NOTE: When the compressor is rotating in the wrong direc-
tion, the unit will sound louder than normal and will not
provide cooling.
Condenser Coil — The condenser coil is accessible
through the side access panel on condenser section, or through
side access panel on condenser section. Use a stiff brush when
cleaning coil. Be careful not to bend aluminum fins.
Evaporator Coil — The evaporator coil is accessible for
cleaning through the side access panel on evaporator section.
When necessary, wash coil with a commercial cleaner (Oakite
164) or dishwasher detergent using a pressurized spray canis-
ter. Flush coil from return-air duct side and take care not to get
water in ductwork or unit insulation.
Condensate Drain — Clean and empty drain pan at
least once a year to prevent sludge build-up.
Lubrication — Lubrication of the condenser and evapora-
tor motors is not necessary since both are equipped with
permanently lubricated bearings. Do not oil.
Unit Condenser Motor — All 50AH units contain
belt-driven adjustable-pulley fan systems. The unit fan motors
are shipped with adjustable pulley at 4 turns open.
Cooling — To start unit, turn on main power supply. Set
system selector switch at COOL position and fan switch at
AUTO. position. Adjust thermostat to a setting below room
temperature. Compressor, condenser and evaporator motors
start on closure of contactors.
TO SHUT OFF UNIT — Set system selector switch at OFF
position or reset thermostat at a position above room
temperature.
Blower Wheel Servicing — In-space servicing is rec-
ommended for the evaporator and condenser blowers. Both are
removed by loosening and removing the 2 screws (sizes 024-
060) or 4 screws (sizes 072 and 096) that hold them in place. In
both cases, the entire assembly is then moved outside of the
base unit. Once outside, the blower wheel and condenser shaft
bearings and/or evaporator motor can be serviced.
17
Blower Belt Adjustment — Inspect blower belt for
wear, proper belt tension, and pulley alignment as conditions
require or at the beginning of each heating and air conditioning
season.
Make sure that fan shafts and motor shafts are parallel and
level. The most common causes of misalignment are nonparal-
lel shafts and improperly located sheaves. Where shafts are not
parallel, belts on one side are drawn tighter and pull more than
their share of the load. As a result, these belts wear out faster,
requiring the entire set to be replaced before it has given maxi-
mum service. If misalignment is in the sheave, belts enter and
leave the grooves at an angle, causing excessive belt and
sheave wear.
a50-7135tf
SHAFT ALIGNMENT — Check shaft alignment by measur-
ing the distance between the shafts at 3 or more locations. If the
distances are equal, then the shafts are parallel.
SHEAVE ALIGNMENT
1. To check the location of the fixed sheaves on the shafts,
use a straightedge or a piece of string. If the sheaves are
properly aligned, the string will touch them at the points
indicated by the arrows in Fig. 9. Rotate each sheave a
half revolution to determine whether the sheave is wob-
bly or the drive shaft is bent. Correct any misalignment.
2. With sheaves aligned, tighten cap screws evenly and
progressively.
Fig. 9 — Sheave Alignment
1
1
NOTE: There should be a /8-in. to /4-in. gap between
the mating part hub and the bushing flange. If the gap is
closed, the bushing is probably the wrong size.
LB FORCE
3. With taper-lock bushed hubs, be sure the bushing bolts
are tightened evenly to prevent side-to-side pulley wob-
ble. Check by rotating sheaves and rechecking sheave
alignment. When substituting field-supplied sheaves for
factory-supplied sheaves, only the motor sheave should
be changed.
DEFLECTION
a50-7136ef
BELT TENSION ADJUSTMENT — Using a gage, apply
4 lb of force to the center of the belt and adjust the tension until
a deflection of 1/64-in. is achieved for every inch of shaft center
distance. See Fig. 10.
Ideal belt tension is the lowest value under which belt slip
will not occur at peak load conditions.
Fig. 10 — Fan Belt Tension
Refrigerant Charge — Unit is shipped fully charged.
Amount of refrigerant charge is listed on unit nameplate (also
refer to Table 1). Refer to Carrier GTAC II; Module 5; Charg-
ing, Recovery, Recycling, and Reclamation manual.
Unit panels must be in place when unit is operating during
charging procedure. Unit must operate for at least 10 minutes
before adjusting charge. Use standard evacuating techniques.
After evacuating system, weigh in the specified amount of re-
frigerant. (Refer to Table 1.)
18
Copyright 2010 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500057-01
Printed in U.S.A.
Form 50AH-14SI
Pg 20
5-10
Replaces: 50AH-12SI
|