Hitachi RAM 72Q5 User Manual

If you wish to prepare the copper tubes and insulation material in the field, we recommend the following.  
FOR SERVICE PERSONNEL ONLY  
G
No.  
Material  
Specification  
Carefully read through the procedures of proper  
Small dia.  
Large dia.  
Small dia.  
Large dia.  
Small dia.  
Large dia.  
Small dia.  
Large dia.  
Deoxidized annealed copper pipe with 6.35mm O.D., 0.8mm wall thickness.  
Deoxidized annealed copper pipe with 9.52mm O.D., 1.0mm wall thickness.  
Deoxidized annealed copper pipe with 6.35mm O.D., 0.8mm wall thickness.  
Deoxidized annealed copper pipe with 12.7mm O.D., 1.0mm wall thickness.  
Flare nuts with 6.35mm O.D..  
4.0kW or less  
installation before starting installation work.  
The sales agent should inform customers regarding  
the correct operation of installation.  
G
1
Cooper tube  
Flare nut  
5.0kW or more  
4.0kW or less  
5.0kW or more  
SPLIT UNIT AIR CONDITIONER  
INSTALLATION MANUAL  
Tools Needed For Installation Work  
(Mark  
is exclusive use tool for R410A)  
G
G
G
G
– Screwdriver Measuring Tape Knife  
+
Saw  
Flare nuts with 9.52mm O.D..  
G
G
ø 65mm Power Drill  
Key ( 4mm) Wrench (14, 17, 22, 26mm)  
Leakage Detector Pipe Cutter Putty Vinyl Tape  
Hexagonal Wrench  
Gas  
2
3
Flare nuts with 6.35mm O.D..  
G
G
G
G
HFC  
Outdoor Unit  
RAM-72Q5  
Flare nuts with 12.7mm O.D..  
R410A  
G
G
Pliers Flare Tool  
Vacuum Pump Adapter  
Vacuum Pump  
Foamed polyethylene insulation pipe which does not corrode the copper tube.  
Large dia. pipe side: 15mm I.D.., 8mm wall thickness.  
Small dia. pipe side: 8mm I.D., 7mm wall thickness.  
Manifold Valve Charge Hose  
Insulation for refrigerating pipe  
SAFETY PRECAUTION  
G
G
Read the safety precautions carefully before operating the unit.  
The contents of this section are vital to ensure safety. Please pay special attention to the following sign.  
WARNING ........ Incorrect methods of installation may cause death or serious injury.  
4
5
6
7
8
Connecting cord  
Vinyl tape  
Refer to item 3.3.  
!
! CAUTION ......... Improper installation may result in serious consequence.  
Make sure to connect earth wire.  
This sign in the figures indicates prohibition.  
Be sure that the unit operates in proper condition after installation. Explain to customer the proper way of operating  
Sealer (Putty)  
Refrigerator oil  
Bushing for refrigerating pipes  
the unit as described in the users guide.  
1. Proper place for installation  
1.1 Outdoor unit  
!
WARNING  
(1) Keep the space around the unit for maintenance and avoiding the effects of hindrance for normal ventilation of the unit.  
(2) The northern or eastern side of the building is better to install. At the installation on the southern or western side unavoidably, some blind  
should be set up for the unit. (In this case, the blind must not obstruct the ventilation of the unit.)  
(3) Youd better not put the unit at a place where is full of dirt and at a place where is wet in the rain.  
(4) Place as near as possible to the indoor unit.  
G
Please request your sales agent or qualified technician to install your unit. Water leakage, short circuit or fire may occur if you  
do the installation work yourself.  
G
G
G
G
Please observe the instructions stated in the installation manual during the process of installation. Improper installation may  
cause water leakage, electric shock and fire.  
(5) Install the unit in a stable place to minimize vibration or noise.  
(6) After arranging the cords and pipes, secure them in place.  
Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the  
units may collapse and impose danger.  
Observe the rules and regulations of the electrical installation and the methods described in the installation manual when  
dealing with the electrical work. Use power cables approved by the authorities of your country.  
G
This appliance must be earthed.  
Power is supplied through outdoor unit, do not connect power source to indoor unit.  
WARNING  
!
G
Be sure to use the specified wire for connecting the indoor and outdoor units. Please ensure that the connections are tight  
after the conductors of the wire are inserted into the terminals. Improper insertion and loose contact may cause over-heating  
and fire.  
2. In the electrical installation a separator with a contact gap of more than  
3mm has to be installed. During cleaning or service the set has to be  
switched off with this separator.  
3.2 Connection of the connecting cords and power cord  
(1) Cut off the connecting cord, the power cord and strip the  
insulation of the wire, as shown in Fig. 3-2.  
G
Please use the specified components for installation work. Otherwise, the units may collapse or water leakage, electric shock  
and fire may occur.  
(2) Connect the connecting cord and power cord to the terminal  
board. (Fig. 3-3)  
(3) Fix the connecting cords and power cord with steel band  
certainly. (Fig. 3-3)  
3. Installation procedure and notice  
G
G
Be sure to use the specified piping set for R-410A. Otherwise, this may result in broken copper pipes or faults.  
Especially, the selection of installation place need great care for the  
split type air conditioner, because it is very difficult to move from place  
to place after the first installation.  
When installing or removing an air conditioner, only specified refrigerant (R410A) shall be allowed, do not allow air or moisture  
to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a rupture  
may be caused.  
3.1 Wiring  
30mm  
G
Green-and-yellow (ground)  
Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with fire, a poisonous  
gas may occur.  
(1) Connect the electrical wiring between the Indoor and Outdoor unit,  
as shown in Fig. 3-1. Never connect the wiring by mistake.  
In case of wrong connection, the unit does not operate properly  
and it may cause malfunction.  
10mm  
G
G
After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks  
into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.  
10mm  
55mm  
Power cord and  
connecting cord  
(2) The connecting cord must be fixed by the band which is located  
near the terminal board.  
Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner  
technician or electrician. Improper repairs may result in water leakage, electric shock and fire, etc.  
Detail of cutting power cord  
Wiring Pattern  
Procedures of Wiring  
G
Be sure to connect the earth wire from the power supply wire to the outdoor unit and between the outdoor and indoor  
unit. Improper earthing may cause electric shock.  
60mm  
Green-and-yellow (ground)  
Indoor Unit  
10mm  
Indoor unit No. 1  
Indoor unit No. 2  
Indoor unit No. 3  
Indoor unit No. 4  
Screw for ground, earth screw  
Screw for ground, earth screw  
10mm  
Screw for ground, earth screw  
Screw for ground, earth screw  
85mm  
Connecting cord  
!
CAUTION  
Terminal board  
Terminal board  
Terminal board  
Terminal board  
G
A circuit breaker must be installed in the house distribution box for the direct connected power supply wire to the outdoor unit.  
In case of other installations a main switch with a contact gap or more than 3.5mm has to be installed. Without a  
circuit breaker, the danger of electric shock exists.  
Do not install the unit near a location where there is flammable gas. The outdoor unit may catch fire if flammable  
gas leaks around it.  
For Indoor Unit No. 1 (C1, D1),  
Indoor Unit No. 2 (C2, D2),  
Indoor Unit No. 3 (C3, D3) and  
Indoor Unit No. 4 (C4, D4)  
C
D
C
D
C
D
C
D
Green-and-  
Yellow  
Green-and-  
Yellow  
Green-and-Yellow  
Green-and-Yellow  
G
G
Screw for ground,  
earth screw  
Fig. 3-2  
Be sure to tighten the flare nut to the specified torque using a torque wrench. If the flare nut is tightened excessively, it may  
crack as time elapses, cause refrigerant leakage.  
Terminal board  
C1 D1  
Terminal board  
C2 D2  
Terminal board  
C3 D3  
Terminal board  
C4 D4  
Terminal board  
L
N
G
G
Please ensure smooth flow of water when installing the drain hose.  
An IEC approved power cord should be used. Power cord type: NYM.  
Screw for ground, earth screw  
For Indoor unit No. 1  
Screw for ground, earth screw  
For Indoor unit No. 2  
Screw for ground, earth screw  
For Indoor unit No. 3  
Screw for ground, earth screw  
For Indoor unit No. 4  
THE CHOICE OF MOUNTING SITE (Please note the following matters and obtain permission from customer before installation).  
Green-and-Yellow  
Power cord  
Outdoor Unit  
!
WARNING  
Fig. 3-1  
G
The Outdoor unit must be mounted at a location which can support heavy weight. Otherwise, noise and vibration will increase.  
!
WARNING  
G
!
The naked part of the wire core should be 10 mm and fix it to the terminal tightly. Then try to pull the individual wire to check if the contact is  
CAUTION  
tight. Improper insertion may burn the terminal.  
G
G
G
Do not expose the unit under direct sunshine or rain. Besides, ventilation must be good and clear of obstruction.  
The air blown out of the unit should not point directly to animals or plants.  
The clearances of the unit from top, left, right and front are specified in figure below. At least 3 of the above sides must be open  
air.  
Be sure that the hot air blown out of the unit and noise do not disturb the neighbourhood.  
Do not install at a location where there is flammable gas, steam, oil and smoke.  
The location must be convenient for water drainage.  
Be sure to use only power cables approved from the authorities in your country. For example in Germany: Cable type: NYM 3x1.5mm2. (fuse  
G
G
G
= 16A time delay)  
Please refer to the installation manual for wire connection to the terminals of the units. The cabling must meet the standards of electrical  
installation.  
There is a AC voltage of 220-240V between the L and N terminals. Therefore, before servicing, be sure to remove the plug from the AC outlet  
or switch off the main switch.  
G
G
G
G
Place the Outdoor unit and its connecting cord at least 1m away from the antenna or signal line of television, radio or telephone.  
This is to avoid noise interference.  
Wiring of The Outdoor Unit  
G
Please remove the side cover for wire connection.  
G
If you cannot attach the side cover due to the connecting cord, press the connecting cord in direction to the front panel  
Figure showing the Installation of Outdoor Unit.  
to fix it.  
!
G
G
Be sure that the hooks of the side cover is fixed in certainly. Otherwise water leakage may occur and this causes short  
circuit or faults.  
The connecting cord should not touch to service valve and pipes. (It becomes high temperature in heating operation.)  
Height difference  
Piping length  
Dimension of Mounting Stand  
of the Outdoor unit  
WARNING  
Indoor unit 2 Indoor unit 3  
Indoor unit 4  
Indoor unit 1  
Height difference between indoor units should  
be not more than 5m.  
(unit: mm)  
3.3 Checking for the electric source and the voltage range  
mounting stand  
57  
Indoor unit 3  
Indoor unit 4  
Outdoor unit  
L1  
G
Before installation, the power source must be checked and necessary wiring work must be completed. To make the wiring capacity proper,  
use the wire gauges list below for the lead-in from a pole transformer and for the wiring from a switch board of fuse box to the main switch  
and outdoor unit in consideration of the locked rotor current.  
L2  
L3  
L4  
Indoor unit 2  
Indoor unit 1  
Outdoor unit  
12  
35  
508  
198  
IMPORTANT  
(L1 + L2 + L3 + L4) = Maximum 60m  
Cable length  
Wire cross-section  
!
WARNING  
Minimum piping length for each indoor unit is 5m.  
Maximum piping length for one indoor unit is 25m.  
In case the pipe length is more than 30m, add  
refrigerant R410A at 20 gram per every meter exceeds.  
up to 16m  
up to 15m  
up to 25m  
1.5mm2  
2.5mm2  
4.0mm2  
G
Connect the Connecting Cord to C1 and D1 Indoor 1for indoor unit 1,  
C2 and D2 Indoor 2for indoor unit 2, C3 and D3 Indoor 3for indoor  
unit 3, C4 and D4 Indoor 4for indoor unit 4.  
When removing side cover, pull the handle after releasing  
the hook by pulling it downward.  
Bind connecting cords to make them  
fit between the convex sections.  
Connect the  
earth cord  
Face this side (suction side) of the unit  
to the wall.  
AC 220V — 240V ONLY  
Remove side cover when  
connecting the piping and  
connecting cord.  
INDOOR 1 INDOOR 2 INDOOR 3 INDOOR 4  
L N  
C1 D1 C2 D2 C3 D3 C4 D4  
500  
Pull downward  
After remove the screw  
and cover, put the  
connecting cords and fix  
the cover with screw.  
[Outdoor unit installation]  
Mount the Outdoor unit on stable ground to prevent vibration and increase of  
noise level.  
!
CAUTION  
Decide the location for piping after sorting out the different types of pipe available.  
!
CAUTION  
G
Make sure to connect to  
two or more indoor units.  
Arrange power cord so they do  
not touch service valve.  
Flare adaptor for piping  
One unit of 1.8kW, 2.5kW,  
3.5kW or 5.0kW  
Earth line  
Fig. 3-3  
The flare adaptor for piping is required  
depending on combination of indoor  
units.  
• ø9.52 (3/8) ø 12.7 (1/2)  
Parts number TA261D-4 001  
• ø12.7(1/2) ø 9.52 (3/8)  
Parts number TA261D-6 002  
Type of grounding rod  
SP-EB-2  
Length  
900mm  
One unit of 1.8kW, 2.5kW, 3.5kW or 5.0kW  
(5kW unit: Optional flare adaptor for piping is necessary.)  
Grounding rod  
(optional)  
One unit of 1.8kW, 2.5kW, 3.5kW, 5.0kW or 6.0kW  
(5kW, 6kW unit: Optional flare adaptor for piping is necessary.)  
(Earth wire and grounding rod are not supplied. Please use optional items below.)  
G
Investigate the power supply capacity and other electrical conditions at the installation location.  
One unit of 1.8kW, 2.5kW, 3.5kW, 5.0kW or 6.0kW  
(2.5kW, 3.5kW unit: Optional flare adaptor for piping is necessary.)  
Depending on the model of room air conditioner to be installed, request the customer to make arrangements for the necessary electrical  
work etc.  
The electrical work includes the wiring work up the outlet. In localities where electrical conditions are poor, use of a voltage regulation is  
recommended.  
To the outdoor unit, up to four indoor units can be connected until the total value of each unitss capacity reaches 11 kW.  
The pipe connection ports of the outdoor unit and connectable indoor units are shown above.  
IMPORTANT  
Fuse Capacity  
30A time delay fuse  
<
IA93: A  
>

Briggs Stratton 126300 User Manual
Carrier KSALA0301410 User Manual
Cino FUZZYSCAN F600 User Manual
First Alert 9120 User Manual
Friedrich 230 VoltsUS12 User Manual
Fujitsu Air Conditioner INVERTER User Manual
Goodman Mfg CKLB30 1D User Manual
Heat Controller Inc Air Conditioner VMC09SB 1 User Manual
HP Hewlett Packard Hewlett Packard All in One Printer L2245W User Manual
HP Hewlett Packard HP PHOTOSMART 2600 User Manual