LST Smoke Alarm FC600 O User Manual

Optical Smoke Detector  
FC600/O  
• Addressable conventional technology  
• Individual detector identification with  
optional address module  
• Allows for connection of external  
remote indicator  
• Anti-tamper locking feature on  
detector base  
• Double dust trap and insect screen  
• Function check by means of test  
magnet or test gas  
Description  
The Optical Smoke Detector FC600/O is based on the  
IR light scattering principle and offers superior wide-  
spectrum detection of smoke aerosols generated by  
the majority of fires. A symmetrical detection chamber  
allows for optimal smoke sensitivity from all directions.  
Any alarm will be transmitted to the fire detection pa-  
nel in conventional technology. An individual detector  
identification can be obtained with the optional Address  
Module NG58-1.  
An automatic drift compensation keeps the response  
sensitivity of the detector constant for a long period.  
The double dust trap effectively protects the detector  
FC600/O against false alarms resulting from dust con-  
tamination and ambient light. An insect screen prevents  
insects from interfering with the detection chamber.  
Several types of detector bases are available to faci-  
litate quick and easy installation. To prevent unautho-  
rized removal of the detector, all detector bases are  
equipped with an anti-tamper locking feature.  
The detector is equipped with an LED indicator which  
is visible from all sides at any angle and thus facilitates  
easy identification of the alarming detector. In addition,  
a remote indicator can also be connected.  
A detector function test can be conveniently conducted  
by using either a test magnet or test gas.  
Specifications  
Operating voltage  
Current consumption  
Ambient temperature  
Relative humidity  
Dimensions ø × h (without base)  
Colour  
10 – 30VDC (supply through detector line voltage)  
typ. 75µA (normal condition)  
-30°C to +70°C  
max. 95% (no condensation)  
106 × 46 (mm)  
white  
Weight  
80g  
Approvals  
LPCB 603a/01  
0832-CPD-0125  
Order number  
Order name  
241070  
0832–CPD–0125  
Optical Smoke Detector/Conv./FC600 FC600/O  
Building Safety. Building Security.  
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27  
FC600-O_DBL_LST_EN_0850.PDF • PAGE 1  
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED  
 

Kyocera Telescope KD135SX UPU User Manual
Land Pride Lawn Mower RB05 Series User Manual
Lanier Headphones 480 0066 User Manual
LG Electronics Flat Panel Television OLED55B6P User Manual
LG Electronics Portable DVD Player DP570MH User Manual
Lightolier Stereo System RD Cable User Manual
M 2GR45MF 2GR65MR 2GR85MF 3GR45MF 3GR65MF 3GR85MF 4GR45MF ML 136407 ML 136408 ML 136409 ML 136410 ML 136417 ML 136418 ML 136419 ML 136420 ML 136421 ML 136422 ML 136423 User Manual
Magnavox CRT Television 29MT4515 User Manual
Magnavox Stereo System US2 MANT050 User Manual
Maretron Switch SIM100 User Manual