Vector Stereo Amplifier DA 250DH CU User Manual

OPERATING INSTRUCTIONS  
DUAL POWER AMPLIFIERS  
DA-250D CU  
DA-250DH CU  
Note: The figure shows the DA-250D.  
Thank you for purchasing TOA's Dual Power Amplifier.  
Please carefully follow the instructions in this manual to ensure long, trouble-free use of your equipment.  
 
1. IMPORTANT SAFETY INSTRUCTIONS  
• Read these instructions.  
• Keep these instructions.  
• Heed all warnings.  
• Follow all instructions.  
• Do not use this apparatus near water.  
• Clean only with dry cloth.  
• Do not block any ventilation openings. Install in accordance with the manufacturer's instructions.  
• Do not install near any heat sources such as radiators, heat registers, stoves, or other apparatus (including  
amplifiers) that produce heat.  
• Do not defeat the safety purpose of the polarized or grounding-type plug. A polarized plug has two blades  
with one wider than the other. A grounding type plug has two blades and a third grounding prong. The wide  
blade or the third prong are provided for your safety. If the provided plug does not fit into your outlet, consult  
an electrician for replacement of the obsolete outlet.  
• Protect the power cord from being walked on or pinched particularly at plugs, convenience receptacles, and  
the point where they exit from the apparatus.  
• Only use attachments/accessories specified by the manufacturer.  
• Use only with the cart, stand, tripod, bracket, or table specified by the manufacturer,  
or sold with the apparatus. When a cart is used, use caution when moving the  
cart/apparatus combination to avoid injury from tip-over.  
• Unplug this apparatus during lightning storms or when unused for long periods of time.  
• Refer all servicing to qualified service personnel. Servicing is required when the apparatus has been  
damaged in any way, such as power-supply cord or plug is damaged, liquid has been spilled or objects have  
fallen into the apparatus, the apparatus has been exposed to rain or moisture, does not operate normally, or  
has been dropped.  
FCC REQUIREMENTS  
Note: This equipment has been tested and found to comply with the limits for a Class A digital  
device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable  
protection against harmful interference when the equipment is operated in a commercial  
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not  
installed and used in accordance with the instruction manual, may cause harmful interference to  
radio communications. Operation of this equipment in a residential area is likely to cause harmful  
interference in which case the user will be required to correct the interference at his own expense.  
• Reorient or relocate the receiving antenna.  
• Increase the separation between the equipment and receiver.  
• Connect the equipment into an outlet on a circuit different from that to which the receiver is  
connected.  
• Consult the dealer or an experienced radio/TV technician for help.  
• This Class A digital apparatus complies with Canadian ICES-003.  
• Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada.  
3
 
2. SAFETY PRECAUTIONS  
• Before installation or use, be sure to carefully read all the instructions in this section for correct and safe  
operation.  
• Be sure to follow all the precautionary instructions in this section, which contain important warnings and/or  
cautions regarding safety.  
• After reading, keep this manual handy for future reference.  
Safety Symbol and Message Conventions  
Safety symbols and messages described below are used in this manual to prevent bodily injury and property  
damage which could result from mishandling. Before operating your product, read this manual first and  
understand the safety symbols and messages so you are thoroughly aware of the potential safety hazards.  
Indicates a potentially hazardous situation which, if mishandled, could  
result in death or serious personal injury.  
WARNING  
Indicates a potentially hazardous situation which, if mishandled, could  
result in moderate or minor personal injury, and/or property damage.  
CAUTION  
· If you detect smoke or a strange smell coming  
from the unit.  
WARNING  
· If water or any metallic object gets into the unit  
· If the unit falls, or the unit case breaks  
· If the power supply cord is damaged (exposure of  
the core, disconnection, etc.)  
· If it is malfunctioning (no tone sounds.)  
When Installing the Unit  
• Do not expose the unit to rain or an environment  
where it may be splashed by water or other liquids,  
as doing so may result in fire or electric shock.  
• To prevent a fire or electric shock, never open nor  
remove the unit case as there are high voltage  
• Use the unit only with the voltage specified on the  
components inside the unit. Refer all servicing such  
unit. Using a voltage higher than that which is  
as modification inside the unit to qualified service  
specified may result in fire or electric shock.  
personnel.  
• Do not cut, kink, otherwise damage nor modify the  
• Do not place cups, bowls, or other containers of  
power supply cord. In addition, avoid using the  
liquid or metallic objects on top of the unit. If they  
power cord in close proximity to heaters, and never  
accidentally spill into the unit, this may cause a fire  
place heavy objects -- including the unit itself -- on  
or electric shock.  
the power cord, as doing so may result in fire or  
electric shock.  
• Do not insert nor drop metallic objects or flammable  
materials in the ventilation slots of the unit's cover,  
as this may result in fire or electric shock.  
• Be sure to replace the unit's terminal cover after  
connection completion. Because the voltage of up  
to 140 V is applied to the high impedance speaker  
• Do not touch a plug during thunder and lightning,  
terminals, never touch these terminals to avoid  
as this may result in electric shock.  
electric shock. (DA-250DH only)  
• External wiring connected to the terminals marked  
with requires installation by an instructed person.  
CAUTION  
(DA-250DH only)  
• The apparatus shall be connected to a mains  
socket outlet with a protective earthing connection.  
When Installing the Unit  
• Never plug in nor remove the power supply plug  
with wet hands, as doing so may cause electric  
shock.  
When the Unit is in Use  
• Should the following irregularity be found during  
• When unplugging the power supply cord, be sure  
to grasp the power supply plug; never pull on the  
cord itself. Operating the unit with a damaged  
power supply cord may cause a fire or electric  
shock.  
use, immediately switch off the power, disconnect  
the power supply plug from the AC outlet and  
contact your nearest TOA dealer. Make no further  
attempt to operate the unit in this condition as this  
may cause fire or electric shock.  
4
 
• When moving the unit, be sure to remove its power  
supply cord from the wall outlet. Moving the unit  
with the power cord connected to the outlet may  
cause damage to the power cord, resulting in fire or  
electric shock. When removing the power cord, be  
sure to hold its plug to pull.  
• Make sure that all volume controls are set to  
minimum position before power is switched on.  
Loud noise produced at high volume when power is  
switched on can impair hearing.  
• Do not operate the unit for an extended period of  
time with the sound distorting. This is an indication  
of a malfunction, which in turn can cause heat to  
generate and result in a fire.  
• Avoid installing the unit in humid or dusty locations,  
in locations exposed to the direct sunlight, near the  
heaters, or in locations generating sooty smoke or  
steam as doing otherwise may result in fire or  
electric shock.  
• Contact your TOA dealer as to the cleaning. If dust  
is allowed to accumulate in the unit over a long  
period of time, a fire or damage to the unit may  
result.  
• To avoid electric shocks, be sure to switch off the  
unit's power when connecting speakers.  
• If dust accumulates on the power supply plug or in  
the wall AC outlet, a fire may result. Clean it  
periodically. In addition, insert the plug in the wall  
outlet securely.  
• The unit is designed exclusively to be mounted in  
an equipment rack. Be sure to follow the  
instructions below when rack-mounting the unit.  
Failure to do so may cause a fire or personal injury.  
• Switch off the power, and unplug the power supply  
plug from the AC outlet for safety purposes when  
cleaning or leaving the unit unused for 10 days or  
more. Doing otherwise may cause a fire or electric  
shock.  
· Install the equipment rack on a stable, hard floor.  
Fix it with anchor bolts or take other arrangements  
to prevent it from falling down.  
· Be sure to use the screws with a diameter of over  
5 mm (0.2") and length of over 12 mm (0.47") to  
mount the unit.  
· When connecting the unit's power cord to an AC  
outlet, use the AC outlet with current capacity  
allowable to the unit.  
An all-pole mains switch with a contact  
separation of at least 3 mm (0.12") in each pole  
shall be incorporated in the electrical installation  
of the building.  
When the Unit is in Use  
• With the High-pass filter jumper socket kept to the  
OFF position (factory preset), operating the unit for  
long periods of time while the Peak indicator is  
illuminated due to excessive input signal may  
damage the connected speakers, possibly resulting  
in fire. Operating the unit with the High-pass filter  
jumper socket set to the ON position may decrease  
the possibility of speaker damage or fire due to  
excessive input signal.  
The lighting flash with arrowhead symbol,  
within an equilateral triangle, is intended  
to alert the user to the presence of  
uninsulated "dangerous voltage" within  
the product's enclosure that may be of  
sufficient magnitude to constitute a risk of  
electric shock to persons.  
5
 
3. GENERAL DESCRIPTION  
TOA's DA-250D and DA-250DH Dual Power Amplifiers feature high power handling capabilities and durability.  
The DA-250D is configured with 250 W x 2 channels (4 Ω output) and 170 W x 2 channels (8 Ω output), and  
the DA-250DH features a 250 W x 2 channels (19.6 Ω output) configuration.  
Besides, each model's output is made available for bridge connection, allowing it to be used as a monaural  
amplifier of 500 W (8 Ω for DA-250D, 39.2 Ω for DA-250DH).  
Their wide range of applications include stores and permanent sound systems.  
4. FEATURES  
• 1U rack mounting size*.  
• Low power consumption and light weight.  
• An input signal to Channel 1 can be routed to both channels 1 and 2, and the output level adjusted using the  
input level control for each channel.  
• Electronically-balanced inputs.  
• Input terminals employ removable terminal blocks to provide maximum connection ease.  
• Input/output status LED indicators for each channel.  
• Built-in protection circuitry disconnects the output when a short circuit, overload, or unusual temperature rise  
occurs.  
* 1U size = 44.5 mm or 1.75" (reference size)  
5. HANDLING PRECAUTIONS  
• Keep the input cable away from the output cable. If installed close to each other, oscillation could occur.  
• To avoid unit failures, never connect outputs of two or more units in parallel.  
• Only connect speakers with an impedance equal to or greater than those specified. Connecting speakers  
with a smaller than specified impedance could cause damage to the unit.  
• Periodically clean the filter located inside the ventilation panel on the unit's front panel. If the filter becomes  
clogged, heat will become trapped inside the enclosure.  
• Install the unit in locations where the temperature is between –10 and +40°C (14°F and 104°F) and the  
moisture is less than 90%RH (no dew condensation must be formed).  
• To clean, be sure to first switch off the unit's power, then wipe with a dry cloth. When the unit gets very dirty,  
use a cloth damped in a neutral cleanser. Never use benzene, thinner, alcohol, or chemically-treated  
cleaning cloth because such volatile liquids could deform or discolor the unit.  
6
 
6. INSTALLATION PRECAUTIONS  
Rack mounting screws are not supplied with the unit.  
Be sure to use the screws with a diameter of over 5 mm (0.2") and  
length of over 12 mm (0.47") to mount the unit.  
Failure to do so may cause personal injury.  
CAUTION  
• The supplied power supply cord is designed for exclusive use with this unit. Never use it with other  
equipment.  
• When mounting the unit in an equipment rack, the inside of the rack must be sufficiently ventilated.  
To achieve sufficient ventilation, remove all panels on the rear of the rack.  
• When mounting the unit in the rack, also mount a Perforated Panel larger than 1U in size*:  
(1) at the top and the bottom of the rack, and  
(2) above and below every 5 units.  
Power amplifiers  
DA-250D/250DH  
Power amplifiers  
DA-250D/250DH  
Perforated panel  
• Robust structure is one of the unit's main features. However, if the strength is particularly needed when  
installing the unit in the rack, use a supporting runner for the safety purposes.  
* 1U size = 44.5 mm or 1.75" (reference size)  
7
 
7. NOMENCLATURE AND FUNCTIONS  
[Front]  
3
4
5
2
1
Note: The figure shows the DA-250D.  
5. Indicators [INPUT, OUTPUT, PEAK, PROTECT]  
1. Power switch [  
ON /  
OFF]  
The indicators are as follows from left to right:  
Power is switched on and off with each  
depression of this switch.  
• Input indicator [INPUT]  
Lights green regardless of the input level  
control setting when an input signal level  
exceeds about –20 dB.  
2. Power indicator [POWER]  
Lights blue when the power is switched on.  
• Output indicator [OUTPUT]  
Lights yellow when an output level exceeds  
about 1 W at an 8 Ω load (DA-250D) or 19.6 Ω  
load (DA-250DH).  
3. Input level controls [CH 1/BRIDGE, CH 2]  
Adjust the input level of each channel.  
• Peak indicator [PEAK]  
Lights red when an output signal clips  
(distortion occurs).  
When a bridge connection is made  
When Channels 1 and 2 are bridge-connected  
(BRIDGE ON/OFF switch (9) is set to ON), the  
CH 1/BRIDGE level control adjusts the input  
levels of Channels 1 and 2. In this event, the  
CH 2 level control cannot be used.  
• Protection indicator [PROTECT]  
Lights red when the protection circuitry is  
activated. (See p. 14; Protection Operation  
List.) When the power is switched on, this  
indicator lights for about 2 seconds and then  
extinguishes.  
4. Ventilation panel (Air Vent)  
A filter is located inside the ventilation panel.  
To clean the filter, remove the ventilation panel.  
(See p. 15; Cleaning the Filter.)  
8
 
[Rear]  
6
6
7
7
8
8
9
9
10  
10  
DA-250D  
11  
11  
DA-250DH  
6. AC inlet  
10. CH1 mode ON/OFF switch  
[PARALLEL, ON / OFF]  
Connect the supplied power cord to this inlet.  
Setting this switch to ON (pressed in) transmits  
the Channel 1 input signal to both channels 1  
and 2. Output signal levels can be individually  
adjusted with each channel's input level control  
(3).  
7. Functional ground terminal [SIGNAL GND]  
Hum noise may be generated when external  
equipment is connected to the unit. Connecting  
this terminal to the functional ground terminal of  
the external equipment may reduce the hum  
noise.  
Note  
Be sure to first turn off the power switch when  
changing the CH 1 mode switch settings.  
Note  
This terminal is not for protective ground.  
11. Input terminals [INPUTS]  
Electronically-balanced input terminals.  
Each removable terminal block (3 pins) is  
internally connected in parallel to the  
corresponding XLR type connector.  
8. Speaker output terminals (with a terminal cover)  
Connect speaker cables to these terminals.  
• Removable terminal block (3 pins)  
H: Hot, C: Cold, E: Earth  
9. BRIDGE ON/OFF switch  
[BRIDGE,  
ON /  
OFF]  
Used when bridge-connecting the unit's  
Channels 1 and 2.  
(See p. 10; Settings and Connections.)  
XLR type male connector (XLR-3-31 equivalent)  
Pin 1: Earth, Pin 2: Hot, Pin 3: Cold  
Caution when using an XLR type plug  
• 2-channel input mode  
Set BRIDGE switch to OFF. (factory-preset)  
If a straight plug hits the rack's rear cover or  
wall behind the rack when it is used for  
connection, use the L-shaped plug instead.  
• 1-channel input mode  
Set BRIDGE switch to ON.  
Note  
Be sure to first turn off the power switch when  
changing the BRIDGE switch settings.  
9
 
8. SETTINGS AND CONNECTIONS  
BRIDGE ON/OFF switch  
CH 1 mode ON/OFF switch  
[Rear panel]  
Speaker output terminals  
Input terminals  
(with a terminal cover)  
Note: The figure shows the DA-250D.  
Step 1. Switch off the unit's power.  
Step 2. Set the BRIDGE ON/OFF switch and CH 1 mode ON/OFF switch.  
Step 3. Connect the sound source equipment to the Input terminals.  
Note: Refer to p. 12 for the removable terminal plug connection.  
Step 4. Connect speakers to the Speaker output terminals.  
4-1. Unscrew the output terminal cover.  
4-2. Strip 10 mm (0.39") of insulative jacket from the end of the speaker cable,  
as shown in the figure at right.  
10 mm  
(0.39”)  
4-3. Connect speaker cables to the output terminals.  
4-4. Replace the output terminal cover in place.  
Be sure to replace the unit's terminal cover after connection completion.  
Because high voltage is generated at the speaker output terminals,  
never touch these terminals to avoid electric shock.  
(DA-250DH only)  
WARNING  
10  
 
8.1. Switch Settings and Speaker Connections  
[2 inputs - 2 outputs] (factory-preset)  
Speaker output terminals  
CH2 CH1  
Switch  
BRIDGE  
Setting  
OFF  
OFF  
CH1  
CH2  
CH1  
CH2  
DA-250D  
4 – 8 Ω  
DA-250DH  
19.6 Ω  
CH 1 mode  
4 – 8 Ω  
19.6 Ω  
[1 input - 2 outputs]  
Speaker output terminals  
CH2 CH1  
Switch  
BRIDGE  
Setting  
OFF  
CH1  
CH1  
DA-250D  
4 – 8 Ω  
DA-250DH  
19.6 Ω  
CH 1 mode  
ON  
CH2  
4 – 8 Ω  
19.6 Ω  
[1 input - 1 output]  
Speaker output terminals  
BRIDGE  
Switch  
BRIDGE  
CH 1 mode  
Setting  
ON  
OFF  
CH1  
CH1  
CH2  
DA-250D  
8 Ω  
DA-250DH  
39.2 Ω  
11  
 
9. REMOVABLE TERMINAL PLUG CONNECTION  
Cautions  
• Be sure to use shielded cables for audio signal lines.  
• Avoid soldering cable conductor, as contact resistance may increase when the cable is tightened and the  
solder is crushed, possibly resulting in an excessive rise in joint temperatures.  
• Use cables of AWG 12 – 24.  
Cable end treatment  
7 mm  
Shielded cable  
(0.28”)  
20 mm  
(0.79”)  
Connector connections  
Step 1. Loosen the terminal screw, then insert the cable.  
Step 2. Retighten the terminal screw. (Pull on the cable to ensure it is securely connected.)  
Slotted screwdriver  
Tightens  
Loosens  
2
1
Terminal screw  
1
Hot  
Removable terminal  
plug  
Earth  
Cold  
Shielded cable  
Tip  
Recommended slotted screwdriver type: Screwdriver with blade that is 3 mm (0.12") in width  
Bit shape 3 mm (0.12”)  
12  
 
10. INPUT SENSITIVITY AND HIGH-PASS FILTER ON/OFF SETTINGS  
The Input sensitivity can be set to +4 dB (factory-preset) or -10 dB for each channel.  
Besides, only the DA-250DH employs the High-pass filter on each channel, which can be set to "ON" or "OFF."  
CAUTION  
These servicing instructions are for use by qualified personnel only. To avoid electric shock, do not  
perform any servicing other than that contained in the operating instructions unless you are qualified to  
do so. Refer all servicing to qualified service personnel.  
Step 1. Unscrew 7 screws securing the top cover of the unit, then detach it.  
Step 2. Change the jumper socket position to "+4 dB" or "–10 dB" for the Input sensitivity as illustrated below.  
When a bridge connection is made;  
Set the input sensitivity with the CH1 jumper socket when Channels 1 and 2 are bridge-connected.  
(Input sensitivity setting for the CH2 is disabled.)  
Input sensitivity setting  
[When set to +4 dB]  
[When set to –10 dB]  
(Factory-preset)  
Jumper socket  
Jumper socket  
2
Viewed from top with the  
top cover detached.  
CH2  
C3H1  
Front panel  
High-pass filter setting (DA-250DH only)  
[When set to OFF]  
[When set to ON]  
(Factory-preset)  
Jumper socket  
Jumper socket  
Step 3. Change the jumper socket position to "ON" or "OFF" for the High-pass filter as illustrated above.  
(DA-250DH only)  
CAUTION  
With the High-pass filter jumper socket kept to the OFF position (factory preset), operating the  
unit for long periods of time while the Peak indicator is illuminated due to excessive input signal  
may damage the connected speakers, possibly resulting in fire.  
Operating the unit with the High-pass filter jumper socket set to the ON position may decrease  
the possibility of speaker damage or fire due to excessive input signal.  
When a bridge connection is made;  
Perform the same setting for both Channels 1 and 2.  
Operating the unit with the different setting may cause unit failure.  
Step 4. Replace the detached top cover.  
13  
 
11. PROTECTION OPERATION LIST  
Failure  
Protection  
Operation Indicator  
Remedy  
Recovery  
Overcurrent due Current limiter activated Peak indicator lights. Remove overload.  
Connecting a correct load  
automatically restores  
normal operation.  
to overload  
when impedance drops  
below the specified  
value.  
Short circuit  
Current limiter activated. Protection indicator  
Check speakers and  
lines for short circuit.  
Turn off the power switch.  
Correct the load, then  
switch on the power.  
Load is disconnected.  
lights.  
Rise in heat sink Load disconnected.  
temperature  
Protection indicator  
lights.  
Check the unit for  
Operation automatically  
correct ventilation and returns to normal when  
(over 100°C)  
overload.  
the temperature decreases.  
Temperature rise Built-in amplifier unit  
Four indicators of  
the corresponding  
channel extinguish.  
inside the unit  
(over 80°C)  
that caused the failure  
halted.  
Abnormal DC  
voltage output  
Load disconnected.  
Protection indicator  
lights.  
Contact the TOA dealer where the unit was  
purchased.  
12. TAMPER-PROOF CAP ATTACHMENT  
To protect the input level control from accidental operation, it is recommended to replace the control knob with  
the supplied tamper-proof cap as illustrated.  
Input level control  
Tamper-proof cap (accessory)  
14  
 
13. CLEANING THE FILTER  
Step 1. Switch off the unit's power.  
Step 2. Remove the ventilation panel as shown in the figure.  
Step 3. Detach the filter inside the ventilation panel.  
Step 4. Clear the filter of dust.  
Step 5. Replace the filter and ventilation panel.  
Ventilation Panel  
2
Detach the panel by pressing on the left or right side.  
3
Filter  
Ventilation Panel  
15  
 
14. BLOCK DIAGRAMS  
14.1. DA-250D  
CH 1  
CH 1 INPUT  
OUTPUT  
OUTPUT 1  
relay  
H
C
E
+
-
Current Limiter  
Short Detector  
+4 dB  
10 dB  
CH 1  
-
Protection Circuit  
input level  
control  
BRIDGE  
OUTPUT  
CH 1 sensitivity  
selection jumper  
OUTPUT 2  
relay  
CH 2 INPUT  
ON  
(+4 dB/-10 dB)  
H
C
E
+
-
Current Limiter  
Short Detector  
OFF  
PARALLEL  
switch  
CH 2  
BRIDGE ON/OFF switch  
OUTPUT  
+4 dB  
10 dB  
CH 2  
Protection Circuit  
-
input level  
control  
CH 2 sensitivity  
selection jumper  
(+4 dB/-10 dB)  
14.2. DA-250DH  
CH 1 INPUT  
CH 1  
OUTPUT  
H
C
E
OUTPUT 1  
relay  
+
OFF  
ON  
-
HPF  
Current Limiter  
Short Detector  
50 Hz  
+4 dB  
10 dB  
CH 1  
CH 1 HPF  
-
input level  
control  
BRIDGE  
OUTPUT  
ON/OFF jumper  
Protection Circuit  
CH 1 sensitivity  
selection jumper  
CH 2 INPUT  
OUTPUT 2  
relay  
(+4 dB/  
-
10 dB)  
ON  
H
C
E
+
-
OFF  
ON  
HPF  
PARALLEL  
switch  
OFF  
BRIDGE ON/OFF  
Current Limiter  
Short Detector  
CH 2  
50 Hz  
OUTPUT  
+4 dB  
10 dB  
switch  
CH 2 HPF  
CH 2  
-
ON/OFF jumper  
Protection Circuit  
input level  
control  
CH 2 sensitivity  
selection jumper  
(+4 dB/-10 dB)  
16  
 
15. DIMENSIONAL DIAGRAM  
Unit: mm (inches)  
442 (17.4)  
465 (18.31)  
482 (18.98)  
17  
 
16. SPECIFICATIONS  
16.1. DA-250D CU  
Power Source  
120 V AC, 50/60 Hz  
Amplification system  
Power Consumption  
Digital class D  
120 W (based on UL/CSA standards)  
650 W (rated output 4 Ω x 2)  
420 W (rated output 8 Ω x 2)  
Input  
2 circuits, +4 dB* (1.23 V, input level control in maximum position),  
10 kΩ, electronically-balanced, removable terminal block (3 pins)  
CH 1 mode ON/OFF switch (ON: PARALLEL, OFF: Each ch)  
Rated Output  
2 channels: 250 W x 2 (4 Ω), 170 W x 2 (8 Ω)  
1 channel (BRIDGE): 500 W (8 Ω)  
M4 screw terminal, distance between barriers: 8.8 mm (0.35")  
Frequency Response  
20 – 20,000 Hz (±1 dB)  
Total Harmonic Distortion 0.1% (1 kHz), 0.3% (20 – 20,000 Hz)  
Protection Circuit  
Protection against excessive current flow due to overload, short circuit,  
unusual DC voltage output, and heat sink temperature rise (over 100°C)  
S/N Ratio  
100 dB (A-weighted)  
70 dB (A-weighted)  
Crosstalk  
LED Indicator  
Power (blue) x 1, Input (green) x 2, Output (yellow) x 2, Peak (red) x 2,  
Protect (red) x 2  
Cooling  
Forced air cooling  
Operating Temperature  
Operating Humidity  
Finish  
–10°C to +40°C (14°F to 104°F)  
Under 90% RH (no condensation)  
Panel: Aluminum, black, alumite  
Case: Plated steel sheet  
Dimensions  
Weight  
482. (w) x 44 (h) x 401.8 (d) mm (18.98" x 1.73" x 15.82")  
5 kg (11.02 lb)  
* 0 dB = 0.775 V  
Note: The design and specifications are subject to change without notice for improvement.  
• Accessories  
Power cord (2 m) ................................................................. 1  
Removable terminal plug (3 pins) ........................................ 2  
Tamper-proof cap ................................................................ 2  
18  
 
16.2. DA-250DH CU  
Power Source  
120 V AC, 50/60 Hz  
Digital class D  
Amplification system  
Power Consumption  
120 W (based on UL/CSA standards)  
580 W (rated output 19.6 Ω x 2)  
Input  
2 circuits, +4 dB* (1.23 V, input level control in maximum position),  
10 kΩ, electronically-balanced, removable terminal block (3 pins)  
CH 1 mode ON/OFF switch (ON: PARALLEL, OFF: Each ch)  
Rated Output  
Frequency Response  
2 channels: 250 W x 2 (19.6 Ω)  
1 channel (BRIDGE): 500 W (39.2 Ω)  
M4 screw terminal, distance between barriers: 8.8 mm (0.35")  
20 – 20,000 Hz (±1 dB):  
HPF OFF  
50 – 20,000 Hz (–3 dB, +0 dB): HPF ON  
(selectable with the inner jumper)  
Total Harmonic Distortion 0.1% (1 kHz), 0.3% (20 – 20,000 Hz): HPF OFF  
0.1% (1 kHz), 0.3% (100 – 20,000 Hz): HPF ON  
Protection Circuit  
Protection against excessive current flow due to overload, short circuit,  
unusual DC voltage output, and heat sink temperature rise (over 100°C)  
S/N Ratio  
100 dB (A-weighted)  
70 dB (A-weighted)  
Crosstalk  
LED Indicator  
Power (blue) x 1, Input (green) x 2, Output (yellow) x 2, Peak (red) x 2,  
Protect (red) x 2  
Cooling  
Forced air cooling  
Operating Temperature  
Operating Humidity  
Finish  
–10°C to +40°C (14°F to 104°F)  
Under 90% RH (no condensation)  
Panel: Aluminum, black, alumite  
Case: Plated steel sheet  
Dimensions  
Weight  
482. (w) x 44 (h) x 401.8 (d) mm (18.98" x 1.73" x 15.82")  
5 kg (11.02 lb)  
* 0 dB = 0.775 V  
Note: The design and specifications are subject to change without notice for improvement.  
• Accessories  
Power cord (2 m) ................................................................. 1  
Removable terminal plug (3 pins) ........................................ 2  
Tamper-proof cap ................................................................ 2  
19  
 
133-22-125-50  
 

Texas Instruments Cell Phone 3000 MCU User Manual
Texas Instruments Network Card TMS320C6747 DSP User Manual
Texas Instruments Stereo Amplifier TPA102 MSOP User Manual
Timex Watch M805 User Manual
Toshiba Projection Television 50HM66 User Manual
Traulsen Refrigerator UHT27 R User Manual
Tricity Bendix Cooktop SE310 User Manual
Tripp Lite TV Cables P560 020 User Manual
ViewSonic Projector S50 X50 User Manual
Walker Indoor Furnishings V42Y79B User Manual